venturelighting SELECT-PRO MODERN HIGHBAY User Manual

June 5, 2024
venturelighting

VENTURE LIGHTING’S SELECT-PRO MODERN HIGHBAY
USER MANUAL

SELECT-PRO MODERN HIGHBAY

venturelighting SELECT PRO MODERN HIGHBAY - STOPBefore You Begin
READ THESE INSTRUCTIONS COMPLETELY AND CAREFULLY

UNPACKING

  • Unpack and carefully examine the product.
  • Report any damage and save all packing materials if any part(s) were damaged during shipping.
  • Do not attempt to install or use this equipment if it is damaged.

**INCLUDED IN THIS BOX

**

  • LED Fixture
  • Carabiner and Safety Cable
  • Installation instructions

WARNING – RISK OF FIRE, ELECTRIC SHOCK, INJURY, OR PROPERTY DAMAGE

  • Failure to follow these instructions or altering equipment could result in injury or damage and void warranty. Venture assumes no liability for injury, damages, or losses of any kind that may arise from the improper, careless, or negligent installation, handling or use of this product.

  • This equipment must be installed and serviced per applicable codes and ordinances by qualified personnel (ex. licensed electrician) familiar with the
    operation of the product and any hazards involved.

  • Disconnect power to the equipment and allow it to cool before installing or servicing.

  • Handle sharp edges with care. To prevent wiring damage, do not expose wiring to sharp edges.

  • Verify that all electrical connections have been properly made and the fixture is grounded to avoid potential electrical shocks.

  • It is the responsibility of the installer to confirm the proper input voltage is used with this equipment.

  • Do not handle energized equipment when hands are wet when standing on wet surfaces, or in water.

  • This fixture must be mounted securely to a structure to support the weight.

SUPPLIER’S DECLARATION OF CONFORMITY (SDoC)

  • This equipment complies with the limits for a Class A digital device, pursuant to Part 15 Subpart B of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial, industrial, or business environment.
  • This equipment complies with the limits for Class A lighting equipment, pursuant to Innovation, Science and Economic Development Canada’s CAN ICES-005 (A) / NMB-005 (A).

For warranty information refer to www.venturelighting.com/resources/warranties.

IMPORTANT SAFETY INFORMATION

  • Operating temperature: -40°C to +40°C (-40°F to +104°F).
  • Suitable for use in wet locations.
  • All wiring and connectors used with this equipment shall be rated at a minimum of 75°C (167°F).

Installation Instructions

  1. Disconnect power from the luminaire and follow proper lockout/Tagout procedures before beginning installation or maintenance.

  2. Remove the existing luminaire (if present) and dispose of it per local requirements.

  3. Default CCT – 5000K; Default Wattage – Highest.

  4. Use selector switch to choose CCT and Wattage settings. (Figure 1)venturelighting SELECT PRO MODERN HIGHBAY - FIG 1

  5. Attach safety cable to screw hole on a fixture. Once fixture installation is complete, connect another end of the cable to the ceiling or mounting surface.
    Installation Instructions – Suspension Mount 6:

  6. Attach chain or cable to eye-bolt on top of the fixture. (Figure 2)venturelighting SELECT PRO MODERN HIGHBAY - FIG 2

  7. Attach chain or cable to the ceiling structure.

  8. Connect the supply wires to the junction box, or similar, as shown in the wiring diagram below.
    NOTE: The correct polarity of the dimming connections is essential to proper operation.
    NOTE: If not using the dimming functionality, insulate the Dim(+) (purple) and Dim(-) (pink) wires separately (bare wires should not be left exposed). DO NOT connect the Driver Dim(+) (purple) to the Driver Dim(-) (pink) wire as the fixture will not operate correctly.

  9. Power can now be restored to the system.

Installation Instructions – Surface Mount

6: Remove hole plugs from 4 screw holes on fixture heatsink. Use bracket as a guide to determine which plugs to remove.
7: Attach fixture to Surface Bracket by utilizing the provided mounting hardware.
8: The surface kit is supplied with anchors. Drill (2) 10mm holes in the ceiling. Use bracket as a template.
9: Use a hammer to pound supplied anchors into holes. (Figure 3)
10: Attach the surface bracket to anchors and tighten nuts. (Figure 4 & 5)
11: Set fixture to the proper angle and tighten angle adjustment screws. (Figure 6)
12: Connect the supply wires to the junction box, or similar, as shown in the wiring diagram below.
NOTE: The correct polarity of the dimming connections is essential to proper operation.
NOTE: If not using the dimming functionality, insulate the Dim(+) (purple) and Dim(-) (pink) wires separately (bare wires should not be left exposed). DO NOT connect the Driver Dim(+) (purple) to the Driver Dim(-) (pink) wire as the fixture will not operate correctly.
13: Power can now be restored to the system.

venturelighting SELECT PRO MODERN HIGHBAY - FIG 3456

Installation Instructions – 1/2″ Pendant Mount

6: Remove hole plugs from 4 screw holes on fixture heatsink. Use bracket as a guide to determine which plugs to remove.
7: Attach fixture to Surface Bracket by utilizing the provided mounting hardware.
8: Set fixture to the proper angle and tighten angle adjustment screws. (Figure 6)
9: Screw on lock nut to ½” threaded pipe.
10: Threaded pipe will pass through the center hole on the Surface Bracket.
11: Add second lock nut to pipe to secure fixture and bracket to the pipe. (Figure 7)

12: Connect the supply wires to the junction box, or similar, as shown in the wiring diagram below.
NOTE: The correct polarity of the dimming connections is essential to proper operation.
NOTE: If not using the dimming functionality, insulate the Dim(+) (purple) and Dim(-) (pink) wires separately (bare wires should not be left exposed). DO NOT connect the Driver Dim(+) (purple) to the Driver Dim(-) (pink) wire as the fixture will not operate correctly.
13: Power can now be restored to the system.

Installation Instructions – 3/4″ Pendant Mount

6: Remove the eye bolt from the fixture.
7: Screw in a ¾” pendant mount accessory. (Figure 8) 8: Route power and dimming wires through pendant accessory and ¾” pipe.
9: Connect the supply wires to the junction box, or similar, as shown in the wiring diagram below.
NOTE: The correct polarity of the dimming connections is essential to proper operation.
NOTE: If not using the dimming functionality, insulate the Dim(+) (purple) and Dim(-) (pink) wires separately (bare wires should not be left exposed). DO NOT connect the Driver Dim(+) (purple) to the
Driver Dim(-) (pink) wire as the fixture will not operate correctly.
10: Power can now be restored to the system.

Wiring Diagram:

venturelighting SELECT PRO MODERN HIGHBAY - FIG 9venturelighting SELECT PRO MODERN HIGHBAY - QR
Codehttp://www.venturelighting.com/
800-451-2606
7905 Cochran Road, Suite 300
Glenwillow, Ohio 44139 USA
E-mail: Venture_Lighting@VentureLighting.com
Venturelighting.com
©2021 Venture Lighting International
Venture Lighting is a registered trademark of Venture Lighting International.
AK001 6-A

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals