Raychem T-100 Splice and Tee Connection Kit Instruction Manual
- June 5, 2024
- Raychem
Table of Contents
Raychem T-100 Splice and Tee Connection Kit
INSTRUCTION
TOOLS NEEDED
WARNING:
To prevent electrical shock or fire, this product must be installed correctly.
Water ingress must be avoided before and during the installation.
CAUTION:
Prolonged or repeated contact with the sealant in the core sealer may cause
skin irritation. Wash hands thoroughly. Overheating or burning the sealant
will produce fumes that may cause polymer fume fever. Avoid contamination of
cigarettes or tobacco. Consult MSDS VEN 0058 for further information.
WARNING:
The purchaser should make the manufacturer aware of any external effects or
aggressive substances that the equipment may be exposed to.
ATEX and IECEx approved
Rated voltage: 480 Vac (when used with nVent RAYCHEM VPL4)
Ambient temperature: –55°C to +56°C
For ambient temperatures >+40°C
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas (for
example nVent RAYCHEM GL-38-M25-METAL).
For voltages >254Vac and nVent RAYCHEM BTV, QTVR, XTV, KTV or HTV heating
cables:
Use a power cable with continuous temperature resistance of minimum +90°C.
Maximum pipe temperature:
Heater type
|
T max continuous
| T max intermittent 1000h cumulative| T max power
off
---|---|---|---
BTV| 65°C| 85°C| –
QTVR| 110°C| 110°C| –
XTV| 121°C| 250°C| –
KTV| 150°C| 250°C| –
HTV| 205°C| 260°C| –
VPL| See tables below| –| 260°C
VPL: Maximum pipe temperature depending on heating cable reference and voltage
Voltage (VAC)| 120| 208| 230| 240| 254|
277| 385| 400| 480
---|---|---|---|---|---|---|---|---|---
5VPL1-CT| 230| | | | | | | |
10VPL1-CT| 205| | | | | | | |
15VPL1-CT| 170| | | | | | | |
20VPL1-CT| 150| | | | | | | |
5VPL2-CT| | 235| 230| 230| 225| 225| | |
10VPL2-CT| | 220| 210| 205| 200| 195| | |
15VPL2-CT| | 200| 180| 170| 145| 105| | |
20VPL2-CT| | 150| 150| 150| | | | |
5VPL4-CT| | | | | | | 230| 230| 230
10VPL4-CT| | | | | | | 215| 215| 205
15VPL4-CT| | | | | | | 195| 195| 160
20VPL4-CT| | | | | | | 150| 150| 150
INSTALLATION
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>