Current Interrupting: Certified for current interrupting at
full rated current -
Dielectric Voltage: Withstands 1,500V minimum
-
Trip Level: 4 to 6 mA
-
Trip Time: .025 second nominal
-
Frequency: 60 Hz
-
Voltage: 120V AC +10% – 15% (102V to 132V)
-
Amperage: 15A/20A, 20A Feed Thru
-
Maximum Interrupting Capacity: 10,000A
FAQ
Q: What is the maximum interrupting capacity of the GFCI receptacle?
A: The maximum interrupting capacity is 10,000A.
Q: What wire sizes are accommodated by the terminals?
A: The terminals accommodate #14-#10 AWG copper stranded or solid conductor only.
Ground Fault Products
Heavy Duty Commercial Tamper-Resistant and Weather-resistant GFCI Receptacles
Features
- Patented shutter design for tamper-resistant protection
- Meets NEC requirements for weather resistance (406.9), UV and corrosion resistance for harsh and damp applications
- Patented AUTOGUARD® self-test technology
- Protects against line and load reversal, no power to the face or downstream if the device is miswired
- Single LED status indicator – green indicates power, red indicates a trip, flashing red indicates end-of-life
Ordering Information
- Description Color UPC Catalog Number
- 15 A, 125V, Style White 883778999345 GFRTW15W Line®,
- AUTOGUARD® self-test GFCI receptacle, tamper-resistant and weather-resistant, flush face, back and side wired, tri-drive screws
Listings
- UL Listed – Canadian and U.S.
- UL 943 Class A for GFCIs UL File E41978
- Meets ADA Standards
- Meets all NEC® and CEC requirements
- CSA Certified
- NEMA® WD-6 ANSI 73 Compliant
Specifications
- Face: Nylon
- Base: Nylon
- Power Contacts: Brass
- Ground Contacts: Brass
- Mounting Strap: Zinc plated steel
- Mounting Screws: Zinc plated steel
- Auto-Ground Staple: Stainless steel
Performance
Electrical
- Current Interrupting: Certified for current interrupting at full-rated current
- Dielectric Voltage: Withstands 1,500V minimum
- Trip Level: 4 to 6 mA
- Trip Time: .025 second nominal
- Frequency: 60 Hz
- Voltage: 120V AC +10% – 15% (102V to 132V)
- Amperage: 15A/20A, 20A Feed Thru
- Maximum Interrupting Capacity: 10,000A
Mechanical
- Product Identification: Ratings are a permanent part of the device
- Terminal Accommodation: #14-#10 AWG copper stranded or solid conductor only
- Terminal Identification: Terminals identified in accordance with UL 498 and CSA
Environmental
- Flammability: UL 94V-2
- Operating Temperature: -35°C to 66°C or -30°F to 150°F
Accessories
- Wallplates for duplex openings
- Dimensions in Inches (mm)
Online Resources
- Customer Use Drawing eCatalog
- Installation Instructions
CONTACT
- Hubbell Wiring Device-Kellems
- Hubbell Incorporated (Delaware)
- 40 Waterview Drive
- Shelton, CT 06484
- Phone 800-288-6000
- Fax 800-255-1031
- Specifications are subject to change without notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>