SYSTY Mair SYSVRF2 Outdoor unit Mini VRF Heat Pump Installation Guide
- June 5, 2024
- SYSTY Mair
Table of Contents
SYSVRF2 Outdoor unit Mini VRF Heat Pump
SYSVRF2 AIR EVO A HP R
GB Outdoor unit Mini VRF Heat Pump
INSTALLATION MANUAL
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
CONTENTS
PAGE
PRECAUTIONS…………………………………………………………………………….1 ATTACHED FITTINGS……………………………………………………………………2 OUTDOOR UNIT INSTALLATION……………………………………………………..3 INSTALL THE CONNECTING PIPE……………………………………………………4 ELECTRICAL WIRING……………………………………………………………………9 TEST RUNNING………………………………………………………………………….12 CONFIGURATION………………………………………………………………………..12 PRECAUTIONS ON REFRIGERANT LEAKAGE…………………………………..13 ERROR CODES…………………………………………………………………………..14 TURN OVER TO CUSTOMER…………………………………………………………14
1. PRECAUTIONS
Ensure that all Local, National and International regulations are satisfied.
Read this “PRECAUTIONS ” carefully before Installation. The precautions
described below include the important items regarding safety. Observe them
without fail. After the installation work, perform a trial operation to check
for any problem. Follow the Owner’s Manual to explain how to use and maintain
the unit to the customer. Turn off the main power supply switch (or breaker)
before maintenance the unit . Ask the customer that the Installation Manual
and the Owner’s Manual should be kept together .
CAUTION
New Refrigerant Air Conditioner Installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT(R410A)WHICH DOES NOT
DESTROY OZONE LAYER. The characteristics of R410A refrigerant are;
Hydrophilic, oxidizing membrane or oil, and its pressure is approx.1.6 times
higher than that of refrigerant R22.Accompanied with the new refrigerant,
refrigerating oil has also been changed ,Therefore, during installation work,
be sure that water, dust, former refrigerant, or refrigerating oil does not
enter the refrigerating cycle. To prevent charging an incorrect refrigerant
and refrigerating oil, the sizes of connecting sections of charging port of
the main unit and installation tools are charged from those for the
conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A):
For connecting pipes, use new and clean piping designed for R410A,and please
care so that water or dust does not enter. Moreover, do not use the existing
piping because there are problems with pressure-resistance force and impurity
in it.
CAUTION
Do not connect the Appliance from Main Power Supply directly.
WARNING
Ask an authorized dealer or qualified installation professional to
install/maintain the air conditioner. Inappropriate installation may result in
water leakage,electric shock or fire. Turn off the main power supply switch or
breaker before attempting any electrical work. Make sure all power switches
are off.Failure to do so may cause electric shock. Connect the connecting
cable correctly. If the connecting cable is connected in a wrong way, electric
parts may be damaged. When moving the air conditioner for the installation
into another place, be very careful not to enter any gaseous matter other than
the specified refrigerant into the refrigeration cycle. If air or any other
has is mixed in refrigerant, the gas pressure in the refrigeration cycle
becomes abnormally high and it may resultingly causes pipe burst and injuries
on persons. Do not modify this unit by removing any of the safety guards or by
by-passing any of the safety interlock switches. Exposure of unit to water or
other moisture before installation may cause a short-circuit of electrical
parts. Do not store it in a wet basement or expose to rain or water. After
unpacking the unit, examine it carefully if there are possible damage. Do not
install in a place that might increase the vibration of the unit. To avoid
personal injury (with sharp edges), be careful when handling parts. Perform
installation work properly according to the Installation Manual. Inappropriate
installation may result in water leakage, electric shock or fire. When the air
conditioner is installed in a small room, provide appropriate measures to
ensure that the concentration of refrigerant leakage occur in the room does
not exceed the critical level. Install the air conditioner securely in a
location where the base can sustain the weight adequately. Perform the
specified installation work to guard against an earthquake. If the air
conditioner is not installed appropriately, accidents may occur due to the
falling unit. If refrigerant gas has leaked during the installation work,
ventilate the room immediately. If the leaked refrigerant gas comes in contact
with fire, noxious gas may generate. After the installation work, confirm that
refrigerant gas doer not leak. If refeigerant gas leaks into the room and
flows near a fire source, such as a cooking range, noxious gas might generate.
Electrical work must be performed by a qualified electrician in accordance
with the Installation Manual. Make sure the air conditioner uses an exclusive
power supply. The appliance shall be installed in accordance with national
wiring regulations. If the supply cord is damaged, it must be replaced by the
manufacture or its service agent or a similarly qualified person in order to
avoid a hazard. An all-pole disconnection switch having a contact separation
of at least 3mm in all poles should be connected in fixed wiring. The
dimensions of the space necessary for correct installation of the appliance
including the minimum permissible distances in order to avoid a hazard.
1
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
The temperature of refrigerant circuit will be high, please keep the
interconnection cable away from the copper tube. The power cord type
designation is H05RN-For above/H07RN-F.
An insufficient power supply capacity or inappropriate installation may cause
fire. Use the specified cables for wiring connect the terminals securely fix.
To prevent external forces applied to the terminals from affecting the
terminals. Be sure to provide grounding. Do not connect ground wires to gas
pipes, water pipes, lightning rods or ground wires for telephone cables.
Conform to the regulations of the local electric company when wiring the power
supply. Inappropriate grounding may cause electric shock. Do not install the
air conditioner in a location subject to a risk of exposure to a combustible
gas. If a combustible gas leaks, and stays around the unit, a fire may occur.
For appliances intended for use at altitudes exceeding 2000m, the maximum
altitude of use shall be stated.
Required tools for installation work 1) Philips screw driver 2) Hole core
drill(65mm)
- Spanner 4) Pipe cutter 5) Knife 6) Reamer 7) Gas leak detector 8) Tape measure 9) Thermometer 10) Mega-tester 11) Electro circuit tester 12) Hexagonal wrench 13) Flare tool 14) Pipe bender 15) Level vial 16) Metal saw
- Gauge manifold (Charge hose:R410A special requirement) 18) Vacuum pump
(Charge hose:R410A special requirement) 19) Torque wrench
1/4(17mm)16N·m (1.6kgf·m) 3/8(22mm)42N·m (4.2kgf·m) 1/2(26mm)55N·m (5.5kgf·m) 5/8(15.9mm)120N·m (12.0kgf·m) 20) Copper pipe gauge adjusting projection margin 21) Vacuum pump adapter
2. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are
some spare fittings , please restore them carefully.
NAME 1. Outdoor unit installation manual
2. Outdoor unit owner’s manual
INSTALLATION FITTINGS
3. Installation Instructions: Indoor Unit Manifold
4.Water outlet connection pipe
5.Matched resistance 6.Waterproof chassis cover
7.Connection pipe(26/28/33.5kW)
SHAPE
QUANTITY 1 2 1 1 2 2 1
Refrigerant Piping Piping kit used for the conventional refrigerant cannot be
used. Use copper pipe with 0.8 mm or more thickness for 9.5. Use copper pipe
with 1.0 mm or more thickness for 15.9. Use copper pipe with 1.0 mm or more
thickness for 19.0. Flare nut and flare works are also different form those of
the conventional refrigerant.take out the flare nut attached to the main unit
of the air conditioner, and use it.
Before installation Be careful to the following items before installation.
Air purge For air purge, use a vacuum pump. Do not use refrigerant charged in
the outdoor unit for air purge. (The refrigerant for air purge is not
contained in the outdoor unit.)
Electrical cabling Be sure to fix the power cables and indoor/outdoor
connecting cables with clamps so that they do not contact with the cabinet,
etc.
Installation Place A place which provides a specified space around the outdoor
unit. A place were the operation noise and discharged air are not given to
your neighbors. A place that is not exposed to a strong wind. A place that
does not block a passage. When the outdoor unit is installed in an elevated
position, make sure it’s four feet securely installed. There must be
sufficient space for carrying in the unit. A place where the drain water does
not make any problem.
CAUTION
Install the outdoor unit at a place where discharge air is not blocked. When
an outdoor unit is installed in a place that is always exposed to a strong
wind like a coast or on a high storey of a building, secure a normal fan
operation by using a duct or a wind shield.
2
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
When installing the outdoor unit in a place that is constantly exposed to a
strong wind such as the upper stairs or rooftop of a building, apply the
windproof measures referring to the following examples. Install the unit so
that its discharge port faces to the wall of the building. Keep a distance
3000mm or more between the unit and the wall surface. Do not mount the outdoor
unit on a wall.
3000
The insulation of the metal parts of the building and the air conditioner
should comply with the regulation of National Electric Standard.
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at
least 1 meter away from televisions and radios. This is to prevent image
interference and noise in those electrical appliances. (Noise may be generated
depending on the conditions under which the electric wave is generated, even
if 1 meter is kept.)
3.2 Installation space (Unit:mm)
Fig.2-1 Supposing the wind direction during the operation season of the discharge port is set at right angle to the wind direction.
Strong wind
Strong wind
1558
1120
668
206
440 400 494 528
Fig.2-2
Installation in the following places may result in some troubles. Do not
install the unit in such places below.
A place full of machine oil. A place full of sulphuric gas. A place where
high-frequency radio waves are likely to be generated as from audio quipment,
welders, and medical equipment.
3. OUTDOOR UNIT INSTALLATION
3.1 Installation place
Please keep away from the following place, or malfunction of the machine may
be caused:
There is combustible gas leakage. There is much oil (including engine oil)
ingredient. There is salty air surrounding(near the coast) There is caustic
gas (the sulfide, for example) existing in the air (near a hotspring) A place
the heat air expelled out from the outdoor unit can reach your neighbor’s
window. A place that the noise interferes your neighbors every day life. A
place that is too weak to bear the weight of the unit Uneven place.
Insufficient ventilation place. Near a private power station or high Frequency
equipment. Install indoor unit, outdoor unit, power cord and connecting wire
at least 1m away from TV set or radio to prevent noise or picture
interference.
3
Single unit installation
(Wall or obstacle) Air inlet >300
Air inlet
300
Fig.3-1
Maintain the electric wire and pipeline >600
3000
Air outlet
Parallel connect the two units or above
300 >3000
600
Parallel connect the front with rear sides
Fig.3-2 Fig.3-3
3000
1000
6000
4000
300
Fig.3-4
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
3.3 Moving and installation
Since the gravity center of the unit is not at its physical center, so please
be careful when lifting it with a sling. Never hold the inlet of the outdoor
unit to prevent it from deforming. Do not touch the fan with hands or other
objects. Do not lean it more than 45°, and do not lay it sidelong. Make
concrete foundation according to the sepecifications of the outdoor
units.(refer to Fig.3-5) Fasten the feet of this unit with bolts firmly to
prevent it from collapsing in case of earthquake or strong wind. (refer to
Fig.3-5)
4. INSTALL THE CONNECTING PIPE
Check whether the height drop between the indoor unit and outdoor unit, the
length of refrigerant pipe, and the number of the bends meet the following
requirements:
600
Fix with bolt
4.1 Refrigerant piping
Fig.4-1
Fig.3-5
NOTE
All the pictures in this manual are for explanation purpose only. They may be
slightly different from the air conditioner you purchased(depend on model).The
actual shape shall prevail.
3.4 Centralized Chassis Drainage
When the outdoor unit requires centralized drainage, install the chassis and
two waterproof covers for the chassis, as shown in Figure 3-6. Install the
water outlet union pipe and sealing ring on the chassis, and then connect the
drainage pipe to complete centralized drainage installation.
Waterproof chassis cover
Sealing ring for the water outlet union pipe
CAUTION
Please pay attention to avoid the components while connect to the connecting
pipes. To prevent the refrigerant piping from oxidizing inside when welding,
it is necessary to charge nitrogen, or oxide will chock the circulation
system.
The indoor and outdoor connecting pipe interface and power line outlet
Vavious piping and viring patterns can be selected,such as out from the front
,the back the side ,and undersurface, etc.(The follow display the locations of
several piping and wiring knock-off interfaces)
Table 4-1
Front out pipe
Side out pipe
Fig.3-6
CAUTION
While installing the outdoor unit, pay attention to the installation place and
the drainage pattern; if it’s installed at the alpine zone, the frozen
condensed water will block up the water outlet, please pull out the rubber
stopper of the reserve water outlet. If that still fails to satisfy for the
water draining, please knock open the other two water outlets, and keep the
water can drain in time. Pay attention to the knock the reserve water outlet
from outside to inside, and it will be beyond repair after knocking open,
please pay attention to the installation place, lest cause the inconvenience.
Please do the moth proofing for the knocked out hole, to avoid the pest
processing into and destroy the components.
CAUTION
1. Side out pipe: cut the side hole of the pipe-outlet plate selectively. It
is suggested to cut a piece of metal plate below to avoid the mouse come and
destroy the machine wiring body. 2.Front out pipe: cut the frontal hole of the
pipe-outlet plate selectively. It is suggested to cut a piece of metal plate
right side to avoid the mouse come and destroy the machine wiring body. 3.
Wiring of power cord: the strong and weak electrical wire should be out
through the two plastic holes of the pipe-outlet plate, and binded with gas
and liquid pipe together.
