SYSTY Mair SYSVRF2 Outdoor unit Mini VRF Heat Pump Installation Guide

June 5, 2024
SYSTY Mair

SYSVRF2 Outdoor unit Mini VRF Heat Pump

SYSVRF2 AIR EVO A HP R

GB Outdoor unit Mini VRF Heat Pump
INSTALLATION MANUAL

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

CONTENTS

PAGE

PRECAUTIONS…………………………………………………………………………….1 ATTACHED FITTINGS……………………………………………………………………2 OUTDOOR UNIT INSTALLATION……………………………………………………..3 INSTALL THE CONNECTING PIPE……………………………………………………4 ELECTRICAL WIRING……………………………………………………………………9 TEST RUNNING………………………………………………………………………….12 CONFIGURATION………………………………………………………………………..12 PRECAUTIONS ON REFRIGERANT LEAKAGE…………………………………..13 ERROR CODES…………………………………………………………………………..14 TURN OVER TO CUSTOMER…………………………………………………………14

1. PRECAUTIONS
Ensure that all Local, National and International regulations are satisfied. Read this “PRECAUTIONS ” carefully before Installation. The precautions described below include the important items regarding safety. Observe them without fail. After the installation work, perform a trial operation to check for any problem. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer. Turn off the main power supply switch (or breaker) before maintenance the unit . Ask the customer that the Installation Manual and the Owner’s Manual should be kept together .

CAUTION
New Refrigerant Air Conditioner Installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT(R410A)WHICH DOES NOT DESTROY OZONE LAYER. The characteristics of R410A refrigerant are; Hydrophilic, oxidizing membrane or oil, and its pressure is approx.1.6 times higher than that of refrigerant R22.Accompanied with the new refrigerant, refrigerating oil has also been changed ,Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle. To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are charged from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A): For connecting pipes, use new and clean piping designed for R410A,and please care so that water or dust does not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance force and impurity in it.

CAUTION
Do not connect the Appliance from Main Power Supply directly.
WARNING
Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner. Inappropriate installation may result in water leakage,electric shock or fire. Turn off the main power supply switch or breaker before attempting any electrical work. Make sure all power switches are off.Failure to do so may cause electric shock. Connect the connecting cable correctly. If the connecting cable is connected in a wrong way, electric parts may be damaged. When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle. If air or any other has is mixed in refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it may resultingly causes pipe burst and injuries on persons. Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches. Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical parts. Do not store it in a wet basement or expose to rain or water. After unpacking the unit, examine it carefully if there are possible damage. Do not install in a place that might increase the vibration of the unit. To avoid personal injury (with sharp edges), be careful when handling parts. Perform installation work properly according to the Installation Manual. Inappropriate installation may result in water leakage, electric shock or fire. When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level. Install the air conditioner securely in a location where the base can sustain the weight adequately. Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to the falling unit. If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate. After the installation work, confirm that refrigerant gas doer not leak. If refeigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate. Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply. The appliance shall be installed in accordance with national wiring regulations. If the supply cord is damaged, it must be replaced by the manufacture or its service agent or a similarly qualified person in order to avoid a hazard. An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring. The dimensions of the space necessary for correct installation of the appliance including the minimum permissible distances in order to avoid a hazard.

1

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube. The power cord type designation is H05RN-For above/H07RN-F.
An insufficient power supply capacity or inappropriate installation may cause fire. Use the specified cables for wiring connect the terminals securely fix. To prevent external forces applied to the terminals from affecting the terminals. Be sure to provide grounding. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables. Conform to the regulations of the local electric company when wiring the power supply. Inappropriate grounding may cause electric shock. Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks, and stays around the unit, a fire may occur. For appliances intended for use at altitudes exceeding 2000m, the maximum altitude of use shall be stated.
Required tools for installation work 1) Philips screw driver 2) Hole core drill(65mm)

  1. Spanner 4) Pipe cutter 5) Knife 6) Reamer 7) Gas leak detector 8) Tape measure 9) Thermometer 10) Mega-tester 11) Electro circuit tester 12) Hexagonal wrench 13) Flare tool 14) Pipe bender 15) Level vial 16) Metal saw
  2. Gauge manifold (Charge hose:R410A special requirement) 18) Vacuum pump (Charge hose:R410A special requirement) 19) Torque wrench
    1/4(17mm)16N·m (1.6kgf·m) 3/8(22mm)42N·m (4.2kgf·m) 1/2(26mm)55N·m (5.5kgf·m) 5/8(15.9mm)120N·m (12.0kgf·m) 20) Copper pipe gauge adjusting projection margin 21) Vacuum pump adapter

2. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.

NAME 1. Outdoor unit installation manual

2. Outdoor unit owner’s manual

INSTALLATION FITTINGS

3. Installation Instructions: Indoor Unit Manifold
4.Water outlet connection pipe

5.Matched resistance 6.Waterproof chassis cover

7.Connection pipe(26/28/33.5kW)

SHAPE

QUANTITY 1 2 1 1 2 2 1

Refrigerant Piping Piping kit used for the conventional refrigerant cannot be used. Use copper pipe with 0.8 mm or more thickness for 9.5. Use copper pipe with 1.0 mm or more thickness for 15.9. Use copper pipe with 1.0 mm or more thickness for 19.0. Flare nut and flare works are also different form those of the conventional refrigerant.take out the flare nut attached to the main unit of the air conditioner, and use it.
Before installation Be careful to the following items before installation.
Air purge For air purge, use a vacuum pump. Do not use refrigerant charged in the outdoor unit for air purge. (The refrigerant for air purge is not contained in the outdoor unit.)
Electrical cabling Be sure to fix the power cables and indoor/outdoor connecting cables with clamps so that they do not contact with the cabinet, etc.

Installation Place A place which provides a specified space around the outdoor unit. A place were the operation noise and discharged air are not given to your neighbors. A place that is not exposed to a strong wind. A place that does not block a passage. When the outdoor unit is installed in an elevated position, make sure it’s four feet securely installed. There must be sufficient space for carrying in the unit. A place where the drain water does not make any problem.
CAUTION
Install the outdoor unit at a place where discharge air is not blocked. When an outdoor unit is installed in a place that is always exposed to a strong wind like a coast or on a high storey of a building, secure a normal fan operation by using a duct or a wind shield.

2

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

When installing the outdoor unit in a place that is constantly exposed to a strong wind such as the upper stairs or rooftop of a building, apply the windproof measures referring to the following examples. Install the unit so that its discharge port faces to the wall of the building. Keep a distance 3000mm or more between the unit and the wall surface. Do not mount the outdoor unit on a wall.
3000

The insulation of the metal parts of the building and the air conditioner should comply with the regulation of National Electric Standard.
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from televisions and radios. This is to prevent image interference and noise in those electrical appliances. (Noise may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is kept.)
3.2 Installation space (Unit:mm)

Fig.2-1 Supposing the wind direction during the operation season of the discharge port is set at right angle to the wind direction.

Strong wind

Strong wind

1558

1120

668

206

440 400 494 528

Fig.2-2
Installation in the following places may result in some troubles. Do not install the unit in such places below.
A place full of machine oil. A place full of sulphuric gas. A place where high-frequency radio waves are likely to be generated as from audio quipment, welders, and medical equipment.
3. OUTDOOR UNIT INSTALLATION
3.1 Installation place
Please keep away from the following place, or malfunction of the machine may be caused:
There is combustible gas leakage. There is much oil (including engine oil) ingredient. There is salty air surrounding(near the coast) There is caustic gas (the sulfide, for example) existing in the air (near a hotspring) A place the heat air expelled out from the outdoor unit can reach your neighbor’s window. A place that the noise interferes your neighbors every day life. A place that is too weak to bear the weight of the unit Uneven place. Insufficient ventilation place. Near a private power station or high Frequency equipment. Install indoor unit, outdoor unit, power cord and connecting wire at least 1m away from TV set or radio to prevent noise or picture interference.
3

Single unit installation
(Wall or obstacle) Air inlet >300
Air inlet

300

Fig.3-1
Maintain the electric wire and pipeline >600

3000

Air outlet

Parallel connect the two units or above

300 >3000

600

Parallel connect the front with rear sides

Fig.3-2 Fig.3-3

3000

1000

6000

4000

300

Fig.3-4

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

3.3 Moving and installation
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling. Never hold the inlet of the outdoor unit to prevent it from deforming. Do not touch the fan with hands or other objects. Do not lean it more than 45°, and do not lay it sidelong. Make concrete foundation according to the sepecifications of the outdoor units.(refer to Fig.3-5) Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind. (refer to Fig.3-5)

4. INSTALL THE CONNECTING PIPE
Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements:

600

Fix with bolt

4.1 Refrigerant piping

Fig.4-1

Fig.3-5

NOTE
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased(depend on model).The actual shape shall prevail.

3.4 Centralized Chassis Drainage
When the outdoor unit requires centralized drainage, install the chassis and two waterproof covers for the chassis, as shown in Figure 3-6. Install the water outlet union pipe and sealing ring on the chassis, and then connect the drainage pipe to complete centralized drainage installation.

Waterproof chassis cover

Sealing ring for the water outlet union pipe

CAUTION
Please pay attention to avoid the components while connect to the connecting pipes. To prevent the refrigerant piping from oxidizing inside when welding, it is necessary to charge nitrogen, or oxide will chock the circulation system.
The indoor and outdoor connecting pipe interface and power line outlet
Vavious piping and viring patterns can be selected,such as out from the front ,the back the side ,and undersurface, etc.(The follow display the locations of several piping and wiring knock-off interfaces)
Table 4-1

Front out pipe

Side out pipe

Fig.3-6
CAUTION
While installing the outdoor unit, pay attention to the installation place and the drainage pattern; if it’s installed at the alpine zone, the frozen condensed water will block up the water outlet, please pull out the rubber stopper of the reserve water outlet. If that still fails to satisfy for the water draining, please knock open the other two water outlets, and keep the water can drain in time. Pay attention to the knock the reserve water outlet from outside to inside, and it will be beyond repair after knocking open, please pay attention to the installation place, lest cause the inconvenience. Please do the moth proofing for the knocked out hole, to avoid the pest processing into and destroy the components.

CAUTION
1. Side out pipe: cut the side hole of the pipe-outlet plate selectively. It is suggested to cut a piece of metal plate below to avoid the mouse come and destroy the machine wiring body. 2.Front out pipe: cut the frontal hole of the pipe-outlet plate selectively. It is suggested to cut a piece of metal plate right side to avoid the mouse come and destroy the machine wiring body. 3. Wiring of power cord: the strong and weak electrical wire should be out through the two plastic holes of the pipe-outlet plate, and binded with gas and liquid pipe together.
4.2 Leak Detection
Use soap water or leak detector to check every joint whether leak or not (Refer to Fig.4-2).Note:
A is low pressure side stop valve B is high pressure side stop valve C and D is connecting pipes interface of indoor and outdoor units

4

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Check point of indoor unit

D

C

B

A

Check point of outdoor unit

4.3 Heat Insulation

Fig. 4-2

Do the heat insulation to the pipes of air side and liquid side separately. The temperature of the pipes of air side and liquid side when cooling, for avoiding condensation please do the heat insulation fully.
The air side pipe should use closed cell foamed insulation material, which the fire-retardant is B1 grade and the heat resistance over 120°C.
When the external diameter of copper pipe12.7mm, the thickness of the insulating layer at least more than 15mm;
When the external diameter of copper pipe15.9mm, the thickness of the insulating layer at least more than 20mm.
Please use attached heat-insulating materials do the heat insulation without clearance for the connecting parts of the indoor unit pipes.

Cut from upward

The unit body

Site pipe side Affiliated heat pump belt
Fig. 4-3

4.4 Connecting method

Select refrigerant pipe

Table 4-2 pipe definition

pipe connect position

code

main pipe

The pipe between outdoor unit to the L1 first branch of indoor unit.

The main pipes of indoor unit

The pipe after the first branch do not direct connect with the indoor unit.

L2L5

The branch pipes The pipe after the branch connect with a,b,c,

of indoor unit

the indoor unit.

d,e,f

Indoor unit branch pipes components

The pipes connect with the main pipe the branch pipe and the the main pipe of indoor unit.

A,B,C, D,E

The first connect methond
Outdoor Unit

L1

A

L2 B

L3

L4 C
c

L5
D d

E e

f

a

b

The first Line Branch Pipe

Fig. 4-4

The second connect methond

Outdoor Unit(Take Model 280 for example)

L1 A
The first Line Branch Pipe

N1

(56)

a

L2 B

intdoor Units

b

N2

(56)

N3

L3 L4
C L5

c D
d

(45)
N4 (45)
e

E

f
N5 (45)

N6 (56)

Fig. 4-5

NOTE
The distance between the first branch to the last indoor unit is more than 15m,choose the second connect methond. The pipe between the indoor unit to the closest branch must less than 15m.

4.4 Confirmation for the diameters of indoor unit connecting pipes

Size of main pipe and corresponding branch joint and branch header

  1. R410A Indoor unit connecting pipes diameters 4-3 2) Example 1In the Fig.4-5,The downstream inner units of the L4,and its total capacity is 45×290refers to the Table 4.4,the air/liquid side of L4 is15.9/9.5

R410A Indoor unit connecting pipes diameters

Table 4-3

Capacity of the downstream indoor unit
A166

Main pipe size (mm)

Air pipe

Liquid pipe

15.9

9.5

Applicable manifold
FQZHN-01D

166A230

19.1

9.5

FQZHN-01D

230A330

22.2

9.5

FQZHN-02D

330A470

25.4

12.7

FQZHN-03D

4.5 Confirmation for the diameters of outdoor

unit connecting pipes

R410A outdoor unit connecting pipes diameters

Table 4-4

Total capactiy of The
outdoor

Main pipe size when the total equivalent piping length of liquid + gas side is <90m

Main pipe size when the total equivalent piping length of liquid + gas side is 90m

units Gas side Liquid si- The first Line Gas side Liquid si- The first Line

(mm) de(mm) Branch Pipe (mm) de(mm) Branch Pipe

20-28KW 22.2 9.5 FQZHN-02D 25.4 12.7 FQZHN-03D

33.5KW 25.4 12.7 FQZHN-03D 25.4 12.7 FQZHN-03D

NOTE
The straight distance between copper pipe turning and the contiguous branch pipe is at least 0.5m; The straight distance between the contiguous branchpipes is at least 0.5m; The straight distance which the branch pipes connected to the indoor unit is at least 0.5m;

5

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Branch header must be connected with indoor units directly, the further branch connection is not allowed.

Select branch joint
Select the branch joint according to the total designed capacity of indoor units which it connects to. If this capacity is more than that of the outdoor unit, then select the connection according to the outdoor unit.
The selection of branch header depends on the quantity of branches it connects to.
Connection method

Table 4-5
Outdoor unit Indoor unit Branch pipe

Gas side Welding or Flaring

Liquid side Welding or Flaring

Flaring

Flaring

Welding or Flaring Welding or Flaring

Piping sizes at the branch pipe

Table 4-6

(A: the total capacity of indoor units)

Refrigerant

A (TYPE)

Air Side ()

Liquid Side ()

Wall mounted 22~45 12.7(Flaring nut)

Wall mounted 56 15.9(Flaring nut)

Four-sided air outlet 28~45 Four-sided air outlet 56~80
One-sided air outlet 18~45 One-sided air outlet 56
Low static pressure 18~45
Low static pressure 56

12.7(Flaring nut) 15.9(Flaring nut) 12.7(Flaring nut) 15.9(Flaring nut) 12.7(Flaring nut) 15.9(Flaring nut)

R410A

Thin duct type 71 A5 duct type 22~45

15.9(Flaring nut) 12.7(Flaring nut)

A5 duct type 56~140 15.9(Flaring nut)

Four-way Cassette Type 15~45

12.7(Flaring nut)

Console Type 22~45 12.7(Flaring nut)

Tow-way Cassette Type 22~45
Tow-way Cassette Type 56~71
Ceiling And Floor Type 36~45 Ceiling And Floor Type 56~160

12.7(Flaring nut) 15.9(Flaring nut) 12.7(Flaring nut) 15.9(Flaring nut)

Expose And Concealed

12.7(Flaring nut)

Floor-standing type 22~45

6.4(Flaring nut) 9.5(Flaring nut) 6.4(Flaring nut) 9.5(Flaring nut)
6.4(Flaring nut) 9.5(Flaring nut)
6.4(Flaring nut) 9.5(Flaring nut) 9.5(Flaring nut) 6.4(Flaring nut) 9.5(Flaring nut) 6.4(Flaring nut) 6.4(Flaring nut) 6.4(Flaring nut) 9.5(Flaring nut) 6.4(Flaring nut) 9.5(Flaring nut) 6.4(Flaring nut)

Expose And Concealed Floor-standing type 56~80

15.9(Flaring nut)

9.5(Flaring nut)

Pipe diameter of the connector in the outdoor unit’s body

Table 4-7

Piping connection Pipe diameter of outdoor unit’s connector(mm)

side

Model(kW)

Gas Side

Liquid Side

20-22.4 26-28 33.5
33.5

19.1 22.2 22.2

9.53 9.53 12.7
6

Table 4-8

Outdoor Unit (kW)

Capacity of Maximum Outdoor unit Quantity of (horsepower) Indoor unit

Sum Capacity of Indoor unit (horsepower)

20

7

11

22.4

8

13

26

9

15

50%~130%

28

10

16

33.5

12

20

When capacity of indoor unit greater than the sum of 100%, capacity

of indoor unit will be attenuated.

When capacity of indoor unit greater than or equal to the sum of

120%, in order to ensure the effectiveness of machine, and then try to

open the indoor units at different time.

NOTE

The indoor unit capacity total can not exceed 130% of the outdoor unit load. Overloading reduces the corresponding capacity.
Table 4-9

Capacity ranking

Capacity (horsepower)

Capacity ranking

Capacity (horsepower)

18

0.6

80

2.8

22

0.8

90

3.2

28

1

100

3.5

36

1.3

112

4

45

1.6

120

4.3

56

2

125

4.5

71

2.5

140

5

When the outdoor unit connects one indoor unit

Table 4-10

MODEL The max height drop(m) The length of

(kW)

When outdoor When outdoor unit is top unit is bottom

refrigerant pipe(m)

The number of bends

20-33.5

25

20

50

less than 10

4.6 Illustration
Outdoor Unit((Take Model 280 for example)

(280)

N1 (56)
a

L1 A

L2 B b

L3 The first line Branch Pipe

L4 C
L5

N2 (56)
c D
d
E

Indoor unit
N3 (45)
N4 (45)
e

f
N5 (45)

N6 (56)

Fig.4-6

Caution: Suppose in the displayed piping system, the total equivalent piping length of air side + liquid side is longer than 90m.

