Sensata ISOSLICE-8 4 Analog Output Isoslice Unit User Manual
- June 3, 2024
- Sensata
Table of Contents
ISOSLICE-8
4 Analog Output Isoslice Unit
User Manual
ISOSLICE-8 4 Analog Output Isoslice Unit
ISOSLICE-8
This is the unit with 4 analog outputs.
Channel Number and Output Range Selection
The channel number is set up using the 12-way dip switch.
If all switches are off, the channel number is 1 (invalid):
Address Switches| Action|
---|---|---
8| add 1
7| add 2
6| add 4
5| add 8
4| add 16
3| add 32
2| add 64
Switches
1 = On, 0 = Off
Channel| 2| 3| 4| 5| 6| 7| 8
1| 0| 0| 0| 0| 0| 0| 0
2| 0| 0| 0| 0| 0| 0| 1
3| 0| 0| 0| 0| 0| 1| 0
4| 0| 0| 0| 0| 0| 1| 1
5| 0| 0| 0| 0| 1| 0| 0
6| 0| 0| 0| 0| 1| 0| 1
7| 0| 0| 0| 0| 1| 1| 0
8| 0| 0| 0| 0| 1| 1| 1
9| 0| 0| 0| 1| 0| 0| 0
10| 0| 0| 0| 1| 0| 0| 1
11| 0| 0| 0| 1| 0| 1| 0
12| 0| 0| 0| 1| 0| 1| 1
13| 0| 0| 0| 1| 1| 0| 0
14| 0| 0| 0| 1| 1| 0| 1
15| 0| 0| 0| 1| 1| 1| 0
16| 0| 0| 0| 1| 1| 1| 1
The ISOSLICE-8 has been factory calibrated for two different ranges for each
output.
These can be chosen using switches 9 to 12 on the 12-way switch.
Range Switches | Output | Off | On |
---|---|---|---|
9 | 1 | 4-20 mA | 0-10V |
10 | 2 | 4-20 mA | 0-10V |
11 | 3 | 4-20 mA | 0-10V |
12 | 4 | 4-20 mA | 0-10V |
Output Type Selection
The output type is set up using the 4-way dip switch
Range Switches | Output | Off | On |
---|---|---|---|
1 | 1 | mA | Voltage |
2 | 2 | mA | Voltage |
3 | 3 | mA | Voltage |
4 | 4 | mA | Voltage |
Calibration of the ISOSLICE-8
There are 2 push buttons and an LED.
The units have been calibrated for 4-20 mA on all channels so recalibration
should not be necessary.
Choose the output channel to calibrate by pushing the raise or lower button when the LED is green. It will flash red between one and four times indicating the output to be calibrated.
When the output has been chosen push and releases both buttons.
The LED will go red.
Press the raise/lower buttons to adjust the output value until correct.
Push and release both buttons. The LED will go off briefly (to indicate it has
learned and saved a new value) and then change to green.
Push and release both buttons
The LED will go amber.
Press the raise/lower buttons to adjust the output value until correct
Push and release both buttons, the led will again go off briefly and then
change to green.
ISOSLICE-8 errors
Green LED flashing (E 2):
The EEPROM checksum indicates the EEPROM is corrupt. Push and release both
buttons to clear the error. Recalibration of all outputs will be required.
Red led flashing (E 5):
The address chosen using the Address switches is invalid.
Connections
7. Output 4 mA, V +ve
8. Output 4 mA, V -ve,
12.
5. Output 3 mA, V +ve
6. Output 3 mA, V -ve,
11.
1. Output 1 mA, V +ve
2. Output 1 mA, V -ve
9.
3. Output 2 mA, V +ve
4. Output 2 mA, V -ve,
10.
Whilst every effort has been taken to ensure the accuracy of this document, we
accept no responsibility for damage, injury, loss, or expense resulting from
errors or omissions, and reserve the right of amendment without notice.
This document may not be reproduced in any way without the prior written
permission of the company
AUG 2022