4.2 Leak Detection
Use soap water or leak detector to check every joint whether leak or not
(Refer to Fig.4-2).Note:
A is low pressure side stop valve B is high pressure side stop valve C and D
is connecting pipes interface of indoor and outdoor units
4
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
Check point of indoor unit
D
C
B
A
Check point of outdoor unit
4.3 Heat Insulation
Fig. 4-2
Do the heat insulation to the pipes of air side and liquid side separately.
The temperature of the pipes of air side and liquid side when cooling, for
avoiding condensation please do the heat insulation fully.
The air side pipe should use closed cell foamed insulation material, which the
fire-retardant is B1 grade and the heat resistance over 120°C.
When the external diameter of copper pipe12.7mm, the thickness of the
insulating layer at least more than 15mm;
When the external diameter of copper pipe15.9mm, the thickness of the
insulating layer at least more than 20mm.
Please use attached heat-insulating materials do the heat insulation without
clearance for the connecting parts of the indoor unit pipes.
Cut from upward
The unit body
Site pipe side Affiliated heat pump belt
Fig. 4-3
4.4 Connecting method
Select refrigerant pipe
Table 4-2 pipe definition
pipe connect position
code
main pipe
The pipe between outdoor unit to the L1 first branch of indoor unit.
The main pipes of indoor unit
The pipe after the first branch do not direct connect with the indoor unit.
L2L5
The branch pipes The pipe after the branch connect with a,b,c,
of indoor unit
the indoor unit.
d,e,f
Indoor unit branch pipes components
The pipes connect with the main pipe the branch pipe and the the main pipe of indoor unit.
A,B,C, D,E
The first connect methond
Outdoor Unit
L1
A
L2 B
L3
L4 C
c
L5
D d
E e
f
a
b
The first Line Branch Pipe
Fig. 4-4
The second connect methond
Outdoor Unit(Take Model 280 for example)
L1 A
The first Line Branch Pipe
N1
(56)
a
L2 B
intdoor Units
b
N2
(56)
N3
L3 L4
C L5
c D
d
(45)
N4 (45)
e
E
f
N5 (45)
N6 (56)
Fig. 4-5
NOTE
The distance between the first branch to the last indoor unit is more than
15m,choose the second connect methond. The pipe between the indoor unit to the
closest branch must less than 15m.
4.4 Confirmation for the diameters of indoor unit connecting pipes
Size of main pipe and corresponding branch joint and branch header
- R410A Indoor unit connecting pipes diameters 4-3 2) Example 1In the Fig.4-5,The downstream inner units of the L4,and its total capacity is 45×290refers to the Table 4.4,the air/liquid side of L4 is15.9/9.5
R410A Indoor unit connecting pipes diameters
Table 4-3
Capacity of the downstream indoor unit
A166
Main pipe size (mm)
Air pipe
Liquid pipe
15.9
9.5
Applicable manifold
FQZHN-01D
166A230
19.1
9.5
FQZHN-01D
230A330
22.2
9.5
FQZHN-02D
330A470
25.4
12.7
FQZHN-03D
4.5 Confirmation for the diameters of outdoor
unit connecting pipes
R410A outdoor unit connecting pipes diameters
Table 4-4
Total capactiy of The
outdoor
Main pipe size when the total equivalent piping length of liquid + gas side is <90m
Main pipe size when the total equivalent piping length of liquid + gas side is 90m
units Gas side Liquid si- The first Line Gas side Liquid si- The first Line
(mm) de(mm) Branch Pipe (mm) de(mm) Branch Pipe
20-28KW 22.2 9.5 FQZHN-02D 25.4 12.7 FQZHN-03D
33.5KW 25.4 12.7 FQZHN-03D 25.4 12.7 FQZHN-03D
NOTE
The straight distance between copper pipe turning and the contiguous branch
pipe is at least 0.5m; The straight distance between the contiguous
branchpipes is at least 0.5m; The straight distance which the branch pipes
connected to the indoor unit is at least 0.5m;
5
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
Branch header must be connected with indoor units directly, the further branch connection is not allowed.
Select branch joint
Select the branch joint according to the total designed capacity of indoor
units which it connects to. If this capacity is more than that of the outdoor
unit, then select the connection according to the outdoor unit.
The selection of branch header depends on the quantity of branches it connects
to.
Connection method
Table 4-5
Outdoor unit Indoor unit Branch pipe
Gas side Welding or Flaring
Liquid side Welding or Flaring
Flaring
Flaring
Welding or Flaring Welding or Flaring
Piping sizes at the branch pipe
Table 4-6
(A: the total capacity of indoor units)
Refrigerant
A (TYPE)
Air Side ()
Liquid Side ()
Wall mounted 22~45 12.7(Flaring nut)
Wall mounted 56 15.9(Flaring nut)
Four-sided air outlet 28~45 Four-sided air outlet 56~80
One-sided air outlet 18~45 One-sided air outlet 56
Low static pressure 18~45
Low static pressure 56
12.7(Flaring nut) 15.9(Flaring nut) 12.7(Flaring nut) 15.9(Flaring nut) 12.7(Flaring nut) 15.9(Flaring nut)
R410A
Thin duct type 71 A5 duct type 22~45
15.9(Flaring nut) 12.7(Flaring nut)
A5 duct type 56~140 15.9(Flaring nut)
Four-way Cassette Type 15~45
12.7(Flaring nut)
Console Type 22~45 12.7(Flaring nut)
Tow-way Cassette Type 22~45
Tow-way Cassette Type 56~71
Ceiling And Floor Type 36~45 Ceiling And Floor Type 56~160
12.7(Flaring nut) 15.9(Flaring nut) 12.7(Flaring nut) 15.9(Flaring nut)
Expose And Concealed
12.7(Flaring nut)
Floor-standing type 22~45
6.4(Flaring nut) 9.5(Flaring nut) 6.4(Flaring nut) 9.5(Flaring nut)
6.4(Flaring nut) 9.5(Flaring nut)
6.4(Flaring nut) 9.5(Flaring nut) 9.5(Flaring nut) 6.4(Flaring nut)
9.5(Flaring nut) 6.4(Flaring nut) 6.4(Flaring nut) 6.4(Flaring nut)
9.5(Flaring nut) 6.4(Flaring nut) 9.5(Flaring nut) 6.4(Flaring nut)
Expose And Concealed Floor-standing type 56~80
15.9(Flaring nut)
9.5(Flaring nut)
Pipe diameter of the connector in the outdoor unit’s body
Table 4-7
Piping connection Pipe diameter of outdoor unit’s connector(mm)
side
Model(kW)
Gas Side
Liquid Side
20-22.4 26-28 33.5
33.5
19.1 22.2 22.2
9.53 9.53 12.7
6
Table 4-8
Outdoor Unit (kW)
Capacity of Maximum Outdoor unit Quantity of (horsepower) Indoor unit
Sum Capacity of Indoor unit (horsepower)
20
7
11
22.4
8
13
26
9
15
50%~130%
28
10
16
33.5
12
20
When capacity of indoor unit greater than the sum of 100%, capacity
of indoor unit will be attenuated.