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Indoor unit branch pipe
Inner branch pipes are a~f, the size selection please refers to Table4-6. Note: The max. length of the branch pipe should not longer than 15m.
The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of the main pipe L2 are N1, N2, and its total capacity is 56×2=112, the size of pipe L2 is 15.9/9.5, and the branch pipe B should be FQZHN-01D. The downstream inner units of the main pipe L4 are N3, N4, and its total capacity is 45×2=90, the size of pipe L4 is15.9/9.5, and the branch pipe D should be FQZHN-01D.
The downstream inner units of the main pipe L5 are N5, N6, and its total capacity is 45+56=101, the size of pipe L5 is15.9/9.5, and the branch pipe E should be FQZHN-01D.

The indoor unit below to the main pipe L3 are N3N6, and its total capacity is 45×3+56=191, the size of pipe L3 is19.1/9.5, and the branch pipe C should be FQZHN-01D. The indoor unit below to the main pipe A are N1N6, and its total capacity is 45×5+56=281, and the branch pipe should be FQZHN-02D, and because the total piping length of liquid + air side is 90m, check Table.4-4, and the first branch pipe should apply FQZHN-02D, and according to the principle of maximum value, it should apply FQZHN-02D.
Main pipe (Please refer to Fig.4-6 and Table 4-4) In Fig.4-6, the main pipe L1, the outdoor unit capacity is
28kW, and check the Table 4-4 to get the size of gas pipe/liquid pipe is 22.2/9.5, and aslo the total equivalent length of liquid side and gas side pipes is >90m,then check the Table 4-4 to get the size of gas pipe/liquid pipe is 25.4/12.7, and according to the maximum value principle, it should apply the 25.4/12.7.

Allowable length and altitude difference of refrigerant pipe Pimitted value

Total Pipe Length(Actual)

150m

Pipe Length

Maximum Piping(L)

Actual Length Equivalent Length

Pipe Length(from the first line branch pipe to furhtest indoor unit)(m) Pipe Length(from the nearest branch pipe equivalent length(m)
Outdoor Unit up Indoor Unit-Outdoor Unit Drop Height(H) Outdoor Unit Down
Indoor Unit to Indoor Unit Drop Heihgt(H)

100m
110m 40m 15m 50m 40m 15m

Drop Height

Piping

table 4-11

L1+L2+L3+L4+L5+a+b+c+d+e+f

L1+L2+L3+L4+L5+f(The first connect methond) or L1+L3+L5+f(The second connect methond)
L2+L3+L4+L5+f(The first connect methond) or L3+L5+f(The second connect methond)
a,b,c,d,e,f

Note: When the total equivalent piping length of liquid + gas side is 90m, it must increase the size of air side main pipe. Besides, according to the distance of refrigerant pipe and the over matched state of inner unit, when the capacity is decreasing it still can increase the gas side main pipe size.

The first cennect methond

Outdoor unit

Drop HEIGHT between indoor unit and uutdoor unit

L1 A
The first line Branch Pipe
L2

Pipe Length(from the nearest branch pipe equivalent length
a

Maximum pipe equivalent length

(from the first line branch pipe) Maximum pipe equivalent length

L3
B

C L4 D L5 E

b

c

d

ef

Indoor Unit

Indoor Unit to Indoor Unit Drop Heihgt

Fig.4-7

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

7
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

The second cennect methond

Drop HEIGHT between indoor unit and uutdoor unit Indoor Unit to Indoor Unit Drop Height

Outdoor unit

Maximum pipe equivalent length

L1

L2

A

L3

The first line Branch Pipe

Pipe Length(from the nearest branch pipe equivalent length
a B
b

N1 N2

(from the first line branch pipe) Maximum pipe equivalent length

L4
C L5

c

N3

D

N4

d

E

f

e N5

N6

Indoor unit

Fig.4-8

4.7 Remove Dirt or Water in the Piping
Make sure there is no any dirt or water before connectiong the piping to the outdoor units. Wash the piping with high pressure nitrogen, never use refrigerant of outdoor unit.
4.8 Airtight Test
Charge pressured nitrogen after connecting indoor/outdoor unit piping to do airtight test.
CAUTION
1. Pressured nitrogen [ 4.3MPa (44kg/cm 2) for R410A] should be used in the airtight test. 2. Tighten high pressure/low pressure valves before
applying pressured nitrogen. 3. Apply pressure from air vent mouth on the hight pressure/
low pressure valves. 4. The high pressure/low pressure valves are closed when
applying pressured nitrogen. 5. The airtight test should never use any oxygen,
flammable gas or poisonous gas.
4.9 Air Purge with Vacuum Pump
Using vacuum pump to do the vacuum,never using refrigerant to expel the air.
Vacuuming should be done from both liquid side and gas side simultaneously.

4.10 Refrigerant Amount to be Added
Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit connection.
When the outdoor unit connects 1 indoor unit:

Table 4-12

Liquid Side Piping Diameter
6.4 9.5
12.7 15.9 19.1 22.2

Refrigerant to be Added Permeter Piping
0.022kg 0.057kg
0.110kg 0.170kg 0.260kg 0.360kg

NOTE
Additional refrigerant volume of divergent pipe is 0.1kg per item (Consider the liquid side of divergent pipe only)

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

8
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

5. ELECTRICAL WIRING

CAUTION

Design a dedicated power supply for the indoor unit and outdoor unit. If the power supply uses a branch loop, install an electricity leakage protector and a manual switch.
The power supply, electric leakage protectors, and manual switches of the indoor units that connect to the same outdoor unit must be universal. Use the same loop for the indoor unit power connect to the same outdoor unit must be universal. Use the same loop for the indoor unit power supplies in the same system. Power on/off at the same time.
Incorporate the outdoor unit and indoor unit connection wiring system and refrigerant pipe system for the same system.
To reduce interference, use a three-core shielded twisted pair as the outdoor unit signal cable. Do not use a multi-core cable.
Complete wiring according to national electrical standards. Employ an electrical engineer for wiring.

Outdoor power supply Switch

Fuse

Power supply for the outdoor unit monitor

L N

Reserved (Optional)
K1 K2 E

L1 L2 L3 N

Outdoor unit K1 K2 E O A E X Y E P Q E

Digital ammeter power supply

To kilowatt-hour meter(Optional)

L N

OA E

Power supply for the central indoor unit controller

To centralized controller(Optional)

L N

X Y E

Use a shielded cable and ground the shielding layer

Outdoor power supply

Switch

LN
Fuse

PQE
Indoor unit

LN
Fuse

PQE
Indoor unit

LN
Fuse

PQE
Indoor unit

LN
Fuse

PQE
Indoor unit

Distribution box

Distribution box

Distribution box

Distribution box

280 Three-phase electrical control system connection of the outdoor unit

Fig.5-1

CAUTION
An incorrect connection configuration may damage the compressor or other components. PQE is a signal cable, which must be connected to a weak current. Do not connect it to strong current. All wiring terminals must be securely fixed. The grounding wire must be grounded as required. After connecting to the connector base, the power cable must be securely fixed. After all wires are connected, check the correctness all components before powering on.

9

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Outdoor unit
PQE

Note: The parts in the dotted line box are optional.Contact the local distributor to purchase them if required.

Use a shield cable and ground the shielding layer.

Indoor unit PQE

Indoor unit PQE

Indoor unit PQE

Indoor unit PQE

Wired Remote controller control

Wiring the indoor unit and outdoor unit control

Add a build-out resistor at the P/Q end of the last indoor unit only. Build- out resistor
Fig. 5-2

CAUTION
When the power cable is parallel to the signal cable, insert electric wires in their respective electric wire pipes and reserve a proper inter-wire distance. (distance between power cables: lower than 10 A ­300 mm; lower than 50 A ­ 500 mm) Use a three-core shielded cable as the indoor/outdoor unit signal cable, and ground the shielding layer as required. The display box, remote control, and build-out resistor are accessories for the indoor unit. The wired controller is optional. To purchase a wired controller, contact your local distributor.

5.1 Outdoor Unit Wiring
Functions of Outdoor Unit Wiring Terminals
L1 L2 L3 N
XT1
Power Supply

Reserved

To kilowatt- To centralized To indoor units com-

hour meter controller

munication bus

20 – 28kW

K1 K2 E O A E X Y E P Q E

Note:Use a three-core shielded cable, and ground the shielding layer

The Specification of Power

Table 5-1

Power Source

380-415V 3N~ 50 Hz

Model

Capicity(kW)

20

22 26 28 33.5

Hz

50

Voltage

380-415

Power Supply

Min.(V) Max.(V) Min Circuit Amps.

342

456

19

19 20.5 21 26.4

Total Over-current Amps. 24.3 24.3 24.3 24.3 33.2

Max Fuse Amps.

25

25 25 25 32

Compressor

MSC RLA

/

/

/

/

/

12 12.4 15 18.4 19.6

kW OFM
FLA

2×0.17 2.1+2.1

CAUTION
Equipment complying with IEC 61000-3-12. A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation. The reserved function is indicated in broken line table,users can select it when necessary.

Outdoor unit monitor

Digital Central indoor ammeter unit controller
33.5kW

Indoor and outdoor unit communication
Fig. 5-3

Indoor/Outdoor Unit Signal Wire Connect the wire according to their numbers.

10

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Wrong connection may cause malfunction . Wiring Connection Seal the wiring connection with the insulation material , or the condensing dew will be caused.
NOTE
The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring correctly and set system address and network address of indoor units

5.2 Indoor Unit Wiring
Power Supply
Capicity(kW)

1.8~16

Table 5-2

Indoor Unit Power

Specifications

Power Wiring Size(mm²)

Circuit Breaker (A)
Indoor Unit /Outdoor Unit Signal Wire (mm2) (Weak electric signal)

220-240V~ 50Hz
3×2.5 16
Three-core shielded wire 3×0.75

Single phase indoor unit

WHITE BLUE BLACK YELLOW GRAY BLACK

LN

XYE P QE

Y/G

XT1

XT3

Display board
Wire controller

Power Supply

To Central Control To Outdoor Monitor (CCM) COMM.BUS COMM. BUS

To wire controller The reserved wire control function is indicated in broken

line table, users can purchase

Please use three-core shielded wire, and the wire controller when

connect the shielded layer to Grounding necessary.

Fig. 5-4

1. Signal wire is three-core, polarized wire. Use three-core shield wire to prevent interference. The grounding method now is grounding the closed end of the shield wire and opening (insulating) at the end. Shield is to be grounded.
2. The control between outdoor unit and indoor unit is BUS type. Addresses is set on field during the installation.

CAUTION
Indoor/Outdoor unit signal wire is low voltage circuit. Do not let it touch the high voltage power wire and put it to gather with power cord in the same wire distribution pipe.

NOTE
The wire diameter and continuous length is under the condition that the voltage vibration is within 2%. If the continuous length is exceed showing value, choose the wire diameter follow relevant regulation.

Indoor unit power supply wiring

Indoor Power Supply Circuit Breaker Manual swtich

Wire Distribution Box

Indoor Unit

Fig. 5-5
CAUTION
1. Refrigerant piping system, indoor unit-indoor unit connection signal wires and indoor unit-outdoor unit connection singal wire are in the same system.
2. When power cord is parallel with signal wire, please put them into separate wire distribution pipes, and leave a proper distance. (Reference distance: It is 300mm when current capacity of power cord is less than 10A, or 500mm when 50A).
Please use shield wire as indoor unit/outdoor unit signal wire. Indoor/Outdoor unit signal wire wiring
Outdoor Unit Close end of the connection shielded wire
Indoor/Outdoor Unit Signal Wire
(open)

in broken line table, users can purchase the wire controller when necessary.

Fig. 5-6

CAUTION
The length of signal wire must not exceed 1200m. A communication error may result when the signal wiring exceeds these limitations.

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

11
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

6. TEST RUNNING
Operate according to “gist for test running” on the electric control box cover.

CAUTION
Test running can not start until the outdoor unit has been connected to the power for 12hr. Test running can not start until all the valves are affirmed open. Never make the forced running. (Or the protector sits back, danger will occur.)

7. CONFIGURATION
7.1 Overview
This chapter describes how the system configuration can be implemented once the installation is complete, and other relevant information. It contains the following information: Implement field settings Energy-saving and optimized operation

i Information
The installation personnel should read this chapter.

7.2 Dial Switch Settings Dial code definitions:
means 0

means 1

Table 7-1 For 200 to 280 unit only
Table 7-1

ENC1 &
S9-3
ENC3 S1-1 S1-2 S1-3
S2
S9-1 S9-2

0-F The number of indoor units is in the range 0-15 0-9 on ENC1 indicate 0-9 indoor units;
0 A-F on ENC1 indicate 10-15 indoor units
1 2 3

0-F The number of indoor units is in the range 16-31 0-9 on ENC1 indicate 16-25 indoor units;
1 A-F on ENC1 indicate 26-31 indoor units
1 2 3

0-7

Outdoor unit network address setting, Only 0 to 7 should be selected (default is 0).

0 When connected to 2nd generation DC indoor unit(default)

1 2 3 1 When connected to AC or 1st generation DC indoor unit 0 Auto addressing (default)

1 2 3 1 Clear indoor unit addresses

0 Reserved 1 2 3 1 Factory test only
000 Auto priority (default) 100 Cooling priority

010 First ON priority 1 2 3 110 Heating only

001 Cooling only

Other combinations,Heating priority

00 Outdoor unit capacity,280

01 1 2 3 10
11

Outdoor unit capacity,260 Reserved Outdoor unit capacity,224/200(customer)

Table 7-2 For 335 unit only,335 unit adopt different PCB

Table 7-2

0-F The number of indoor units is in the range 0-15

0-9 on ENC1 indicate 0-9 indoor units;

ENC1 1 2 3 0 A-F on ENC1 indicate 10-15 indoor units &

S9-3

0-F The number of indoor units is in the range 16-31

0-9 on ENC1 indicate 16-25 indoor units;

1 A-F on ENC1 indicate 26-31 indoor units
1 2 3

ENC3

0-7

Outdoor unit network address setting, Only 0 to 7 should be selected (default is 0).

0 When connected to 2nd generation DC indoor unit(default)

S1-1 1 2 3

1

When connected to AC or 1st generation DC indoor unit

0 Auto addressing (default) S1-2
1 2 3 1 Clear indoor unit addresses
0 Reserved S1-3
1 2 3 1 Reserved
000 Auto priority (default)

100 Cooling priority

010 First ON priority S2 1 2 3 110 Heating only
001 Cooling only

Other combinations,Heating priority

0 Reserved S9-1
1 2 3 1 Outdoor unit capacity,12HP

0 Reserved S9-2
1 2 3 1 Factory test only

NOTE
Please cut off the power supply when changing the dial switch

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

12
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

8. PRECAUTIONS ON REFRIGERANT LEAKAGE

This air conditioner(A/C) adopts inncouous and nonflammable refrigerant. The locating room of the A/C should big engough that any refrigerant leakage is unable to reach critical thickness. So certain esssential action can be taken on time.
Critical thickness——the Max. thickness of Freon without any harm to person. Refrigerant critical thickness: 0.44[kg/m3] for R410A.

Confirm the critical thickness through follow steps, and take necessary actions.
1. Calculate the sum of the charge volume (A[kg]) Total Refrigerant volume of 10HP=factory refrigerant volume + superaddition
2. Calculate the indoor cubage (B[m3]) (as the minimum cubage.

3. Calculate the refrigerant thickness

A[kg]

ImplemBe[mnt3]field

critical thickness settings

Coun tEenr emrgeya-ssuarveinaggaainndstoopvtiemrihzeigdhothpiecrkantieosns

1. Installmechanicalventilator to reduce the refrigerant thickness under critical level. (ventilate regularly)

2. Install leak alarm facility related to mechanical ventilator if you can not regularly ventilate.

Outdoor unit
Indoor unit Room full of leak refrigerant
(All refrigerant has run up) b. Leak alarm related to mechanical ventilator
Indoor unit

A. Ventilation

(Leak hunting siren should be installed in peristome

places easily keep refrigerant)

Fig. 8-1

8.1 Important information for the used refrigerant

This product has the fluorinated gas, it is forbidden to release to air. Refrigerant type: R410A; Volume of GWP: 2088; GWP=Global Warming Potential

Model

Factory charge

Refrigerant/kg

tonnes CO2 equivalent

20-28kW

6.5

13.57

33.5kW

8

16.71

Attention: Frequency of Refrigerant Leak Checks

  1. For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more,but of less than 50 tonnes of CO2 equipment,at least every 12 months, or where a leakage detection system is installed, at least every 24 months
  2. For equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more,but of less than 500 tonnes of CO2 equipment,at least every six months, or where a leakage detection system is installed, at least every 12 months.
  3. For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more,at least every three months, or where a leakage detection system is installed, at least every six months.
  4. Non-hermetically sealed equipment charged with fluorinated greenhouse gases shall only be sold to the end user where evidence is provide that the installation is to be carried out by an undertaking certified person.
  5. Only certificated person is allowed to do installation, operation and maintenance.

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

13
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

9 ERRPOR CODES

Error code

Error description

Remarks

Communication error between main board and H0 compressor drive board

H4 Inverter-module protection

H5 3 times of P2 protection in 30 minutes

Irrecoverable

H7 Qty. of indoor units mismatching

Irrecoverable

H8 High pressure sensor error

HF M-HOME for the indoor and outdoor units does not match Irrecoverable

E1 Phase sequence error

E2 Communication error between indoor and master unit

E4 T3 or T4 temperature sensor error

E5 Abnormal power supply voltage

E6 DC fan motor error

Eb E6 protection appears 6 times in 1 hour

Irrecoverable

E7 Discharge temperature sensor error

EH TL sensor fault

P1 High pressure protection

P2 Low pressure protection

P3 Compressor current protection

P4 Discharge Temp. protection

P5 High Temp. protection of condenser

P8 Typhoon protection

PL Inverter module Temp. protection

L0 Inverter compressor module error

L1 DC bus low voltage protection

L2 DC bus high voltage protection

L4 MCE error

L5 Zero speed protection

L7 Phase sequence protection

Compressor frequency variation greater than 15Hz L8 within one second protection

L9

Actual compressor frequency differs from target frequency by more than 15Hz protection

F1 DC bus voltage error

DC bus voltage error

bH PED protection board error bL High pressure switch protection on driver board

The troubleshooting for each error code, please refer to the service manual.

