EXTRONICS iBATT5xx Zone 1 and 2 Stainless-Steel Universal Battery Enclosure Instruction Manual
- June 5, 2024
- Extronics
Table of Contents
EXTRONICS iBATT5xx Zone 1 and 2 Stainless-Steel Universal Battery
Enclosure
Introduction
The iBATT5xx is an ATEX/IECEx approved floor mount stainless steel battery enclosure for use in Zone1 and Zone 2 hazardous areas. It is designed to be used in conjunction with the iUPS101 UPS & other products to provide an uninterruptible power supply. The iBATT5xx can also be used independently providing the special conditions for safe use are applied as detailed on the ATEX/IECEx certificates. When used in conjunction with the Ex `e’ certified charge protection circuit contained within the iUPS101 system or other Extronics supplied product, users are permitted to charge the internal batteries within a hazardous area.
Safety Information and Notes
Storage of this Manual
Keep this user manual safe and in the vicinity of the device. All persons who have to work on or with the device should be advised on where the manual is stored.
Certification Requirements
The battery box main explosion protection concept is increased safety Ex `e’.
Certified II 2 G Ex e IIC T6 Gb
Special Conditions for Safe Use
- The battery box shall not be exposed to mechanical shock.
- If the battery is to be disconnected from its associated equipment in the hazardous area then a suitably ATEX/IECEx approved disconnection device shall be used
- In the event of battery charger failure, the maximum charge voltage and current specified in the battery manufacturer’s instructions shall not be exceeded.
- The battery box may build up electrostatic charge, so it is essential the precautionary measures advised in section 4.7 are adhered to.
List of Notes
The notes supplied in this chapter provide information on the following
- Warning!
- Possible hazard to life or health.
- Caution
- Possible damage to property.
- Important
- Possible damage to enclosure, device or associated equipment.
- Information
- Notes on the optimum use of the device
Warning
- Installation to be by skilled electricians and instructed personnel in accordance with national legislation, including the relevant standards and, where applicable, in accordance with IEC 79.17 on electrical apparatus for explosive atmospheres.
- The iBATT5xx must only be operated in Zone 1 and Zone 2 hazardous area. Refer to the ATEX/IECEx certificates for further information.
- If charging takes place in a hazardous area the charging circuits must meet the requirements of EN60079-0 and EN60079-7.
- Any load connected to the iBATT5xx must include a suitably rated fuse or protection device in the supply line. If the fuse or protection device is located in a hazardous area it must be suitably certified.
- If the batteries are to be disconnected in a hazardous area, then an appropriately certified means of isolation must be provided.
Important
- The batteries must not be subjected to mechanical shock.
- The technical data indicated on the iBATT5xx ATEX/IECEx rating plate, in this manual and the ATEX/IECEx certificates must be observed at all times.
- The ATEX/IECEx rating label must be fitted at all times, if damaged it must be replaced immediately or the iBATT5xx must be removed from service and the hazardous area.
- Changes in the design and modifications to the equipment are not permitted.
- The iBATT5xx shall be operated as intended and only in an undamaged condition.
- Only suitably rated loads may be connected to the iBATT5xx.
Caution
- This assembly is extremely heavy, therefore ensure the assembly is mounted using suitable fixtures.
- Never operate the iBATT5xx unit outside its rated voltage, current & power as indicated in the specification or the safety of the unit may be impaired.
- Never exceed the maximum loading of the iBATT5xx as stated in the specifications. Adequate protection such as a fuse / protection device must be fitted to connecting equipment to prevent exceeding maximum load.
Important
- For the installation, maintenance and cleaning of the units, it is absolutely necessary to observe the applicable regulations and provisions concerned with explosion protection (EN60079-0:2018, EN 60079-14:2014) as well as the Accident Prevention Regulations.
- The iBATT5xx must not be stored or operated outside of its rated temperature range as stated on the ATEX/IECEx certificates.
- Only replacement batteries supplied by Extronics may be fitted as there are safety related tests that need to be performed on each battery.
Installation
Mounting
The battery enclosure should be securely mounted to the floor with suitable fixings to ensure no movement or vibration.
Opening and Closing the Enclosure
Enclosure can either be supplied with hinged lids or on larger enclosures the lid is removable. Care should be taken when lids are removable due to excessive weights.
Cable Entries
The cable entry to the battery box is via ATEX/IECEx approved Ex e cable gland/s. Customers fitting their own cable glands should install them in accordance with the requirements EN 60079-14 `Electrical Installations in Hazardous Areas (other than mines)’.
Battery Charging
The battery shall be charged according to battery manufacturer’s instructions,
see separate battery product information sheet.
Important!: In the event of battery charger failure, the maximum charge
voltage and current specified in the battery manufacturer’s instructions shall
not be exceeded.
Intended Purpose Usage
Warning!
Maintenance and inspection of the iBATT5xx must be performed in accordance
with IEC 60079-17 `Electrical Installations Inspection and Maintenance’
Important
- Before setting the units to work, read the technical documentation carefully.
- The latest version of the technical documentation or the corresponding technical supplements is valid in each case.
The iBATT5xx is built using modern components and is extremely reliable in operation; however it must only be used for its intended purpose. Please note that the intended purpose also includes compliance with the instructions issued by the manufacturer for installation, setting up and service.
Any other use is regarded as conflicting with the intended purpose. The manufacturer is not liable for any subsequent damage resulting from such inadmissible use. The user bears the sole risk in such cases.
Transportation and Storage
All iBATT5xx enclosures must be so transported and stored that they are not subjected to any excessive mechanical stresses.
Authorized Persons
Only persons trained for the purpose are authorized to handle the iBATT5xx; they must be familiar with the unit and must be aware of the regulation and provisions required for explosion protection as well as the relevant accident prevention regulations.
Cleaning and Maintenance
The cells shall be maintained in accordance with the cell manufacture’s maintenance documents. Refer to battery manufacturer’s instructions, enclosed together with this manual
Cleaning and Maintenance Intervals
The cleaning and maintenance intervals depend on the environment where the system is installed.
Aggressive substances and environments
The iBATT5xx is not designed to come into contact with aggressive substances or environments, please be aware that additional protection may be required.
Exposure to external stresses
The iBATT5xx is not designed to be subjected to excessive stresses e.g. vibration, heat, impact. Additional protection is required to protect against these external stresses. The iBATT5xx will require additional protection if it is installed in a location where it may be subjected to damage.
Prevention of electrostatic charging
The iBATT5xx enclosure can build up electrostatic charge on its surfaces, so
the following steps are to be followed:
Static charge build up should be reduced by:
- Connecting the enclosure to a suitable earth point
- Cleaning off surface dust using a damp cloth
- Not installing into areas where high airflow can occur.
Technical Data
Specification
Maximum Voltage | Unlimited |
---|---|
Maximum Cells per Battery | 36 |
Maximum Capacity | 2500Ah |
Maximum Enclosure Size | 1610 x 1810 x 700 |
Enclosure Material | 316 Stainless Steel |
Finish | Natural or Painted |
Enclosure Ingress Protection | IP43/IP56 |
Environmental | -40ºC to +55ºC |
Certification | ATEX/IECEx Ex II 2 G Ex e IIC T6 Gb |
Temperature Sensor | Optional RTD, Ex’d’ Certified, Can Be Fitted |
Battery Installation & Operating Instructions
See separate battery product information sheet supplied by Extronics.
Certification
ATEX/IECEx Label
EU Declaration of Conformity
Type Codes
See separate battery product information sheet supplied by Extronics.