EMERSON Enardo Rim Vent Pressure Relief Valve Instruction Manual
- June 4, 2024
- Emerson
Table of Contents
Enardo Rim Vent Pressure Relief Valve
**Instruction Manual
**
Instruction Manual D103826X012
December 2021
Enardo Rim Vent
Enardo Rim Vent Pressure Relief Valve
Outside North America Only
WARNING
Failure to follow these instructions or to properly install and maintain this
equipment could result in an explosion, fire, and/or chemical contamination
causing property damage and personal injury or death.
FisherTM rim vents must be installed, operated, and maintained in accordance
with federal, state, and local codes, rules, and regulations, and Emerson
Process Management Regulator Technologies Tulsa, LLC instructions.
Failure to correct trouble could result in a hazardous condition. Call a
qualified service person to service the unit. Installation, operation, and
maintenance procedures performed by an unqualified person may result in
improper adjustment and unsafe operation. Either condition may result in
equipment damage or personal injury. Only a qualified person must install or
service the pressure relief valve.
Introduction
Scope of the Manual
This Instruction Manual provides instructions for the installation and
maintenance of the Leonardo rim vent pressure relief valve.
Figure 1. Enardo Rim Vent Pressure Relief Valve
Product Description
Rim vents (top mount) prevent the loss of vapors in a closed storage system
and relieve pressure in atmospheric and low-pressure storage tanks and
floating roof tanks such as those defined in API 12F, API 12B, API 650, and EN
14015. Rim vents can also be used for emergency venting on small atmospheric
and low-pressure tanks.
The Leonardo rim vent is a pressure-only relief vent that can be installed on
a mating CL150 flat-faced flange. A 6 in. CL150 flange has a bolting circle
with 8 – 0.88 in. bolt holes on a 9 – 1/2 in. bolt hole diameter.
Principle of Operation
Rim vents are installed on floating roofs or cone roofs of storage tanks with
direct communication to the vapor space. In floating roof tanks, rim vents
provide pressure relief to the roof and seal when the tank is empty, the roof
is landed and the tank is being filled.
Pressure relief to the seals can be achieved when the roof is floating and if
product evaporation occurs. As the pressure in the vapor space increases above
the set point, the weight-loaded pallet lifts vertically to relieve pressure.
As the pressure in the vapor space drops back below the rim vent set point,
the pallet lowers and closes. The rim vent set point is adjustable by adding
to or removing weights from the pallet.
Specifications
The Specifications section lists the specifications for the Leonardo rim vent pressure relief valve. The following information is stamped on the nameplate attached to the base of the Leonardo rim vent: pressure setting and the flow rate at 100% overpressure in SCFH.
Available Constructions
See Figure 2
Connection Size
6 in. / 150 mm
Pressure setting(1)
See Table 1
Materials of Construction
See Table 2
Flow Rate
See Table 3
Assembly Weights
See Table 1
Certifications
EN IEC 60079-0:2018
EN IEC 60079-11:2012
EN ISO 80079-36:2016
EN ISO 80079-37:2016
The pressure limits in this Instruction Manual and any applicable standard or
code limitation should not be exceeded.
Figure 2. Enardo Rim Vent Available Constructions and Model Numbering System
Table 1. Enardo Rim Vent Pressure Relief Valve Pressure Settings and Assembly
Weights
PRESSURE SETTING | ASSEMBLY WEIGHT |
---|---|
oz./sq. in. | In. w.c. |
0.5 | 0.9 |
1 | 1.7 |
2 | 3.5 |
4 | 6.9 |
8 | 13.8 |
12 | 20.8 |
Table 2. Materials of Construction
BODY| HOOD| SCREEN| PALLET| WEIGHTS| GASKET|
RODS
---|---|---|---|---|---|---
Cast Aluminum (Alloy 319-F)| Aluminum (Alloy 3003-H14)| Aluminum (Alloy
3003-H14)| Polyphenylene Sulfide (PPS)| Zinc Plated
Carbon Steel
| Teflon®| Aluminum (Alloy 6061-T6)
Table 3. Flow Rate in SCFH at 100% Overpressur e
PRESSURE SETTING | FLOW RATE AT 100% OVERPRESSURE (SCFH) |
---|---|
oz./sq. in. | In. w.c. |
0.5 | 0.9 |
1 | 1.7 |
2 | 3.5 |
4 | 6.9 |
8 | 13.8 |
12 | 20.8 |
Product Identification and Marking
Hazardous Locations
Rim Vents are available in aluminum as indicated in Figure 3.
Nameplate
A nameplate is attached to the vent and contains the following information:
- Model Number Ex. RIM VENT-6-111
- Connection Flange Size 6″
- Serial Number
- Tag Number(Optional)
- Notified Body Number Ex 2460
- Cat. No. (Category Number) Category 2 uncoated aluminum vents
- Date date of manufacture
- Certificate Ex. PRESAFE 17 ATEX 10273X
- Pressure Setting and Flow Rate
– Setting Ex. Z4.0 – Flow Rate SCFH (Air) Ex. 46,463
WARNING
Make sure the line is free of hazardous vapors before installing or servicing
the valve.
Installation
CAUTION
Ensure the rim space or tank is at atmospheric pressure before opening. A
pressure build-up inside the rim space or tank can cause a spray to be emitted
from the rim vent if opened under pressure.
PPE Warning
WARNING
Wear protective gloves and clothing to prevent skin contact when handling lead
weights. Wear eye protection. Avoid breathing dust/fumes/mist/vapors/spray. Do
not eat, dring or smoke while using the product. Avoid release to the
environment. Wash hands with soap and water after handling. Keep away from
excessive heat and open flames.
Installation to a Flanged Pipe with a 6 in. CL150 Flat-Faced Flange
-
Place the base gasket on the flanged pipe.
II 2 G Ex h IIC T6 Gb
OUTER HOUSING OF UNCOATED ALUMINUM
Figure 3. Product Identification and Marking -
Line up bolt holes, and place the rim vent on top of the base gasket.
-
Install nuts and bolts and tighten them in a star pattern. Ensure the rim vent is fastened securely.
Note For proper bolt torquing of the vent connecting the flange to the piping, please refer to Tables 4 and 5.
Installation Directly to a Tank Roof
- The tank requires a 6 in. ANSI bolt pattern on the roof.
- Place the base gasket on the bottom of the rim vent flange and place the assembly on the tank roof with holes lined up.
- Insert eight bolts from the bottom up by reaching inside the tank, through the hatch, and opening the tank roof.
- Attach each nut to the bolt from the outside. Tighten all nuts in a star pattern and ensure the rim vent is fastened securely.
Note For proper bolt torquing of the vent connecting the flange to the piping, please refer to Tables 4 and 5.
Removal of Packing Materials
Prior to operation, remove packing material inside the rim vent.
- Remove the four wing nuts on the hood and remove the hood. Lift the upper guide off of the two vent rods that support it.
- Pull the pallet assembly out of the rim vent and remove the cardboard gasket protector and the roll of packaging from the upper stem.
- Inspect the sealing surface of the rim vent and the gasket on the pallet assembly for any signs of wear or damage.
- Place pallet assembly back in the rim vent. Ensure that the bottom stem is retained by the lower guide hole on the rim vent base.
- Place the upper guide back on the two vent rods, and place the hood back on the four vent rods. Install the four wing nuts and tighten snugly.
Table 4. Torque Specifications – Flat Face Flange, Steel or Aluminum
NOMINAL PIPE DIAMETER | # BOLTS | BOLT DIAMETER | TORQUE |
---|---|---|---|
6 | 8 | 0.75 in. | 49 ft·lbs |
Assumptions:
Use of SAE grade 5 bolts or studs or stronger No lubricant
Elastomer <70 Durometer Shore A
Notes
Flat-faced flanges should never be mated to a raised face flange for
installation.
If lubricant is used on bolts, apply the torque reduction factor listed in
Lubricant Table.
For best results, hardened steel washers should be used on all cast flange
bolted connections.
Table 5. Torque Reduction Factor per Lubricant
DESCRIPTION| COEFFICIENT OF FRICTION| MULTIPLY TORQUE
VALUE IN TABLE BY
---|---|---
Machine Oil| f = 0.15| 0.75
API SA2 Grease| f = 0.12| 0.60
Nickel-based Lubricant| f = 0.11| 0.55
Copper-based Lubricant| f = 0.10| 0.50
Heavy-duty Lubricating Paste| f = 0.06| 0.30
Maintenance
- Perform scheduled maintenance at least once a year or more frequently in corrosive or dusty atmospheres or if conditions warrant.
- During normal maintenance, inspect the pressure gasket and sealing surfaces for signs of wear or corrosion that could cause increased leakage.
- To ensure efficient operation of the rim vent, carefully wipe the pressure seat and gasket with a clean, nonabrasive, and lint-free cloth or paper towel every time the rim vent is opened and during scheduled maintenance. This prevents the accumulation of residue that can deteriorate the performance of the rim vent.
Outside North America Only
Webadmin.Regulators@emerson.com
Facebook.com/EmersonAutomationSolutions
Enardo.com
IN
LinkedIn.com/company/emerson-automation-
solutions
Twitter.com/emr_automation
Emerson Automation Solutions
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574
Tulsa, OK 74146
USA T +1 918 662 6161
Europe
Bologna 40013, Italy
T +39 051 419 0611
Asia Pacific
Singapore 128461, Singapore
T +65 6777 8211
The Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100
D103826X012 © 2015, 2021 Emerson Process Management Regulator Technologies,
Inc. All rights reserved. 12/21.
The Emerson logo is a trademark and service mark of Emerson Electric Co. All
other marks are the property of their prospective owners.
FisherTM is a mark owned by Fisher Controls International LLC, a business of
Emerson Automation Solutions.
The contents of this publication are presented for informational purposes
only, and while every effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied, regarding
the products or services described herein or their use or applicability. All
sales are governed by our terms and conditions, which are available upon
request. We reserve the right to modify or improve the designs or
specifications of such products at any time without notice.
Emerson Process Management Regulator Technologies Tulsa, LLC does not assume
responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use and maintenance of any Emerson
Process Management Regulator Technologies Tulsa, LLC product remains solely
with the purchaser.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>