EMERSON DVC6200 HW2 Digital Valve Controller Instruction Manual
- June 4, 2024
- Emerson
Table of Contents
DVC6200 HW2 Digital Valve Controller
Instruction Manual
**DVC6200 HW2 Digital Valve Controller
**
Alert Record Setup for a Fisher™ FIELDVUE™
Alert Record in the DVC6200 HW2 is accessible using ValveLink™ software or DD-
based communications such as a Trex Device Communicator or AMS Device Manager
and can be configured to record and time stamp alert conditions. Twenty (20)
alert records may be stored in the instrument. The alert record is a great
troubleshooting tool when used properly.
Note
The alert record does not use a first in first out (FIFO) operation. Once the
alert record is full, the instrument will not record additional events until
the alert record is cleared. Alerts will continue to be reported to the
control or asset management system.
Enable the Alert Record
-
The alert record in the DVC6200 is disabled by default. It is good practice to enable the alert record and clear it after startup procedures are complete; when the alert record is enabled during start-up it can be filled with irrelevant alerts.
-
To enable the alert record, open the Detailed Setup menu using the Block icon.
-
Click on Alert Record ( ) at the top of the Detailed Setup window.
-
Verify that Alert Record Enable is set to yes.
a. Use the drop-down menu on the right to change values as needed.
b. Use the left arrow next to the parameter to download the value to the instrument.
Set Alert Record Not Empty and Alert Record Full Alerts
Enabling both of these alerts will generate an alert in Status Monitor when
alert values are recorded and available to view in the Alert Record.
Set Instrument Clock
The initial clock value shown in the right column is the computer time when
the Alert Record page is opened.
- Adjust the time value as needed.
- Use the left arrow to download the time and date to the instrument.
Note
The instrument time will reset to the default value any time power is cycled
to the instrument; set the instrument clock as the last step when
commissioning the instrument in a control loop.
If the instrument clock resets unexpectedly, it may indicate intermittent
power cycle issues are occurring, such as I/O channel cycling on/off or a bad
wire connection.
Configure Key Alerts:
- Enable the alerts you want to monitor using the Detailed Setup menu.
- Key alerts to enable include:
a. Travel Deviation – Travel Alerts Tab
Adjust the Alert Point and Time for the actuator size. b. Supply Pressure Low – Pressure Alerts Tab
Set Alert Point to just below the upper bench set pressure or the minimal pressure required to move a piston. c. Drive Signal – Electronic Alerts tab
The Drive signal is typically between 60 and 80% when the valve is not on a stop. It is used to determine how hard the digital valve controller is working to maintain the position of the valve.
d. Diagnostic Data Available – Informational Status Tab
This alert indicates that PD trigger information is stored in the instrument buffer. e. Pressure Fallback Active – Sensor Alerts Tab
This alert is active if the device goes into pressure fallback.
– Pressure Fallback must be enabled
View and Clear Stored Alert Records
-
Connect to the DVC6200 with ValveLink software.
-
Select Instrument Alert Record from the Diagnostics drop-down menu. A dialog box like the one shown below will appear if there are any stored records.
-
Use the next and previous arrows to scroll through the records. Each record may contain multiple alerts depending on what was active at the time the record was captured.
Note:
The alert record list cannot be downloaded.
Note:
Instrument time is shown as Approximate in the image above because the instrument clock was not reset following a power cycle. -
When finished viewing records click on Clear Instrument Alert Record to erase all current records and allow for 20 new records to be recorded.
Note
The best practice is to set the instrument clock and clear the alert record after the DVC6200 is connected to the control system and final commissioning steps have been performed.
**View Active Alerts
**
Active alerts may be reported via HART protocol to a control or asset management system. They are also viewable using ValveLink Status Monitor. The image below shows active alerts in ValveLink software reported while the Status Monitor is running; this alert information is also recorded in the instrument.
Note
The alert monitor can run in a live process and passively monitor instrument
parameters.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated
entities assume responsibility for the selection, use, or maintenance of any
product. Responsibility for proper selection, use, and maintenance of any
product remains solely with the purchaser and end user.
Fisher, FIELDVUE, and ValveLink are marks owned by one of the companies in the
Emerson Automation Solutions business unit of Emerson Electric Co. Emerson
Automation Solutions, Emerson, and the Emerson logo are trademarks and service
marks of Emerson Electric Co. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes
only, and while every effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied, regarding
the products or services described herein or their use or applicability. All
sales are governed by our terms and conditions, which are available upon
request. We reserve the right to modify or improve the designs or
specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
©2022 Fisher Controls International LLC. All rights reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>