When capacity of indoor unit greater than or equal to the sum of
120%, in order to ensure the effectiveness of machine, and then try to
open the indoor units at different time.
NOTE
The indoor unit capacity total can not exceed 130% of the outdoor unit load.
Overloading reduces the corresponding capacity.
Table 4-9
Capacity ranking
Capacity (horsepower)
Capacity ranking
Capacity (horsepower)
18
0.6
80
2.8
22
0.8
90
3.2
28
1
100
3.5
36
1.3
112
4
45
1.6
120
4.3
56
2
125
4.5
71
2.5
140
5
When the outdoor unit connects one indoor unit
Table 4-10
MODEL The max height drop(m) The length of
(kW)
When outdoor When outdoor unit is top unit is bottom
refrigerant pipe(m)
The number of bends
20-33.5
25
20
50
less than 10
4.6 Illustration
Outdoor Unit((Take Model 280 for example)
(280)
N1 (56)
a
L1 A
L2 B b
L3 The first line Branch Pipe
L4 C
L5
N2 (56)
c D
d
E
Indoor unit
N3 (45)
N4 (45)
e
f
N5 (45)
N6 (56)
Fig.4-6
Caution: Suppose in the displayed piping system, the total equivalent piping length of air side + liquid side is longer than 90m.
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
Indoor unit branch pipe
Inner branch pipes are a~f, the size selection please refers to Table4-6.
Note: The max. length of the branch pipe should not longer than 15m.
The main pipes of indoor unit and the indoor unit branch pipe components The
downstream inner units of the main pipe L2 are N1, N2, and its total capacity
is 56×2=112, the size of pipe L2 is 15.9/9.5, and the branch pipe B should be
FQZHN-01D. The downstream inner units of the main pipe L4 are N3, N4, and its
total capacity is 45×2=90, the size of pipe L4 is15.9/9.5, and the branch pipe
D should be FQZHN-01D.
The downstream inner units of the main pipe L5 are N5, N6, and its total
capacity is 45+56=101, the size of pipe L5 is15.9/9.5, and the branch pipe E
should be FQZHN-01D.
The indoor unit below to the main pipe L3 are N3N6, and its total capacity is
45×3+56=191, the size of pipe L3 is19.1/9.5, and the branch pipe C should be
FQZHN-01D. The indoor unit below to the main pipe A are N1N6, and its total
capacity is 45×5+56=281, and the branch pipe should be FQZHN-02D, and because
the total piping length of liquid + air side is 90m, check Table.4-4, and the
first branch pipe should apply FQZHN-02D, and according to the principle of
maximum value, it should apply FQZHN-02D.
Main pipe (Please refer to Fig.4-6 and Table 4-4) In Fig.4-6, the main pipe
L1, the outdoor unit capacity is
28kW, and check the Table 4-4 to get the size of gas pipe/liquid pipe is
22.2/9.5, and aslo the total equivalent length of liquid side and gas side
pipes is >90m,then check the Table 4-4 to get the size of gas pipe/liquid pipe
is 25.4/12.7, and according to the maximum value principle, it should apply
the 25.4/12.7.
Allowable length and altitude difference of refrigerant pipe Pimitted value
Total Pipe Length(Actual)
150m
Pipe Length
Maximum Piping(L)
Actual Length Equivalent Length
Pipe Length(from the first line branch pipe to furhtest indoor unit)(m) Pipe
Length(from the nearest branch pipe equivalent length(m)
Outdoor Unit up Indoor Unit-Outdoor Unit Drop Height(H) Outdoor Unit Down
Indoor Unit to Indoor Unit Drop Heihgt(H)
100m
110m 40m 15m 50m 40m 15m
Drop Height
Piping
table 4-11
L1+L2+L3+L4+L5+a+b+c+d+e+f
L1+L2+L3+L4+L5+f(The first connect methond) or L1+L3+L5+f(The second connect
methond)
L2+L3+L4+L5+f(The first connect methond) or L3+L5+f(The second connect
methond)
a,b,c,d,e,f
Note: When the total equivalent piping length of liquid + gas side is 90m, it must increase the size of air side main pipe. Besides, according to the distance of refrigerant pipe and the over matched state of inner unit, when the capacity is decreasing it still can increase the gas side main pipe size.
The first cennect methond
Outdoor unit
Drop HEIGHT between indoor unit and uutdoor unit
L1 A
The first line Branch Pipe
L2
Pipe Length(from the nearest branch pipe equivalent length
a
Maximum pipe equivalent length
(from the first line branch pipe) Maximum pipe equivalent length
L3
B
C L4 D L5 E
b
c
d
ef
Indoor Unit
Indoor Unit to Indoor Unit Drop Heihgt
Fig.4-7
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
7
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
The second cennect methond
Drop HEIGHT between indoor unit and uutdoor unit Indoor Unit to Indoor Unit Drop Height
Outdoor unit
Maximum pipe equivalent length
L1
L2
A
L3
The first line Branch Pipe
Pipe Length(from the nearest branch pipe equivalent length
a B
b
N1 N2
(from the first line branch pipe) Maximum pipe equivalent length
L4
C L5
c
N3
D
N4
d
E
f
e N5
N6
Indoor unit
Fig.4-8
4.7 Remove Dirt or Water in the Piping
Make sure there is no any dirt or water before connectiong the piping to the
outdoor units. Wash the piping with high pressure nitrogen, never use
refrigerant of outdoor unit.
4.8 Airtight Test
Charge pressured nitrogen after connecting indoor/outdoor unit piping to do
airtight test.
CAUTION
1. Pressured nitrogen [ 4.3MPa (44kg/cm 2) for R410A] should be used in the
airtight test. 2. Tighten high pressure/low pressure valves before
applying pressured nitrogen. 3. Apply pressure from air vent mouth on the
hight pressure/
low pressure valves. 4. The high pressure/low pressure valves are closed when
applying pressured nitrogen. 5. The airtight test should never use any oxygen,
flammable gas or poisonous gas.
4.9 Air Purge with Vacuum Pump
Using vacuum pump to do the vacuum,never using refrigerant to expel the air.
Vacuuming should be done from both liquid side and gas side simultaneously.
4.10 Refrigerant Amount to be Added
Calculate the added refrigerant according to the diameter and the length of
the liquid side pipe of the outdoor unit/indoor unit connection.
When the outdoor unit connects 1 indoor unit:
Table 4-12
Liquid Side Piping Diameter
6.4 9.5
12.7 15.9 19.1 22.2
Refrigerant to be Added Permeter Piping
0.022kg 0.057kg
0.110kg 0.170kg 0.260kg 0.360kg
NOTE
Additional refrigerant volume of divergent pipe is 0.1kg per item (Consider
the liquid side of divergent pipe only)
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
8
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
5. ELECTRICAL WIRING
CAUTION
Design a dedicated power supply for the indoor unit and outdoor unit. If the
power supply uses a branch loop, install an electricity leakage protector and
a manual switch.
The power supply, electric leakage protectors, and manual switches of the
indoor units that connect to the same outdoor unit must be universal. Use the
same loop for the indoor unit power connect to the same outdoor unit must be
universal. Use the same loop for the indoor unit power supplies in the same
system. Power on/off at the same time.
Incorporate the outdoor unit and indoor unit connection wiring system and
refrigerant pipe system for the same system.
To reduce interference, use a three-core shielded twisted pair as the outdoor
unit signal cable. Do not use a multi-core cable.
Complete wiring according to national electrical standards. Employ an
electrical engineer for wiring.
Outdoor power supply Switch
Fuse
Power supply for the outdoor unit monitor
L N
Reserved (Optional)
K1 K2 E
L1 L2 L3 N
Outdoor unit K1 K2 E O A E X Y E P Q E
Digital ammeter power supply
To kilowatt-hour meter(Optional)
L N
OA E
Power supply for the central indoor unit controller
To centralized controller(Optional)
L N
X Y E
Use a shielded cable and ground the shielding layer
Outdoor power supply
Switch
LN
Fuse
PQE
Indoor unit
LN
Fuse
PQE
Indoor unit
LN
Fuse
PQE
Indoor unit
LN
Fuse
PQE
Indoor unit
Distribution box
Distribution box
Distribution box
Distribution box
280 Three-phase electrical control system connection of the outdoor unit
Fig.5-1
CAUTION
An incorrect connection configuration may damage the compressor or other
components. PQE is a signal cable, which must be connected to a weak current.
Do not connect it to strong current. All wiring terminals must be securely
fixed. The grounding wire must be grounded as required. After connecting to
the connector base, the power cable must be securely fixed. After all wires
are connected, check the correctness all components before powering on.
9
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
Outdoor unit
PQE
Note: The parts in the dotted line box are optional.Contact the local distributor to purchase them if required.
Use a shield cable and ground the shielding layer.
Indoor unit PQE
Indoor unit PQE
Indoor unit PQE
Indoor unit PQE
Wired Remote controller control
Wiring the indoor unit and outdoor unit control
Add a build-out resistor at the P/Q end of the last indoor unit only. Build-
out resistor
Fig. 5-2
CAUTION
When the power cable is parallel to the signal cable, insert electric wires in
their respective electric wire pipes and reserve a proper inter-wire distance.
(distance between power cables: lower than 10 A 300 mm; lower than 50 A 500
mm) Use a three-core shielded cable as the indoor/outdoor unit signal cable,
and ground the shielding layer as required. The display box, remote control,
and build-out resistor are accessories for the indoor unit. The wired
controller is optional. To purchase a wired controller, contact your local
distributor.
5.1 Outdoor Unit Wiring
Functions of Outdoor Unit Wiring Terminals
L1 L2 L3 N
XT1
Power Supply
Reserved
To kilowatt- To centralized To indoor units com-
hour meter controller
munication bus
20 – 28kW
K1 K2 E O A E X Y E P Q E
Note:Use a three-core shielded cable, and ground the shielding layer
The Specification of Power
Table 5-1
Power Source
380-415V 3N~ 50 Hz
Model
Capicity(kW)
20
22 26 28 33.5
Hz
50
Voltage
380-415
Power Supply
Min.(V) Max.(V) Min Circuit Amps.
342
456
19
19 20.5 21 26.4
Total Over-current Amps. 24.3 24.3 24.3 24.3 33.2
Max Fuse Amps.
25
25 25 25 32
Compressor
MSC RLA
/
/
/
/
/
12 12.4 15 18.4 19.6
kW OFM
FLA
2×0.17 2.1+2.1
CAUTION
Equipment complying with IEC 61000-3-12. A disconnection device having an air
gap contact separation in all active conductors should be incorporated in the
fixed wiring according to the National Wiring Regulation. The reserved
function is indicated in broken line table,users can select it when necessary.
Outdoor unit monitor
Digital Central indoor ammeter unit controller
33.5kW
Indoor and outdoor unit communication
Fig. 5-3
Indoor/Outdoor Unit Signal Wire Connect the wire according to their numbers.
10
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
Wrong connection may cause malfunction . Wiring Connection Seal the wiring
connection with the insulation material , or the condensing dew will be
caused.
NOTE
The air-conditioners can connect with Central Control Monitor (CCM). Before
operation, please wiring correctly and set system address and network address
of indoor units
5.2 Indoor Unit Wiring
Power Supply
Capicity(kW)
1.8~16
Table 5-2
Indoor Unit Power
Specifications
Power Wiring Size(mm²)
Circuit Breaker (A)
Indoor Unit /Outdoor Unit Signal Wire (mm2) (Weak electric signal)
220-240V~ 50Hz
3×2.5 16
Three-core shielded wire 3×0.75
Single phase indoor unit
WHITE BLUE BLACK YELLOW GRAY BLACK
LN
XYE P QE
Y/G
XT1
XT3
Display board
Wire controller
Power Supply
To Central Control To Outdoor Monitor (CCM) COMM.BUS COMM. BUS
To wire controller The reserved wire control function is indicated in broken
line table, users can purchase
Please use three-core shielded wire, and the wire controller when
connect the shielded layer to Grounding necessary.
Fig. 5-4
1. Signal wire is three-core, polarized wire. Use three-core shield wire to
prevent interference. The grounding method now is grounding the closed end of
the shield wire and opening (insulating) at the end. Shield is to be grounded.
2. The control between outdoor unit and indoor unit is BUS type. Addresses is
set on field during the installation.
CAUTION
Indoor/Outdoor unit signal wire is low voltage circuit. Do not let it touch
the high voltage power wire and put it to gather with power cord in the same
wire distribution pipe.
NOTE
The wire diameter and continuous length is under the condition that the
voltage vibration is within 2%. If the continuous length is exceed showing
value, choose the wire diameter follow relevant regulation.
Indoor unit power supply wiring
Indoor Power Supply Circuit Breaker Manual swtich
Wire Distribution Box
Indoor Unit
Fig. 5-5
CAUTION
1. Refrigerant piping system, indoor unit-indoor unit connection signal wires
and indoor unit-outdoor unit connection singal wire are in the same system.
2. When power cord is parallel with signal wire, please put them into
separate wire distribution pipes, and leave a proper distance. (Reference
distance: It is 300mm when current capacity of power cord is less than 10A, or
500mm when 50A).
Please use shield wire as indoor unit/outdoor unit signal wire. Indoor/Outdoor
unit signal wire wiring
Outdoor Unit Close end of the connection shielded wire
Indoor/Outdoor Unit Signal Wire
(open)
in broken line table, users can purchase the wire controller when necessary.
Fig. 5-6
CAUTION
The length of signal wire must not exceed 1200m. A communication error may
result when the signal wiring exceeds these limitations.
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
11
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
6. TEST RUNNING
Operate according to “gist for test running” on the electric control box
cover.
CAUTION
Test running can not start until the outdoor unit has been connected to the
power for 12hr. Test running can not start until all the valves are affirmed
open. Never make the forced running. (Or the protector sits back, danger will
occur.)
7. CONFIGURATION
7.1 Overview
This chapter describes how the system configuration can be implemented once
the installation is complete, and other relevant information. It contains the
following information: Implement field settings Energy-saving and optimized
operation
i Information
The installation personnel should read this chapter.
7.2 Dial Switch Settings Dial code definitions:
means 0
means 1
Table 7-1 For 200 to 280 unit only
Table 7-1
ENC1 &
S9-3
ENC3 S1-1 S1-2 S1-3
S2
S9-1 S9-2
0-F The number of indoor units is in the range 0-15 0-9 on ENC1 indicate 0-9
indoor units;
0 A-F on ENC1 indicate 10-15 indoor units
1 2 3
0-F The number of indoor units is in the range 16-31 0-9 on ENC1 indicate
16-25 indoor units;
1 A-F on ENC1 indicate 26-31 indoor units
1 2 3
0-7
Outdoor unit network address setting, Only 0 to 7 should be selected (default is 0).
0 When connected to 2nd generation DC indoor unit(default)
1 2 3 1 When connected to AC or 1st generation DC indoor unit 0 Auto addressing (default)
1 2 3 1 Clear indoor unit addresses
0 Reserved 1 2 3 1 Factory test only
000 Auto priority (default) 100 Cooling priority
010 First ON priority 1 2 3 110 Heating only
001 Cooling only
Other combinations,Heating priority
00 Outdoor unit capacity,280
01 1 2 3 10
11
Outdoor unit capacity,260 Reserved Outdoor unit capacity,224/200(customer)
Table 7-2 For 335 unit only,335 unit adopt different PCB
Table 7-2
0-F The number of indoor units is in the range 0-15
0-9 on ENC1 indicate 0-9 indoor units;
ENC1 1 2 3 0 A-F on ENC1 indicate 10-15 indoor units &
S9-3
0-F The number of indoor units is in the range 16-31
0-9 on ENC1 indicate 16-25 indoor units;
1 A-F on ENC1 indicate 26-31 indoor units
1 2 3
ENC3
0-7
Outdoor unit network address setting, Only 0 to 7 should be selected (default is 0).
0 When connected to 2nd generation DC indoor unit(default)
S1-1 1 2 3
1
When connected to AC or 1st generation DC indoor unit
0 Auto addressing (default) S1-2
1 2 3 1 Clear indoor unit addresses
0 Reserved S1-3
1 2 3 1 Reserved
000 Auto priority (default)
100 Cooling priority
010 First ON priority S2 1 2 3 110 Heating only
001 Cooling only
Other combinations,Heating priority
0 Reserved S9-1
1 2 3 1 Outdoor unit capacity,12HP
0 Reserved S9-2
1 2 3 1 Factory test only
NOTE
Please cut off the power supply when changing the dial switch
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
12
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
8. PRECAUTIONS ON REFRIGERANT LEAKAGE
This air conditioner(A/C) adopts inncouous and nonflammable refrigerant. The
locating room of the A/C should big engough that any refrigerant leakage is
unable to reach critical thickness. So certain esssential action can be taken
on time.
Critical thickness——the Max. thickness of Freon without any harm to person.
Refrigerant critical thickness: 0.44[kg/m3] for R410A.
Confirm the critical thickness through follow steps, and take necessary
actions.
1. Calculate the sum of the charge volume (A[kg]) Total Refrigerant volume of
10HP=factory refrigerant volume + superaddition
2. Calculate the indoor cubage (B[m3]) (as the minimum cubage.
3. Calculate the refrigerant thickness
A[kg]
ImplemBe[mnt3]field
critical thickness settings
Coun tEenr emrgeya-ssuarveinaggaainndstoopvtiemrihzeigdhothpiecrkantieosns
1. Installmechanicalventilator to reduce the refrigerant thickness under critical level. (ventilate regularly)
2. Install leak alarm facility related to mechanical ventilator if you can not regularly ventilate.
Outdoor unit
Indoor unit Room full of leak refrigerant
(All refrigerant has run up) b. Leak alarm related to mechanical ventilator
Indoor unit
A. Ventilation
(Leak hunting siren should be installed in peristome
places easily keep refrigerant)
Fig. 8-1
8.1 Important information for the used refrigerant
This product has the fluorinated gas, it is forbidden to release to air. Refrigerant type: R410A; Volume of GWP: 2088; GWP=Global Warming Potential
Model
Factory charge
Refrigerant/kg
tonnes CO2 equivalent
20-28kW
6.5
13.57
33.5kW
8
16.71
Attention: Frequency of Refrigerant Leak Checks
- For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more,but of less than 50 tonnes of CO2 equipment,at least every 12 months, or where a leakage detection system is installed, at least every 24 months
- For equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more,but of less than 500 tonnes of CO2 equipment,at least every six months, or where a leakage detection system is installed, at least every 12 months.
- For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more,at least every three months, or where a leakage detection system is installed, at least every six months.
- Non-hermetically sealed equipment charged with fluorinated greenhouse gases shall only be sold to the end user where evidence is provide that the installation is to be carried out by an undertaking certified person.
- Only certificated person is allowed to do installation, operation and maintenance.
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
13
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
9 ERRPOR CODES
Error code
Error description
Remarks
Communication error between main board and H0 compressor drive board
H4 Inverter-module protection
H5 3 times of P2 protection in 30 minutes
Irrecoverable
H7 Qty. of indoor units mismatching
Irrecoverable
H8 High pressure sensor error
HF M-HOME for the indoor and outdoor units does not match Irrecoverable
E1 Phase sequence error
E2 Communication error between indoor and master unit
E4 T3 or T4 temperature sensor error
E5 Abnormal power supply voltage
E6 DC fan motor error
Eb E6 protection appears 6 times in 1 hour
Irrecoverable
E7 Discharge temperature sensor error
EH TL sensor fault
P1 High pressure protection
P2 Low pressure protection
P3 Compressor current protection
P4 Discharge Temp. protection
P5 High Temp. protection of condenser
P8 Typhoon protection
PL Inverter module Temp. protection
L0 Inverter compressor module error
L1 DC bus low voltage protection
L2 DC bus high voltage protection
L4 MCE error
L5 Zero speed protection
L7 Phase sequence protection
Compressor frequency variation greater than 15Hz L8 within one second protection
L9
Actual compressor frequency differs from target frequency by more than 15Hz protection
F1 DC bus voltage error
DC bus voltage error
bH PED protection board error bL High pressure switch protection on driver board
The troubleshooting for each error code, please refer to the service manual.
10. TURN OVER TO CUSTOMER
The owner’s manual of indoor unit and owner’s manual of outdoor or unit must be turned over to the customer. Explain the contents in the owner’s manual to the customers in details.
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
14
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
Cooling mode:
Table.3
Information requirements for air-to-air conditioners
Model(s): SYSVRF2 224 AIR EVO A HP R; Test matching indoor units form, non-
duct : 4× SYSVRF CASSETTE 56 Q;
Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Type:compressor driven
If applicable:driver of compressor:electric motor
Item
Symbol Value
Unit
Rated cooling capacity Prated,c
22.4
kW
Item
Seasonal space cooling energy efficiency
Symbol s,c
Value Unit
270.2
%
Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27/19dry/wet bulb
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35
Pdc
22.4
kW
Tj=+35
EERd
3.31
—
Tj=+30
Pdc
16.645
kW
Tj=+30
EERd
4.57
—
Tj=+25 Tj=+20
Pdc
10.990
kW
Pdc
6.399
kW
Tj=+25 Tj=+20
EERd EERd
8.61
—
12.8
—
Degradation co-efficient for air conditioners(*)
Cdc
0.25
Power consumption in modes other than “active mode”
Off mode Thermosat-off mode
POFF PTO
0.04 0
kW
Crankcase heater mode
PCK
kW
Standby mode
PSB
Other items
Capacity control
Sound power level,outdoor
variable
LWA
78
dB
For air-to-air air conditioner:air flow rate,outdoor measured
GWP of the refrigerant
2088 kg CO2 eq(100years)
Contact details (*)If Cdc is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
0
kW
0.04
kW
9000
m3/h
Where information relates to multi-split air conditioners,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
17
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
Heating mode:
Table.4
Information requirements for heat pumps
Model(s): SYSVRF2 224 AIR EVO A HP R; Test matching indoor units form, non-
duct : 4×SYSVRF CASSETTE 56 Q; Outdoor side heat exchanger of air
conditioner:air Indoor side heat exchanger of air conditioner:air
Idication if the heater is equipped with a supplementary heater:no
If applicable:driver of compressor:electric motor Parameters shall be declared
for the average heating season,parameters for the warmer and colder heating
seasoms are optional
Item
Symbol Value
Unit
Item
Symbol
Value Unit
Rated heating capacity Prated,h
22.4
kW
Declared heating capacity for part load at indoor teperature 20¥ and outdoor temperatures Tj
Seasonal space heating energy efficiency
s,h
167.4 %
Declared coefficient of performance or gas utilisation efficiency/auxiliary
energy factor for part load at given outdoor
temperatures Tj
Tj=-7¥
Pdh
12.113
kW
Tj=-7¥
COPd
3.22
—
Tj=+2¥
Pdh
7.272
kW
Tj=+2¥
COPd
3.56
—
Tj=+7¥
Pdh
5.825
kW
Tj=+7¥
COPd
6.76
—
Tj=+12¥
Pdh
3.703
kW
Tbiv=bivalent temperature
Pdh
12.113
kW
TOL=operation temperature
Pdh
13.74
kW
Bivalent temperature
Tbiv
-7
¥
Tj=+12¥ Tbiv =bivalent temperature TOL =operation temperature
COPd COPd COPd
7.76
—
3.22
—
2.35
—
Degradation co-efficient for heat pumps(**)
Cdh
0.25
Power consumption in modes other than “active mode”
Supplementary heater
Off mode
POFF
0.04
kW
Back-up heating capacity(*)
elbu
Thermosat-off mode
PTO
0.04
kW
Type of energy input
Crankcase heater mode PCK
0
kW
Standby mode
PSB
Other items
Capacity control
Sound power level,outdoor
variable
LWA
78
dB
For air-to-air heat pump:air flow rate,outdoor measured
GWP of the refrigerant
2088
kg CO2 eq(100years)
Contact details
(*)
0
kW
0.04
kW
9000
m3/h
(**)If Cdh is not determined by measurement then the default degradation
coefficient of heat pumps shall be 0.25
Where information relates to multi-split heat pumps,the test result and
performance data may be obtained on the basis of performance of the outdoor
unit ,with a combination of indoor unit(s) recommended by the manufacturer or
importer
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
18
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
Cooling mode:
Table.5
Information requirements for air-to-air conditioners
Model(s): SYSVRF2 260 AIR EVO A HP R; Test matching indoor units form, non-
duct : 2×SYSVRF CASSETTE 45 Q + 2×SYSVRF CASSETTE 90 Q;
Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Type:compressor driven
If applicable:driver of compressor:electric motor
Item
Symbol Value
Unit
Rated cooling capacity Prated,c
26
kW
Item
Seasonal space cooling energy efficiency
Symbol s,c
Value Unit
259
%
Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27/19dry/wet bulb
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35
Pdc
26
kW
Tj=+35
EERd
2.59
—
Tj=+30
Pdc
18.843
kW
Tj=+30
EERd
4.53
—
Tj=+25
Pdc
12.745
kW
Tj=+25
EERd
8.35
—
Tj=+20
Pdc
6.330
kW
Tj=+20
EERd
12.66
—
Degradation co-efficient for air conditioners(*)
Cdc
0.25
Power consumption in modes other than “active mode”
Off mode Thermosat-off mode
POFF PTO
0.04 0
kW
Crankcase heater mode
kW
Standby mode
Other items
PCK
0
kW
PSB
0.04
kW
Capacity control
Sound power level,outdoor
variable
LWA
78
