INTERMATIC K4000 Thermal Photo Control Instruction Manual

June 5, 2024
Intermatic

INTERMATIC K4000 Thermal Photo Control LOGO

INTERMATIC K4000 Thermal Photo Contro

WARNING

Risk of Fire or Electric Shock
Disconnect power at the circuit breaker or disconnect switches before beginning installation or servicing.Do NOT use the OFF state of the photocontrol for equipment servicing.

NOTICE
DO NOT MOUNT WITH THE WIRES FACING UP.

Ratings Not LED Compatible

Input Voltage| 120 V Photocontrols| 120-277 V Photocontrols| 208-277 V Photocontrols| 347 V Photocontrols| 480 V Photocontrols
---|---|---|---|---|---
Load Ratings| Tungsten: 15 A, 1800 W

Ballast: 8.3 A, 1000 VA

| Tungsten: 15 A, 1800-4150 W

Ballast: 8.3 A, 1000-2300 VA

| Tungsten: 15 A, 3100-4150 W

Ballast: 8.3 A, 1700-2300 VA

| Tungsten: 15 A, 5205 W

Ballast: 8.3 A, 2880 VA

| Tungsten: 15 A, 7200 W

Ballast: 8.3 A, 4000 VA

Installation

  • Make sure to turn the power off at the breaker before installation.
  • Mount with an approved outdoor junction box or fi xture using the included gasket and nut.
  • DO NOT MOUNT WITH THE WIRES FACING UP OR ON THE BOTTOM OF AN ENCLOSURE.
  • Orient the lens of the photocontrol so it faces NORTH and away from artifi cial light sources that may cause the load to turn off at night.
  • When all wiring is complete, you can turn the breaker back on to restore power to the photocontrol.
  • Test the unit by covering the lens of the photocontrol with a leather glove or similar.
  • The photocontrol should react to a change within 60 seconds.

Wiring Diagram

INTERMATIC K4000 Thermal Photo Contro 1

Assembling

Photocell Wires| 120/277/347 V

Description

| Photocell Wires| 208/240/480 V

Description

---|---|---|---
Black| Connect Line 1 hot wire from the breaker panel| Black| Connect Line 1 1st hot wire from breaker panel
White| Connect Neutral from breaker panel you can connect the neutral for the lights or contactor you are controlling here too)| White| Connect Line 2 2nd hot wire from breaker panel. Here you can also connect the Load 2 wire for the lights or contactor you are controlling. (The other load wire connects to the RED wire *see below)
Red| Connect Load 1 wire switched hot to lights or contactor here| Red| Connect Load 1 wire for the load switched hot to lights or contactor here

**** Included Accessories

  • Metal Light Shield (22LG0120) Qty 1
  • Stem Mount and Stem & Swivel Mount Models

PRO TIP
Use when there is a high amount of incident light on the photocontrol from artifi cial light sources that may interfere with proper operation of photocontrol.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Intermatic User Manuals

Related Manuals