GOODWE GW700-XS Grid Tied PV Inverter Installation Guide

June 5, 2024
GOODWE

GOODWE logo

GW700-XS Grid-Tied PV Inverter
Installation Guide

XS Series
(GW700-XS | GW1000-XS | GW1500-XS | GW2000-XS | GW2500-XS |
GW3000-XS | GW2500N-XS | GW3000N-XS | GW3KB-XS | GW3300-XS)
V1.0-2022-04-11

Safety Precautions

General Disclaimer

  • The information in this quick installation guide is subject to change due to product updates or other reasons. This guide cannot replace the product labels or the safety precautions in the user manual unless otherwise specified. All descriptions here are for guidance only.
  • Before installations, read through the quick installation guide. For additional information, please see the user manual.
  • All operations should be performed by trained and knowledgeable technicians who are familiar with local standards and safety regulations.
  • Check the deliverables for correct model, complete contents, and intact appearance. Contact the manufacturer if any damage is found or any component is missing.
  • Use insulating tools and wear personal protective equipment when operating the equipment to ensure personal safety. Wear anti-static gloves, clothes, and wrist strips when touching electronic components to protect the inverter from damage. The manufacturer shall not be liable for any damage caused by static electricity.
  • Strictly follow the installation, operation, and configuration instructions in this guide and user manual. The manufacturer shall not be liable for equipment damage or personal injury if you do not follow the instructions. For more warranty details, please visit https://en.goodwe.com/warranty.

Safety Disclaimer
Warning
DC Side:

  1. Ensure the component frames and the bracket system are securely grounded.
  2. Connect the DC cables using the delivered PV connectors. The manufacturer shall not be liable for equipment damage if other connectors are used.
  3. Ensure the DC cables are connected tightly, securely, and correctly. Inappropriate wiring may cause poor contacts or high impedances, and damage the inverter.
  4. Measure the DC cable using the multimeter to avoid a reverse polarity connection. Also, the voltage should be under the max DC input voltage. The manufacturer shall not be liable for the damage caused by reverse connection and extremely high voltage.
  5. The PV modules used with the inverter must have an IEC61730 Class A rating.

AC Side:

  1. The voltage and frequency at the connecting point should meet the on-grid requirements.
  2. Additional protective devices like circuit breakers or fuses are recommended on the AC side. Specification of the protective device should be at least 1.25 times the rated AC output rated current.
  3. PE cable of the inverter must be connected firmly. The resistance between the neutral wire and the earth cable is less than 10Ω.
  4. You are recommended to use copper cables as AC output cables. If you prefer aluminum cables, remember to use copper to aluminum adapter terminals.

Product :

  1. Do not apply mechanical load to the terminals, otherwise, the terminals can be damaged.

  2. All labels and warning marks should be visible after the installation. Do not scrawl, damage, or cover any label on the device.

  3. Unauthorized dismantling or modification may damage the equipment, the damage is not covered under the warranty.

  4. Install the inverter away from a high magnetic field to avoid electromagnetic interference. If there is any radio or wireless communication equipment below 30MHz near the inverter, you have to:
    • Install the inverter at least 30m far away from the wireless equipment.
    • Add a low pass EMI filter or a multi-winding ferrite core to the DC input cable or AC output cable of the inverter.

  5. Warning labels on the inverter are as follows.

| HIGH VOLTAGE HAZARD. Disconnect all incoming power and turn off the product before working on it.| | Delayed discharge. Wait 5 minutes after power off until the components are completely discharged.
---|---|---|---
| Read through the guide before working on this device.| | Potential risks exist. Wear proper PPE before any operations.
| High-temperature hazard. Do not touch the product under operation to avoid being burnt.| | Grounding point. Indicates the position for connecting the PE cable.
| CE marking| | Do not dispose of the inverter as household waste. Discard the product in compliance with local laws and regulations, or send it back to the manufacturer.

Check before Power-on

No. Check Item
The product is firmly installed at a clean place that is well-ventilated and

easy-tooperate.
2| The PE, DC input, AC output, and communication cables are connected correctly and securely.
3| Cable ties are intact, routed properly and evenly.
4| Unused ports and terminals are sealed.
5| The voltage and frequency at the connection point meet the inverter grid connection requirements.

EU Declaration of Conformity

GoodWe Technologies Co., Ltd. hereby declares that the inverter with wireless communication modules sold in the European market meet the requirements of the following directives:

  • Radio Equipment Directive 2014/53/EU (RED)
  • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
  • Waste Electrical and Electronic Equipment 2012/19/EU
  • Registration, Evaluation, Authorisation, and Restriction of Chemicals (EC) No 1907/2006 (REACH)

GoodWe Technologies Co., Ltd. hereby declares that the inverter without wireless communication modules sold in the European market meets the requirements of the  following directives:

  • Electromagnetic compatibility Directive 2014/30/EU (EMC)
  • Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
  • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
  • Waste Electrical and Electronic Equipment 2012/19/EU
  • Registration, Evaluation, Authorization, and Restriction of Chemicals (EC) No 1907/2006 (REACH)
    You can download the EU Declaration of Conformity on https://en.goodwe.com.

LED Indicators

Indicator Status Description
Power ![GOODWE GW700 XS Grid Tied PV Inverter - icon3](https://manuals.plus
/wp-content/uploads/2022/07/GOODWE-GW700-XS-Grid-Tied-PV-Inverter-icon3.png)

ON = WiFi is connected/active.
BLINK 1 = WiFi system is resetting.
BLINK 2 = WiFi is not connected to the router.
BLINK 4 = WiFi server problem.
BLINK = RS485 is connected.
OFF = WiFi is not active.
Operating| ON = The inverter is feeding power.
OFF = The inverter is not feeding power at the moment.
Faulty| ON = A fault has occurred.
OFF = No fault.

Product Introduction

Parts

GOODWE GW700 XS Grid Tied PV Inverter - fig1

  1. DC Switch(optional)
  2. PV Input Terminal
  3. WiFi/LAN/4G Communication Module Port
  4. DRED/CT/Remote Shutdown Communication Cable Port(optional)
  5. AC Output Terminal
  6. PE Terminal
  7. Indicator
  8. LCD(optional)
  9. Button(optional)
  10. Heat Sink
  11. Mounting Plate

Dimensions

GOODWE GW700 XS Grid Tied PV Inverter - fig2

Inverter Installation

GOODWE GW700 XS Grid Tied PV Inverter - fig3

Space Requirements

GOODWE GW700 XS Grid Tied PV Inverter - fig4

Angle Requirements

GOODWE GW700 XS Grid Tied PV Inverter - fig5

Installing the Inverter

GOODWE GW700 XS Grid Tied PV Inverter - fig6

GOODWE GW700 XS Grid Tied PV Inverter - fig7

Electrical Connection

PE Cable

GOODWE GW700 XS Grid Tied PV Inverter - fig8

AC Cable

GOODWE GW700 XS Grid Tied PV Inverter - fig9

AC-1 Connector

GOODWE GW700 XS Grid Tied PV Inverter - fig10

AC-2 Connector

GOODWE GW700 XS Grid Tied PV Inverter - fig11

GOODWE GW700 XS Grid Tied PV Inverter - fig12

DC Cable

GOODWE GW700 XS Grid Tied PV Inverter - fig13

MC4

GOODWE GW700 XS Grid Tied PV Inverter - fig14

DEVALAN

GOODWE GW700 XS Grid Tied PV Inverter - fig15GOODWE GW700 XS Grid Tied PV Inverter -
fig16

RS485 Communication Cable

No. Function
1 N/A
2 N/A
3 RS485-
4 N/A
5 N/A
6 RS485+
7 RS485-
8 RS485+

GOODWE GW700 XS Grid Tied PV Inverter - fig18

For Australia only: DRED Communication Cable

No. Function
3 DRM1/5
4 DRM2/6
5 DRM3/7
6 DRM4/8
7 REGEN
8 COM/DRM0

GOODWE GW700 XS Grid Tied PV Inverter - fig20

CT Communication Cable

No. Function
1 CT-
2 CT+

GOODWE GW700 XS Grid Tied PV Inverter - fig22

For Europe only: Remote Shutdown Communication Cable

No. Function
4 Content +
5 Content –

GOODWE GW700 XS Grid Tied PV Inverter - fig24

WARNING
Keep the Remote Shutdown Terminal installed anyway.

Communication Module

WiFi kit, 4G kit, LAN kit, GPRS, Wi-Fi/LAN Kit module: optional.

Power On and Off

GOODWE GW700 XS Grid Tied PV Inverter - fig26

Commissioning

Commissioning via LCD

GOODWE GW700 XS Grid Tied PV Inverter - fig27

Commissioning via SolarGo APP

GOODWE GW700 XS Grid Tied PV Inverter - fig28

http://www.sems.com.cn/home/solargo

Monitoring via SEMS Portal App

GOODWE GW700 XS Grid Tied PV Inverter - fig29

https://www.semsportal.com/home/AppDownload

For more detailed instructions, scan the QR codes below.

|
---|---
https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW
_XS_User%20Manual- EN.pdf
| https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_
WiFi%20Configuration%20Instruction- EN.pdf

|
---|---
https://en.goodwe.com| https://en.goodwe.com

https://en.goodwe.com/

GoodWe Technologies Co., Ltd.
No. 90 Zijin Rd., New District, Suzhou, 215011, China
www.goodwe.com
service@goodwe.com

https://en.goodwe.com/contact-us.asp

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals