weidmuller A Series Modular Terminal Blocks Instruction Manual
- June 12, 2024
- Weidmuller
Table of Contents
INSTALLATION INSTRUCTIONS
& CONDITIONS FOR SAFE USE
II 2 GD
Ex eb IIC Gb
Modular TERMINAL Blocks: A- Series
TÜV 16 ATEX 7909 U
IECEx TUR 16.0036 U
Notified Body No. of Ex – QA: 0344
Label print on package unit: 0344
TÜV21UKEX7001U
Approved Body No. of UK Ex – QA: xxxx
(see product marking)
A Series Modular Terminal Blocks
Standards:
EN 60079-0:2018 and EN 60079-7:2015 A1:2018
IEC 60079-0: 7th Edition and IEC 60079-7: 5.1th Edition
Modular Terminal Blocks: A3C 2.5
Version:| A3C 2.5| Order No
1521740000
---|---|---
in conjunction with:| A3C 2.5 PE| Order No
1521670000
Accessories:| Type| Order No
end plate| AEP 3C 2.5| 1.52E+09
end bracket| AEB 35 SC/1| 1.99E+09
Terminal rail| TS 35/… acc.to DIN EN 60715
Cross-connection| Plugable
ZQV 2.5N/2
ZQV 2.5N/3
ZQV 2.5N/4
ZQV 2.5N/5
ZQV 2.5N/6
ZQV 2.5N/7
ZQV 2.5N/8
ZQV 2.5N/9
ZQV 2.5N/10| Order No
1527540000
1527570000
1527590000
1527620000
1527630000
1527640000
1527670000
1527680000
1527690000
Insulation material:
– Type | Wemid |
---|---|
– Tracking resistance (A) to IEC 60112 | CTI ≥ 600 |
– Flammability class to UL 94 | V0 |
– Operating temperature range | -60°C…+110°C (insulating material limit) |
– Ambient temperature range | -60°C…+40°C (for T6 applications) |
– Ambient temperature range | -60°C…+55°C (for T5 applications) |
– Ambient temperature range | -60°C…+70°C (for T4 applications) |
* in all colours
Technical data according to IEC/EN 60079-7 (increased safety “eb”):
| A3C 2.5| A3C 2.5 PE
---|---|---
– Rated voltage| 550 V|
– Rated current| 21 A / ΔT ≤ 40 K|
– Rated current with ZQV| 21 A / ΔT ≤ 40 K|
– Contact resistance with rated conductor, 2.5 mm²| 0,8 mΩ|
– Rated conductor cross section| 2,5 mm²| 2,5 mm²
– Conductor cross section solid| 0,5 – 2,5 mm²| 0,5 – 2,5 mm²
– Conductor cross section stranded| 0,5 – 2,5 mm²| 0,5 – 2,5 mm²
– Conductor cross section flexible| 0,5 – 2,5 mm²| 0,5 – 2,5 mm²
– cross section, American Wire Gauge| 28 – 12 AWG| 28 – 12 AWG
– Stripping length| 10 mm| 10 mm
IECEx / ATEX / UKCA Terminal and Cross-Connection Arrangements:
Max voltage data according to IEC/EN 60079-7 in conjunction with protective
earth terminal blocks of the A-Series, (increased safety “eb”):
Application Case
A – Continuous no difference between one or two cross connections 440 V
C – Adjacent – separated by an end plate no difference between one or two
cross-connections 550 V
D – Intermediate – bridging one or more unconnected terminals (e.g. every 3rd
terminal) no difference between one or two cross connections 352 V
F – Next to a protective conductor terminal (earth) with end plate 550 V
H – Cross-connection with twin parallel 220 V
Note:
If smaller cross sections than the rated cross section are used, the belonging
lower current has to be laid down in the IECEx/EC-Type Examination Certificate
of the complete apparatus.
Mounting instructions:
The Feed-through terminals and PE terminals of the A-series are suitable for application in enclosures in atmospheres with flammable gases or combustible dust. For use in flammable gases these enclosures must satisfy the requirements according to IEC/EN60079-0 and IEC/EN60079-7. For use in combustible dust these enclosures must satisfy the requirements according to IEC/EN60079-0 and IEC/EN60079-31. Regarding the use of accessories the instructions of the manufacturer must be followed.
Schedule of Limitations:
The Feed-through terminals and PE terminals of the A-series are suitable for
use in enclosures in atmospheres with flammable gases or combustible dust. For
flammable gases these enclosures must satisfy the requirements according to
IEC/EN60079-0 and IEC/EN60079-7. For combustible dust the enclosure must
satisfy the requirements according to IEC/EN60079-0 and IEC/EN60079-31.
The enclosure shall be constructed to block all sun and UV light from
affecting the terminal blocks. The terminal blocks shall be placed inside a
suitable certified IP54 enclosure in type of protection “e” for gas
atmosphere. For dust atmosphere the terminal blocks shall be mounted inside a
suitable certified enclosure (EN60079-31) in type of protection “t”.
Under normal operating conditions the temperature rise of the terminal blocks
is maximum 40 K, measured at the maximum permitted rated current. Due to the
above mentioned, the terminal blocks may be used in apparatus of temperature
classes T6..T1 as long as the terminal block ambient temperature range is not
exceeded. No part of terminal block must exceed 110 °C under any condition.
T6 (- 60°C … +40 °C)
T5 (- 60°C … +55 °C)
T4 (- 60°C … +70 °C)
When using the types A3C 2.5 and A3C 2.5 PE especially with other terminal
blocks series or sizes or accessories the requirements for clearance and
creepage distances according to IEC/EN60079-7 must be observed. Regarding the
use of covers, cross-connectors and end brackets the instructions of the
manufacturer must be followed.
For cross connection accessories current rating, resistance across the
terminal please refer to the table under “Technical data” above.
If smaller conductor cross sections than the rated conductor cross sections
are used, then the corresponding lower current shall be stated in the
Certificate of the complete apparatus.
No other wire sizes or types than the ones specified in instructions must be
used. The terminal blocks must either be mounted next to another block of the
same type and size or with an end plate.
– Cross connections with blank ends shall not be used.
– Manually cut cross connections shall not be used.
Essential Health and Safety Requirements:
Concerning ESRs this Schedule verifies compliance with the Annex II of ATEX / Schedule 1 of UKCA directive and Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations 2016 only. By placing the product on the market, the manufacturer declares compliance with other relevant Directives, and all other safety related requirements including those of Annex II / Schedule 1 of these Directives.
Weidmüller Interface GmbH Co. KG; Klingenbergstraße 26, 32758
Detmold-Germany
Version: A3C 2.5; 10652171
Index: 04
Date: 11.2021
References
Read User Manual Online (PDF format)