dB
For air-to-air air conditioner:air flow rate,outdoor measured
10000 m3/h
GWP of the refrigerant
2088 kg CO2 eq(100years)
Contact details (*)If Cdc is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
Where information relates to multi-split air conditioners,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
19
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
Heating mode:
Table.6
Information requirements for heat pumps
Model(s): SYSVRF2 260 AIR EVO A HP R; Test matching indoor units form, non-
duct : 2×SYSVRF CASSETTE 45 Q + 2×SYSVRF CASSETTE 90 Q; Outdoor side heat
exchanger of air conditioner:air Indoor side heat exchanger of air
conditioner:air Idication if the heater is equipped with a supplementary
heater:no If applicable:driver of compressor:electric motor Parameters shall
be declared for the average heating season,parameters for the warmer and
colder heating seasoms are optional
Item
Symbol Value
Unit
Item
Symbol
Value Unit
Rated heating capacity Prated,h
26
kW
Declared heating capacity for part load at indoor teperature 20¥ and outdoor temperatures Tj
Seasonal space heating energy efficiency
s,h
178.2 %
Declared coefficient of performance or gas utilisation efficiency/auxiliary
energy factor for part load at given outdoor
temperatures Tj
Tj=-7¥
Pdh
13.663
kW
Tj=-7¥
COPd
3.17
—
Tj=+2¥
Pdh
8.703
kW
Tj=+2¥
COPd
3.90
—
Tj=+7¥
Pdh
6.027
kW
Tj=+7¥
COPd
7.17
—
Tj=+12¥
Pdh
3.881
kW
Tbiv=bivalent temperature
Pdh
13.633
kW
TOL=operation temperature
Pdh
15.861
kW
Bivalent temperature
Tbiv
-7
¥
Tj=+12¥ Tbiv =bivalent temperature TOL =operation temperature
COPd COPd COPd
8.36
—
3.17
—
2.32
—
Degradation co-efficient for heat pumps(**)
Cdh
0.25
Power consumption in modes other than “active mode”
Supplementary heater
Off mode
POFF
0.04
kW
Back-up heating capacity(*)
elbu
Thermosat-off mode
PTO
0.04
kW
Type of energy input
Crankcase heater mode PCK
0
kW
Standby mode
PSB
Other items
Capacity control
Sound power level,outdoor
variable
LWA
78
dB
For air-to-air heat pump:air flow rate,outdoor measured
GWP of the refrigerant Contact details
2088
kg CO2 eq(100years)
(*)
0
kW
0.04
kW
10000 m3/h
(**)If Cdh is not determined by measurement then the default degradation
coefficient of heat pumps shall be 0.25
Where information relates to multi-split heat pumps,the test result and
performance data may be obtained on the basis of performance of the outdoor
unit ,with a combination of indoor unit(s) recommended by the manufacturer or
importer
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
20
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
Cooling mode:
Table.7
Information requirements for air-to-air conditioners
Model(s): SYSVRF2 280 AIR EVO A HP R; Test matching indoor units form, non-
duct : 2×SYSVRF CASSETTE 56 Q + 2×SYSVRF CASSETTE 90 Q;
Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Type:compressor driven
If applicable:driver of compressor:electric motor
Item
Symbol Value
Unit
Rated cooling capacity Prated,c 28
kW
Item
Seasonal space cooling energy efficiency
Symbol s,c
Value Unit
251
%
Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27/19dry/wet bulb
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35
Pdc
28
kW
Tj=+35
EERd
2.33
—
Tj=+30
Pdc
20.662
kW
Tj=+30
EERd
4.31
—
Tj=+25 Tj=+20
Pdc
13.537
kW
Pdc
6.328
kW
Tj=+25 Tj=+20
EERd EERd
8.16
—
12.66
—
Degradation co-efficient for air conditioners(*)
Cdc
0.25
Power consumption in modes other than “active mode”
Off mode
POFF
0.04
kW
Thermosat-off mode
PTO
0
kW
Crankcase heater mode Standby mode
PCK
0.04
kW
PSB
0.04
kW
Other items
Capacity control
Sound power level,outdoor
variable
LWA
78
dB
For air-to-air air conditioner:air flow rate,outdoor measured
11000 m3/h
GWP of the refrigerant
2088
kg CO2 eq(100years)
Contact details (*)If Cdc is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
Where information relates to multi-split air conditioners,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
21
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
Heating mode:
Table.8
Information requirements for heat pumps
Model(s): SYSVRF2 280 AIR EVO A HP R; Test matching indoor units form, non-
duct : 2×SYSVRF CASSETTE 56 Q + 2×SYSVRF CASSETTE 90 Q; Outdoor side heat
exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Idication if the heater is equipped with a supplementary heater:no
If applicable:driver of compressor:electric motor
Parameters shall be declared for the average heating season,parameters for the
warmer and colder heating seasoms are optional
Item
Symbol Value
Unit
Item
Symbol
Value Unit
Rated heating capacity Prated,h
28
kW
Seasonal space heating energy efficiency
s,h
179.4
%
Declared heating capacity for part load at indoor teperature 20¥ and outdoor temperatures Tj
Declared coefficient of performance or gas utilisation efficiency/auxiliary
energy factor for part load at given outdoor
temperatures Tj
Tj=-7¥
Pdh
15.715
kW
Tj=-7¥
COPd
2.93
—
Tj=+2¥
Pdh
9.445
kW
Tj=+2¥
COPd
3.99
—
Tj=+7¥
Pdh
6.060
kW
Tj=+7¥
COPd
7.26
—
Tj=+12¥
Pdh
3.906
kW
Tbiv=bivalent temperature
Pdh
15.715
kW
TOL=operation temperature
Pdh
17.534
kW
Bivalent temperature
Tbiv
-7
¥
Tj=+12¥ Tbiv =bivalent temperature TOL =operation temperature
COPd COPd COPd
8.48
—
2.93
—
2.21
—
Degradation co-efficient for heat pumps(**)
Cdh
0.25
Power consumption in modes other than “active mode”
Supplementary heater
Off mode
POFF
0.04
kW
Back-up heating capacity(*)
elbu
Thermosat-off mode
PTO
0.04
kW
Type of energy input
Crankcase heater mode PCK
0
kW
Standby mode
PSB
Other items
Capacity control
Sound power level,outdoor
variable
LWA
78
dB
For air-to-air heat pump:air flow rate,outdoor measured
GWP of the refrigerant
2088
kg CO2 eq(100years)
Contact details
(*)
0 0.04 11000
kW kW m3/h
(**)If Cdh is not determined by measurement then the default degradation
coefficient of heat pumps shall be 0.25
Where information relates to multi-split heat pumps,the test result and
performance data may be obtained on the basis of performance of the outdoor
unit ,with a combination of indoor unit(s) recommended by the manufacturer or
importer
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
22
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North
Yorkshire, BD24 9RH
Certified: www.systemair.com
16100101A05013 V.F
Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk
Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire,
BD24 9RH
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>