HUBBELL HCX Series Emergency Unit LED Exit Sign Models Instruction Manual
- June 3, 2024
- Hubbell
Table of Contents
HUBBELL HCX Series Emergency Unit LED Exit Sign Models
Installation Instructions
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
- Do not use outdoors.
- Do not let power supply cords touch hot surfaces.
- Do not mount near gas or electric heaters.
- Use caution when servicing batteries.
- Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Caution: To avoid shattering: Do not operate the lamp in excess of rated voltage, protect the lamp against abrasion and scratches and against liquids when the lamp is operating, and dispose of the lamp with care.
- Do not store or place flammable materials near the lamp.
- Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS
Product Over View
END MOUNT
CEILING/BACK MOUNT INSTALLATION INSTRUCTIONS
Remove the faceplate by pressing the snaps at the top or bottom of the
housing.
Remove the cover located at the top or end of the housing.
Connect 18” jumper leads (provided) to AC wiring in the outlet box. Fasten the
mounting plate (provided) to the outlet box. Feed wires through the canopy and
fasten the canopy to the mounting plate. Snap exit housing onto the canopy.
Remove the back plate by releasing two large snaps located inside the housing.
Remove appropriate knockouts from the backplate and attach them to the outlet
box (mounting plate not required). Route and connect leads at the upper corner
of the housing. Connect batteries by observing polarity. Loosen lamp head
adjustment screws. Position lamp heads as required. Retighten. Insert
directional chevrons as required. Press the faceplate onto the housing. To
install the second faceplate (if required) remove the backplate by pressing in
the snaps at the top or bottom of the housing. Then release the two large
snaps located inside the housing. Install faceplate.
Location
CHANGING LAMP HEAD LOCATIONS OR REMOVING LAMPHEADS – END MOUNT
Disconnect lamp leads at the printed circuit board. Remove the lamp head from
the housing by squeezing press-fit tabs from the inside of the housing.
Remove the lamp head hole plug in a new location.
Route lamp leads through new hole location and press fit lamp head into a new
location. Reconnect the lamp leads to the printed circuit board (refer to the
wiring diagram). Press the fit hole plugs into the old lamp head hole
location.
Wiring Diagram
Troubleshooting
The unit does not light
- Check wiring connections.
The emergency circuit does not work
- Batteries are shipped uncharged and disconnected. Connect battery leads and charge before testing.
- Make sure the charger board is properly seated.
- Check wiring connections.
Maintenance
Signs should be tested and maintained in accordance with National Electrical
Code and NFPA 101 Life Safety Code
requirements. It is recommended that emergency exit signs be tested for 30
seconds once a month and for 90
minutes once a year.
Recycling Information
All thermoplastic parts are recyclable. All cartons contain recycled
materials. Please recycle responsibly.
NOTICE:
Emergency model exit signs contain rechargeable sealed lead-acid batteries
which must be recycled or disposed of properly.
Hubbell Lighting, Inc. Life Safety Products
Copyright © Hubbell Lighting, Inc., All Rights Reserved
- Specifications are subject to change without notice.
- Printed in the U.S.A.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>