venture lighting AS0044-B LED STRIP LIGHT FIXTURE BATTERY BACKUP User Manual

June 5, 2024
venturelighting

venture lighting AS0044-B LED STRIP LIGHT FIXTURE BATTERY BACKUP

Before You Begin
Read These Instructions Completely and Carefully

Upgrade Instructions

  • STEP 1: Disconnect power from the existing luminaire and follow proper lockout/Tagout procedures before beginning installation or maintenance.

  • STEP 2: Remove the existing luminaire. Dispose of the lamp(s) and ballast(s) per local requirements.

  • STEP 3: Remove lens and wire way cover. (A)

  • STEP 4: Select the installation point and locate studs. For rear access points, feed wires through holes. (B)

  • STEP 5: Select the wiring access point and remove the appropriate knockout.

  • STEP 6: Make the necessary wiring connections as shown in the wiring diagram. (C)
    NOTE:

    • The wiring between the battery backup, fixture test switch, driver(s), and LED modules is already completed. There are two black input wires: the flagged black wire should be connected to continuous (or unswitched) input power. When power is interrupted on this wire, the fixture will enter battery backup mode. The unlabeled input wire should be connected to the switch or control that will turn the fixture on and off under normal circumstances.
      • The polarity of the dimming connections is important to ensure the performance as desired.
      • If not using the dimming functionality, DO NOT connect the Driver Dim+ (purple) to the Driver DIM- (pink). The fixture will not operate as desired.
  • STEP 7: Replace the wire cover and secure the diffuser into place.

  • STEP 8: Power can now be restored to the fixture.

Wiring Diagram

WARNING

Risk of fire and electric shock

  • Disconnect power from the luminaire and follow proper lockout/Tagout procedures before beginning installation or maintenance. Contact a qualified electrician for installation.
  • Venture Lighting’s LED Strip Fixture installation requires knowledge of luminaire electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
  • To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
  • The product should be installed and operated by a qualified electrician or technician in accordance with relevant local codes.
  • Check to make sure that all fixture connections have been properly made and the fixture is grounded to avoid potential electrical shocks.
  • Suitable for use in damp and dry locations.
  • The installer must determine that the supply voltage meets the fixture requirement.
  • Minimum 90°C supply conductors.