E-Mon 62-0384 Split-Core Current Sensors Instruction Manual
- June 3, 2024
- E-Mon
Table of Contents
E-Mon 62-0384 Split-Core Current Sensors
INSTALLATION INSTRUCTIONS
E-Mon
1985 Douglas Drive North Golden Valley, MN 55422 www.emon.com
info@emon.com
CURRENT SENSOR ASSEMBLY
STEP 1: For each phase being monitored, you will need one two-piece current sensor assembly. (A three-phase meter will require three (3) current sensor assemblies.) Open the two-piece current sensor assembly by releasing the nylon clamp using a flathead screwdriver.
Fig. 1. 25-200 Amp Interior Dim: 1″x 6/16”.
STEP 2: Using a flathead screwdriver, press the tab on the nylon clamp to open the current sensor assembly.
Fig. 2. 800-1600 Amp Interior Dim: 3.375″x 6″.
STEP 3: Reassemble current sensor assembly around the conductor(s) to be monitored. Be sure that the current sensor halves marked are both facing the load side of the conductor being monitored. The colored arrow will be on the source side of the conductor being monitored and MUST be pointed in a clockwise direction around the conductor being monitored. Tighten nylon clamp to complete assembly. Using a flathead screwdriver, press the tab on the nylon clamp to open the current sensor assembly.
Fig. 3. The arrow on the current sensor assembly should point clockwise.
IMPORTANT
When looking from the source side of the conductor(s) being monitored, you should see the arrow on the current sensor assembly, and the arrow should be pointing clockwise around the conductor(s) being monitored. If the arrow is not on the source side, inaccurate readings may result.
SPLIT-CORE CURRENT SENSORS
Model Numbers
Model #| Amperage| Interior Dim.
CS25| 25 amp| 7/8” x 1 1/2”
CS50| 50 amp| 7/8” x 1 1/2”
CS100| 100 amp| 7/8” x 1 1/2”
CS200| 200 amp| 7/8” x 1 1/2”
CS400| 400 amp| 1 1/2” x 2 3/4”
CS800| 800 amp| 3 1/4” x 4 1/2”
CS1600| 1600 amp| 3 1/4” x 4 1/2”
CS3200| 3200 amp| 5 7/16” x 7 7/8”
All current sensors are split-core type. (Solid-core option available; specify when ordering.) All current sensors shipped in complete sets of three (3).The above split-core current sensors are supplied with E-Mon D-Mon® Class 1000, 2000, 2100, 3000, 4000 and 4100 meters. Current sensors can be installed up to 2000 feet away from meter (500 feet for Class 3000 meters). Leads supplied are 3′ in length and can be extended up to 2000 feet using low voltage #14-22 AWG wire. (stranded/twisted not required) See local electrical codes for proper sizing. (Continued on next page)
SPLIT-CORE CURRENT SENSORS
When paralleling current sensors, the meter reading must be multiplied by the
number of sets of current sensors in parallel.Solid-core current sensors
available in 100 & 200 amp configuration. Specify when ordering.By using this
E-Mon literature, you agree that E-Mon will have no liability for any damages
arising out of your use or modification to, the literature. You will defend
and indemnify E-Mon, its affiliates and subsidiaries, from and against any
liability, cost, or damages, including attorneys’ fees, arising out of, or
resulting from, any modification to the literature by you.
E-Mon
1985 Douglas Drive North Golden Valley, MN 55422 www.emon.com
info@emon.com ® U.S. Registered
Trademark © 2014 E-Mon 62-0384—02 M.S. Rev. 11-14 Printed in United States
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>