Raychem Elexant 450c Thermostat Instruction Manual
- June 5, 2024
- Raychem
Table of Contents
Elegant 450c
CONNECT AND PROTECT
Operation Manual
PROGRAM START
Quickstart: | Navigation: SELECTION back ( <- ) or next ( -> ) |
---|---|
Language selection | Select your language from the language menu: |
EN; DE; NL; DA; FR; IT; SV; NO; FI; RU; CZ; PL; SK; LT
next ( -> )
Checking sensor connection| The unit is automatically executing a connection
check of sensors 1 and 2. If there is no sensor connected, the unit will stop
the Quickstart process. In this case, power off, connect a sensor, and power
on again.
Note: 1 Sensor needs to be connected at least. back ( <- ) or next ( ->
)
Country selection| Select a country in this menu:
DE; AT; CH; GB; FR; IT; PL; CZ; DK; SE; BE; RU; NO; LT; SK; NL; FI; IE
back ( <- ) or next ( -> )
Date input| Use the +/- button to select the day, month, and year. back ( <-
) or next ( -> )
Time input| Use the +/- button to set the hour and minute. back ( <- ) or
next ( -> )
Select heating cable type| Select the installed pipe freeze protection
heating cable:
10XL2-ZH / 15XL2-ZH / 26XL2-ZH / 31XL2-ZH / FS-10C-2X / Other systems back (
<- ) or next ( -> )
Operation mode| Select an operation mode:
AMBIENT: Ambient temperature measurement. The operation will be based on PASC
(Proportional ambient temperature system control).
The unit is working in an energy efficiency mode depending on the outside
temperature to operate the heating cable based on an internally calculated
duty cycle.
LINE: Pipe/line temperature measurement.
Assignment of sensors: Sensor 1 for heating circuit 1; sensor 2 for heating
circuit 2; a revision of this assignment can be done later in the parameter
settings.
back ( <- ) or next ( -> )
Parameter settings| Default values are set for each parameter. Change the
default values by clicking on the arrow sign for each value and entering a new
value.
back ( <- ) or next ( -> )
Pipe diameter| Select pipe diameter from the range DN 10 up to DN 125. back (
<- )
Set min. ambient temperature| The minimum ambient temperature is the minimum
expected temperature outside the building. This parameter influences the duty
cycle duration. Use the +/- keys to select a temperature. Clicking on the
“back” icon ( <- ) will store the value and show it in plumbing settings.
Value Range: From –40°C to 0°C back ( <- )
Set temperature*| Select the temperature using the +/- keys.
The minimum temperature is 0°C and the max. temperature is +80°C back ( <- )
Test program start| YES:
The test program runs for 30 minutes, during which all parameters will be
ignored to check the heating cable and connection on site. You can stop the
test program at any time.
Quickstart completed -> Main screen
NO: Quickstart completed – > Main screen
- Note: During Quickstart, the selected parameter is valid for the heating circuits (zone) 1 and 2. An adjustment per heating circuit (zone) can be done for each individual heating zone in the parameter setting menu after Quickstart is completed.
Main Screen
PARAMETER SETTINGS
System|
---|---
Information| General info about the unit name, commissioning date, firmware
version, nVent contact info per country, and unit serial number.
Test program| Test program
YES:
The test program runs for 30 minutes, during which all parameters will be
ignored to check the heating cable and the connection on site. You can stop
the test program at any time.
NO: Back to main menu settings
Reset| Confirm:
Activate the Quick install menu and return all settings to factory
settings. The Quickstart process restarts automatically.
Cancel: Back to main menu settings
Service| Access for nVent service team
Status| Info on the current status of the control unit:
Sensor 1: Open/short or temperature value Sensor 2: Open/short or temperature
value SET Point temperature: Value in °C
Duty cycle: Value will be displayed only in PASC mode
Operation mode: LINE / PASC (heating circuit 1 / heating circuit 2)
Key lock| The unit´s parameter input can be protected by a key lock; Access
code: 3000.