10. TURN OVER TO CUSTOMER

The owner’s manual of indoor unit and owner’s manual of outdoor or unit must be turned over to the customer. Explain the contents in the owner’s manual to the customers in details.

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

14
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Cooling mode:

Table.3

Information requirements for air-to-air conditioners

Model(s): SYSVRF2 224 AIR EVO A HP R; Test matching indoor units form, non- duct : 4× SYSVRF CASSETTE 56 Q;
Outdoor side heat exchanger of air conditioner:air

Indoor side heat exchanger of air conditioner:air

Type:compressor driven

If applicable:driver of compressor:electric motor

Item

Symbol Value

Unit

Rated cooling capacity Prated,c

22.4

kW

Item
Seasonal space cooling energy efficiency

Symbol s,c

Value Unit

270.2

%

Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27/19dry/wet bulb

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj

Tj=+35

Pdc

22.4

kW

Tj=+35

EERd

3.31

Tj=+30

Pdc

16.645

kW

Tj=+30

EERd

4.57

Tj=+25 Tj=+20

Pdc

10.990

kW

Pdc

6.399

kW

Tj=+25 Tj=+20

EERd EERd

8.61

12.8

Degradation co-efficient for air conditioners(*)

Cdc

0.25

Power consumption in modes other than “active mode”

Off mode Thermosat-off mode

POFF PTO

0.04 0

kW

Crankcase heater mode

PCK

kW

Standby mode

PSB

Other items

Capacity control
Sound power level,outdoor

variable

LWA

78

dB

For air-to-air air conditioner:air flow rate,outdoor measured

GWP of the refrigerant

2088 kg CO2 eq(100years)

Contact details (*)If Cdc is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25

0

kW

0.04

kW

9000

m3/h

Where information relates to multi-split air conditioners,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

17
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Heating mode:

Table.4

Information requirements for heat pumps

Model(s): SYSVRF2 224 AIR EVO A HP R; Test matching indoor units form, non- duct : 4×SYSVRF CASSETTE 56 Q; Outdoor side heat exchanger of air conditioner:air Indoor side heat exchanger of air conditioner:air
Idication if the heater is equipped with a supplementary heater:no
If applicable:driver of compressor:electric motor Parameters shall be declared for the average heating season,parameters for the warmer and colder heating seasoms are optional

Item

Symbol Value

Unit

Item

Symbol

Value Unit

Rated heating capacity Prated,h

22.4

kW

Declared heating capacity for part load at indoor teperature 20¥ and outdoor temperatures Tj

Seasonal space heating energy efficiency

s,h

167.4 %

Declared coefficient of performance or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor
temperatures Tj

Tj=-7¥

Pdh

12.113

kW

Tj=-7¥

COPd

3.22

Tj=+2¥

Pdh

7.272

kW

Tj=+2¥

COPd

3.56

Tj=+7¥

Pdh

5.825

kW

Tj=+7¥

COPd

6.76

Tj=+12¥

Pdh

3.703

kW

Tbiv=bivalent temperature

Pdh

12.113

kW

TOL=operation temperature

Pdh

13.74

kW

Bivalent temperature

Tbiv

-7

¥

Tj=+12¥ Tbiv =bivalent temperature TOL =operation temperature

COPd COPd COPd

7.76

3.22

2.35

Degradation co-efficient for heat pumps(**)

Cdh

0.25

Power consumption in modes other than “active mode”

Supplementary heater

Off mode

POFF

0.04

kW

Back-up heating capacity(*)

elbu

Thermosat-off mode

PTO

0.04

kW

Type of energy input

Crankcase heater mode PCK

0

kW

Standby mode

PSB

Other items

Capacity control
Sound power level,outdoor

variable

LWA

78

dB

For air-to-air heat pump:air flow rate,outdoor measured

GWP of the refrigerant

2088

kg CO2 eq(100years)

Contact details

(*)

0

kW

0.04

kW

9000

m3/h

(**)If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
Where information relates to multi-split heat pumps,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

18
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Cooling mode:

Table.5

Information requirements for air-to-air conditioners

Model(s): SYSVRF2 260 AIR EVO A HP R; Test matching indoor units form, non- duct : 2×SYSVRF CASSETTE 45 Q + 2×SYSVRF CASSETTE 90 Q;
Outdoor side heat exchanger of air conditioner:air

Indoor side heat exchanger of air conditioner:air

Type:compressor driven

If applicable:driver of compressor:electric motor

Item

Symbol Value

Unit

Rated cooling capacity Prated,c

26

kW

Item
Seasonal space cooling energy efficiency

Symbol s,c

Value Unit

259

%

Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27/19dry/wet bulb

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj

Tj=+35

Pdc

26

kW

Tj=+35

EERd

2.59

Tj=+30

Pdc

18.843

kW

Tj=+30

EERd

4.53

Tj=+25

Pdc

12.745

kW

Tj=+25

EERd

8.35

Tj=+20

Pdc

6.330

kW

Tj=+20

EERd

12.66

Degradation co-efficient for air conditioners(*)

Cdc

0.25

Power consumption in modes other than “active mode”

Off mode Thermosat-off mode

POFF PTO

0.04 0

kW

Crankcase heater mode

kW

Standby mode

Other items

PCK

0

kW

PSB

0.04

kW

Capacity control
Sound power level,outdoor

variable

LWA

78

dB

For air-to-air air conditioner:air flow rate,outdoor measured

10000 m3/h

GWP of the refrigerant

2088 kg CO2 eq(100years)

Contact details (*)If Cdc is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25

Where information relates to multi-split air conditioners,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

19
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Heating mode:

Table.6

Information requirements for heat pumps
Model(s): SYSVRF2 260 AIR EVO A HP R; Test matching indoor units form, non- duct : 2×SYSVRF CASSETTE 45 Q + 2×SYSVRF CASSETTE 90 Q; Outdoor side heat exchanger of air conditioner:air Indoor side heat exchanger of air conditioner:air Idication if the heater is equipped with a supplementary heater:no If applicable:driver of compressor:electric motor Parameters shall be declared for the average heating season,parameters for the warmer and colder heating seasoms are optional

Item

Symbol Value

Unit

Item

Symbol

Value Unit

Rated heating capacity Prated,h

26

kW

Declared heating capacity for part load at indoor teperature 20¥ and outdoor temperatures Tj

Seasonal space heating energy efficiency

s,h

178.2 %

Declared coefficient of performance or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor
temperatures Tj

Tj=-7¥

Pdh

13.663

kW

Tj=-7¥

COPd

3.17

Tj=+2¥

Pdh

8.703

kW

Tj=+2¥

COPd

3.90

Tj=+7¥

Pdh

6.027

kW

Tj=+7¥

COPd

7.17

Tj=+12¥

Pdh

3.881

kW

Tbiv=bivalent temperature

Pdh

13.633

kW

TOL=operation temperature

Pdh

15.861

kW

Bivalent temperature

Tbiv

-7

¥

Tj=+12¥ Tbiv =bivalent temperature TOL =operation temperature

COPd COPd COPd

8.36

3.17

2.32

Degradation co-efficient for heat pumps(**)

Cdh

0.25

Power consumption in modes other than “active mode”

Supplementary heater

Off mode

POFF

0.04

kW

Back-up heating capacity(*)

elbu

Thermosat-off mode

PTO

0.04

kW

Type of energy input

Crankcase heater mode PCK

0

kW

Standby mode

PSB

Other items

Capacity control
Sound power level,outdoor

variable

LWA

78

dB

For air-to-air heat pump:air flow rate,outdoor measured

GWP of the refrigerant Contact details

2088

kg CO2 eq(100years)

(*)

0

kW

0.04

kW

10000 m3/h

(**)If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
Where information relates to multi-split heat pumps,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

20
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Cooling mode:

Table.7

Information requirements for air-to-air conditioners

Model(s): SYSVRF2 280 AIR EVO A HP R; Test matching indoor units form, non- duct : 2×SYSVRF CASSETTE 56 Q + 2×SYSVRF CASSETTE 90 Q;
Outdoor side heat exchanger of air conditioner:air

Indoor side heat exchanger of air conditioner:air

Type:compressor driven

If applicable:driver of compressor:electric motor

Item

Symbol Value

Unit

Rated cooling capacity Prated,c 28

kW

Item
Seasonal space cooling energy efficiency

Symbol s,c

Value Unit

251

%

Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27/19dry/wet bulb

Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj

Tj=+35

Pdc

28

kW

Tj=+35

EERd

2.33

Tj=+30

Pdc

20.662

kW

Tj=+30

EERd

4.31

Tj=+25 Tj=+20

Pdc

13.537

kW

Pdc

6.328

kW

Tj=+25 Tj=+20

EERd EERd

8.16

12.66

Degradation co-efficient for air conditioners(*)

Cdc

0.25

Power consumption in modes other than “active mode”

Off mode

POFF

0.04

kW

Thermosat-off mode

PTO

0

kW

Crankcase heater mode Standby mode

PCK

0.04

kW

PSB

0.04

kW

Other items

Capacity control
Sound power level,outdoor

variable

LWA

78

dB

For air-to-air air conditioner:air flow rate,outdoor measured

11000 m3/h

GWP of the refrigerant

2088

kg CO2 eq(100years)

Contact details (*)If Cdc is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25

Where information relates to multi-split air conditioners,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

21
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Heating mode:

Table.8

Information requirements for heat pumps
Model(s): SYSVRF2 280 AIR EVO A HP R; Test matching indoor units form, non- duct : 2×SYSVRF CASSETTE 56 Q + 2×SYSVRF CASSETTE 90 Q; Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Idication if the heater is equipped with a supplementary heater:no
If applicable:driver of compressor:electric motor
Parameters shall be declared for the average heating season,parameters for the warmer and colder heating seasoms are optional

Item

Symbol Value

Unit

Item

Symbol

Value Unit

Rated heating capacity Prated,h

28

kW

Seasonal space heating energy efficiency

s,h

179.4

%

Declared heating capacity for part load at indoor teperature 20¥ and outdoor temperatures Tj

Declared coefficient of performance or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor
temperatures Tj

Tj=-7¥

Pdh

15.715

kW

Tj=-7¥

COPd

2.93

Tj=+2¥

Pdh

9.445

kW

Tj=+2¥

COPd

3.99

Tj=+7¥

Pdh

6.060

kW

Tj=+7¥

COPd

7.26

Tj=+12¥

Pdh

3.906

kW

Tbiv=bivalent temperature

Pdh

15.715

kW

TOL=operation temperature

Pdh

17.534

kW

Bivalent temperature

Tbiv

-7

¥

Tj=+12¥ Tbiv =bivalent temperature TOL =operation temperature

COPd COPd COPd

8.48

2.93

2.21

Degradation co-efficient for heat pumps(**)

Cdh

0.25

Power consumption in modes other than “active mode”

Supplementary heater

Off mode

POFF

0.04

kW

Back-up heating capacity(*)

elbu

Thermosat-off mode

PTO

0.04

kW

Type of energy input

Crankcase heater mode PCK

0

kW

Standby mode

PSB

Other items

Capacity control
Sound power level,outdoor

variable

LWA

78

dB

For air-to-air heat pump:air flow rate,outdoor measured

GWP of the refrigerant

2088

kg CO2 eq(100years)

Contact details

(*)

0 0.04 11000

kW kW m3/h

(**)If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
Where information relates to multi-split heat pumps,the test result and performance data may be obtained on the basis of performance of the outdoor unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

22
Our Address Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

Certified: www.systemair.com

16100101A05013 V.F

Get In Touch
Call: 0845 6880112 Email: info@adremit.co.uk

Our Address
Puravent, Adremit Limited, Unit 5a, Commercial Yard, Settle, North Yorkshire, BD24 9RH

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals