INTERMATIC EK4000 Series LED-Incandescent Electronic Photocontrol Instruction Manual
- October 30, 2023
- Intermatic
Table of Contents
ELECTRONIC PHOTOCONTROL
MODEL EK4000 Series
Installation and Setup Instructions
EK4000 Series LED-Incandescent Electronic Photocontrol
WARNING
Risk of Fire or Electric Shock
- Disconnect power at the circuit breaker(s) or disconnect switch(es) before beginning installation or servicing.
- Do NOT use the OFF state of the photocontrol for equipment servicing.
NOTICE
- DO NOT MOUNT WITH THE WIRES FACING UP.
Ratings:
Input Voltage| 120-277 V Photocontrols| 347 V Photocontrols|
480 V Photocontrols
---|---|---|---
Load Ratings| Tungsten: 1000 W
Ballast: 1800 VA
Electronic Ballast: 6 A| Tungsten: 1000 W
Ballast: 1800 VA
Electronic Ballast: 2 A| Tungsten: 1000 W
Ballast: 1800 VA
Electronic Ballast: 0.35 A*
*Tested with 150 W 480 V LED driver with 120 Apk/100µs In-rush current
Installation:
- Make sure to turn the power off at the breaker before installation.
- Mount with an approved outdoor junction box or fi xture using the included gasket and nut. (See photo)
- DO NOT MOUNT WITH THE WIRES FACING UP OR ON THE BOTTOM OF AN ENCLOSURE.
- Orient the lens of the photocontrol so it faces NORTH and away from artifi cial light sources that may cause the load to turn off at night.
- See diagram below for wiring.
- When all wiring is complete, you can turn the breaker back on to restore power to the photocontrol.
- Test the unit by covering the lens of the photocontrol with a leather glove or similar. The photocontrol should react to a change within 30 seconds.
Wiring Diagram
Photocell Wires| 120/277/347 V
Description| Photocell Wires| 208/240/480 V
Description
---|---|---|---
Black| Connect Line 1 (hot) wire from the breaker panel| Black| Connect Line 1
(1st hot) wire from breaker panel
White| Connect Neutral from breaker panel (you can connect the neutral for the
lights or contactor you are controlling here too)| White| Connect Line 2 (2nd
hot) wire from breaker panel. Here you can also connect the Load 2 wire for
the lights or contactor you are controlling. (The other load wire connects to
the RED wire see below)
Red| Connect Load 1 wire (switched hot to lights or contactor) here| Red|
Connect Load 1 wire for the load (switched hot to lights or contactor) here
Included Accessories:
- Metal Light Shield (22LG0120) Qty 1 – Stem Mount and Stem & Swivel Mount Models
- Light Shield Plastic Dome (6LV1352) Qty 1 – Button Style Models
- Self-Adhesive Round Labels (LGLBL) – All Models
PRO TIP: Use when there is a high amount of incident light on the photocontrol from artifi cial light sources that may interfere with proper operation of photocontrol. LIMITED WARRANTY
Warranty service is available by either (a) returning the product to the
dealer from whom the unit was purchased or (b) completing a warranty claim
online at www.intermatic.com.
This warranty is made by: Intermatic Incorporated, Customer Service 1950
Innovation Way, Suite 300, Libertyville, IL 60048.
For warranty service go to: http://www.Intermatic.com or call 815-675-7000.
INTERMATIC INCORPORATED
Libertyville, Illinois 60048 USA
www.intermatic.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>