When the key lock is “On”, the setup and timer menus’ are protected by a
password.
The unit can be unlocked by entering the pre-defined password (3000).
After 10 minutes of inactivity on-screen or when the Lock “on” key is pressed,
the unit will automatically lock itself.
To deactivate the Key lock function, enter code 3000 and activate “OFF”. The
key lock code cannot be changed.
Heating Cable & Pipe
| Heating zone 1 Example| Heating zone 2 Example| Parameters|
Note
Mode| ON| / ON| AMBIENT Sensor: ON/OFF LINE Sensor: ON/OFF Default:—
Heating circuit 1: ON; OFF Heating circuit 2: ON; OFF Default: —| Individual
adjustments per heating zone.
Assign a sensor to each heating zone by activating the check mark.
AMBIENT: Ambient temperature measurement by PASC – proportional ambient
temperature measurement. Energy-saving mode; is recommended for multiple pipe
segments.
LINE: Pipe temperature measurement.
Setpoint| +3°C| / +3°C| NTC Sensor:
Range: 0°C to +80°C
PT100 Sensor (with sensor module SM-PT100-2)
Range: 0°C to +245°C Default: +3°C| The set temperature is the temperature to
ensure protect the pipe from freezing or to maintain a certain pipe
temperature.
Select the temperature using the + / – keys for each heating circuit zone
individually.
Heating Cable & Pipe
| Heating zone 1 Example| Heating zone 2 Example| Parameters|
Note
Min. expected ambient temperature| –15°C| / –15°C| Range: –40°C to 0°C
Default: –15°C| Sensor PASC (AMBIENT)
The temperature is the minimal outdoor temperature to be expected and will be
used for the ambient temperature (PASC) algorithm only. It will set the
correct duty cycle for an optimized and energy-saving operation. If the
ambient temperature is below this set point, the relay is 100% ON.
Select the temperature by using the + / – keys.
| | | |
Cable type
XL-TRACE -1| 15XL2-ZH| | Heating cable range:
10XL2-ZH
15XL2-ZH
26XL2-ZH
31XL2-ZH FS-C10-2X
Other systems
Default: —| Select the type of nVent RAYCHEM heating cable used in your
installation, connected to heating zone 1.
Another system can be used if the heating cable type is not known or listed.
Cable type
XL-TRACE -2| | 15XL2-ZH| Heating cable range:
10XL2-ZH
15XL2-ZH
26XL2-ZH
31XL2-ZH FS-C10-2X
Other systems
Default: —| Select the type of nVent RAYCHEM heating cable used in your
installation, connected to heating zone 2.
Another system can be used if the heating cable type is not known or listed.
Pipe diameter| DN 25| / DN 25| Range: DN 10 – DN 125
Default: DN 25| Assign the correct pipe diameter per heating zone 1 and/or 2.
You can change the value from DN 10 up to DN 125. This has an impact on the
ambient temperature sensing mode to define the correct duty cycle.
Note: In the case of multiple pipe sizes per heating zone, select the
bigger size of the pipe network.
Low-temperature alarm| 0°C| / 0°C| Standard NTC Sensor: Range: –40°C to +78°C
Default: 0°C
PT-100 Sensor with SM-PT-100-2:
Range: –40°C to +245°C
Default: 0°C| To determine the low-temperature limit. When the value is
reached, a warning will appear on the screen. The buzzer tone will be active.
The relay will be continuously ON and will not interrupt the unit’s
functioning. The info status main screen will show the actual pipe
temperature.
High-temperature alarm| +65°C| +65°C| Standard NTC Sensor: Range : +2°C to
+90°C Default: +65°C
PT-100 Sensor with SM-PT-100-2:
Range: +2°C to +250°C Default: +65°C| To determine the high-temperature limit;
A warning will appear on the screen when the value is reached.
The relay will be continuously OFF and will not interrupt the unit’s
functioning.
Value range:
+2°C to +90°C /Standard NTC sensor
+2°C to +250°C /Sensor module SM-PT-100-2 for PT-100
Heating Cable & Pipe
| Heating zone 1 Example| Heating zone 2 Example| Parameters|
Note
Heating in case of sensor error| ON| / ON| Fail-Safe: ON/OFF Default: ON| In
case of a sensor error (short/open) the heating output (Relay) can be switched
OFF by activating a checkmark per heating zone.
Default: ON; the heating system will not be switched OFF in sensor failure
mode.
Hysteresis| 2 K| / 2K| Range: 1 – 5
Default: 2K| Adjustable hysteresis above-set point.
General Settings
Language| Choose your language from the language menu.| Languages:
EN; DE; NL; DA; FR; IT; SV; NO; FI; RU; CZ; PL; SK; LT
Country| Select a country in this menu. Your selection defines the default
values used for time format, pipe diameter and insulation thickness, and
customer contact data.| Countries
DE; AT; CH; GB; FR; IT; PL; CZ; DK; SE; BE; RU; NO; LT; SK; NL; FI; IE
Date| Use the up/down arrow keys to select the year.
After a power break of more than 10 days, you need to re-enter the date.|
Default: 00;00,2018
Time| Use up/down arrow keys to set hour and minute.
After a power break of more than 10 days, you need to re-enter the time.|
Default: 00:00
Alarm tone| An alarm tone will go off inside the unit indicating an error
condition. Activate/deactivate the alarm tone by pressing ON/OFF.
Note: Alarm messages will be displayed and the alarm relay will switch
any time in case of a malfunction.| Default: OFF
FACTORY SETTINGS (DEFAULT)
Language | English |
---|---|
Country | None; To be selected |
Date | 01/01/2018 or last saved date |
Time | 00:00 or last saved time |
Operation mode | To be selected |
Heating cable type | To be selected |
Pipe diameter | DN 25 |
Insulation thickness | 30 mm |
SET temperature | +3°C |
Minimum ambient temperature | –15°C |
Heating in sensor failure mode | ON |
Low-temperature limit | –40°C |
High-temperature limit | +85°C |
Low-temperature alarm | 0°C |
High-temperature alarm | +65°C |
Alarm sound | OFF |
Key lock | ON |
**** ERROR / ALARMS AND TROUBLESHOOTING
Error Code | Elegant 450C | Remedy |
---|---|---|
E:2.1 | SENSOR_1_OPEN | Check sensor connection |
E:2.2 | SENSOR_1_SHORT | Check the sensor and replace it |
E:2.3 | SENSOR_2_OPEN | Check sensor connection |
E:2.4 | SENSOR_2_SHORT | Check the sensor and replace it |
E:3.1 | SENSOR_1_TEMP_HIGH | Sensor 1 High-temperature alarm |
E:3.2 | SENSOR_2_TEMP_HIGH | Sensor 2 High-temperature alarm |
E:4.1 | SENSOR_1_TEMP_LOW | Sensor 1 Low-temperature alarm |
E:4.2 | SENSOR_2_TEMP_LOW | Sensor 2 Low-temperature alarm |
E:5 | n/a | |
E:6.0 | n/a | |
E:6.1 | INTERNAL_ERROR | Replace unit |
E:6.2 | INTERNAL_ERROR_RTC | Replace unit |
E:6.3 | INTERNAL_ERROR_PM | Replace unit |
E:6.4 | INTERNAL_ERROR_ADC | Replace unit |
E:6.5 | INTERNAL_ERROR_IP | Replace unit |
E:6.6 | n/a |
Belgique
Tel +32 16 21 35 02
Fax +32 16 21 36 04
salesbelux@nVent.com
Nederland
Tel 0800 0224978
Fax 0800 0224993
salesnl@nVent.com
Our powerful portfolio of brands:
CADDA | ERICO | HOFFMAN | RAYCHEM | SCHROFF | TRACER |
---|
©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services
GmbH or its affiliates. All other trademarks are the property of their
respective owners.
nVent reserves the right to change specifications without notice.
RAYCHEM-OM-EU1838-ELEXANT450c-ML-2108