novus TxIsoRail-HRT Temperature Transmitter User Manual

June 4, 2024
Novus

TxIsoRail-HRT Temperature Transmitter
User Manual

INTRODUCTION

The TxIsoRail-HRT is a configurable DIN rail mount temperature transmitter widely required in various industrial processes. Its universal input can be configured to read RTDs, thermocouples, and mV signals.
It converts the input signal into a 4-20 mA linear output proportional to the configured range. The TxIsoRail-HRT uses the HART® communication protocol over the 4-20 mA output current loop.
The input and output are electrically isolated, enhancing their performance and user and system safety.

SPECIFICATIONS

Sensor input: User defined. The supported sensors are listed in Table 1, along with their maximum measurement and minimum retransmission ranges.
Thermocouples: Types J, K, R, S, T, N, E, and B according to IEC 60584 (ITS-90).
Impedance >> 1 MΩ
Pt100: Excitation 0.15 mA, α= 0.00385, according IEC 60751 (ITS-90).
Pt1000: Excitation 0.20 mA, α= 0.00385, according IEC 60751 (ITS-90).
NTC R25: 10 kΩ ±1 %, β25/85 = 3435
Voltage: 0 to 50 mVdc. Impedance >> 1 MΩ

Sensor Type| Maximum Measurement Range| Minimum Retransmission Range
---|---|---
Thermocouple K| -150 to 1370 °C (-238 to 2498 °F)| 50 °C (90 °F)
Thermocouple J| -100 to 760 °C (-148 to 1400 °F)| 50 °C (90 °F)
Thermocouple R| -50 to 1760 °C (-58 to 3200 °F)| 200 °C (360 °F)
Thermocouple S| -50 to 1760 °C (-58 to 3200 °F)| 200 °C (360 °F)
Thermocouple T| -160 to 400 °C (-256 to 752 °F)| 50 °C (90 °F)
Thermocouple N| -270 to 1300 °C (-454 to 2372 °F)| 50 °C (90 °F)
Thermocouple E| -90 to 720 °C (-130 to 1328 °F)| 50 °C (90 °F)
Thermocouple B| 500 to 1820 °C (932 to 3308 °F)| 200 °C (360 °F)
Pt100| -200 to 650 °C (-328 to 1202 °F)| 30 °C (54 °F)
Pt1000| -200 to 650 °C (-328 to 1202 °F)| 30 °C (54 °F)
NTC| -30 to 120 °C (-22 to 248 °F)| 10 °C (18 °F)
Voltage| 0 to 50 mV| 3 mV

Table 1 – Sensors accepted by the transmitter

Switch-on delay: < 10 s with factory damping filter configured. The accuracy is only guaranteed after 15 min.
Terms of reference: Ambient: 25 ° C (77 °F); voltage: 24 Vdc, load:
250 Ω. 15 minutes required for stabilization time after configuration.
Temperature Effect:
NTC: < 0.11 % FS / 25 °C (77 °F)
Other sensors: < 0.05 % FS / 25 °C (77 °F) (FS = Full Scale)
Response time: Typical 6 s using factory damping filter. This is the maximum time between a temperature step being applied in the input and the output reaching 90 % of the corresponding value.
HART Protocol Version: 7
RTD cable resistance effect: 0.005 °C / Ω
Maximum allowable cable resistance for RTD: 25 Ω
Accuracy: Calibration error in relation to sensor measuring range.

Sensor Type CURRENT LOOP HART
Typical Error Maximum Error Typical Error

Maximum Error
Pt100 (-200 to 650 °C)| 0.08 %| 0.15 %| 0.05 %| 0.15 %
Pt1000 (-200 to 650 °C)| 0.07 %| 0.15 %| 0.04 %| 0.15 %
K, J, R, S, T, N, E, B| 0.07 % ( )| 0.15 % ( )| 0.04 % ( )| 0.15 % ( )
mV| 0.07 %| 0.15 %| 0.04 %| 0.15 %
NTC| 0.20 °C (0.36 °F)| 0.45 °C (0.81 °F)| 0.15 °C (0.27 °F)| 0.45 °C (0.81 °F)

Table 2 – Input accuracy

*() Add cold junction compensation: < ± 1 °C (1.8 °F).
Power supply influence: < 0.005 % / V typical (percentage of the full measure range).
Output (4-20 mA): 4-20 mA current, 2-wires; and proportional to the configured range.
Output Resolution (4-20 mA): 0.25 µA
Power supply: 8.5 to 36 Vdc (output 4-20 mA)
Maximum load (RL): RL (max.) = (Vdc – 8.5) / 0.0215 [Ω] Where: Vdc = Power supply voltage (8.5 to 36 Vdc)
Operating Temperature: -40 to 85 °C (-40 to 185 °F)
Humidity: 0 to 90 % RH
It features electrical isolation between input and output: 1.5 Vrms
Internal protection against polarity inversion.
Cold junction compensation for thermocouples.
Connection Wire Cross Section: 0.14 to 1.5 mm²
Screw Tightening: 0.8 Nm
Housing: ABS UL94-HB
Protection: IP20
Standards and Certifications:** NAMUR NE-43 standard and CE, UKCA, and HART® certifications.

CONFIGURATION

When the transmitter is used with the factory setting, no further action is required and the transmitter is ready to be installed.
Changes to the configuration are possible through the TxConfig II software, provided free of charge.
The TxConfig II configuration software allows the device configuration.
A TxConfig-HRT interface is required to allow communication between a computer and the device. The Txconfig II configuration software is continuously updated and new versions can be downloaded at no charge from the manufacturer’s website. To install, execute the TxConfigIISetup.exe file and follow the instructions.
The interface connects the transmitter to the computer, as shown in Fig. 1: novus TxIsoRail HRT Temperature Transmitter -
Transmitter

SOFTWARE CONFIGURATION:

novus TxIsoRail HRT Temperature Transmitter - SOFTWARE
CONFIGURATION

The fields on the screen mean:

  1. General Information: This field shows information that identifies the transmitter. This information should be sent to the manufacturer in an eventual request for technical assistance.

  2. Sensor: Select the type of sensor to be used. See Table 1.

  3. Unit: Select the temperature unit to °C (Celsius) or °F (Fahrenheit).

  4. Range: Sets de measurement range of the transmitter.
    Lowest Limit: Equivalent temperature for a current of 4 mA.
    Highest Limit: Equivalent temperature for a current of 20 mA.
    Sensor Range
    The values chosen cannot exceed the Range of sensors shown in this field. See Table 1 of this manual.
    Minimum Range
    Do not set a lower band (span) than the Minimum Range indicated below in this same field. See Table 1 of this manual.

  5. HART Information:
    Tag: Field with a brief identification of the equipment (up to 8 characters);
    Descriptor: Descriptor used by the master to register the data (up to 16 characters);
    Message: Message used by the master for registering (up to 32 characters);

  6. Sensor Failure: It establishes the output behavior when the transmitter indicates a failure:
    Minimum: Output current goes to < 3.6 mA (down-scale), typically used for refrigeration.
    Maximum: Output current goes to > 21.5 mA (up-scale), typically used for heating.

  7. Zero Offset: It corrects small deviations presented in the transmitter output, for example, when the sensor is replaced.

  8. Filter: Damping filter.
    The damping filter changes the response time of the transmitter in order to smooth the variations in the output. The value set in the filter indicates the time interval at which the PV will reach 63 % of its final value.
    The factory setting is 1.0 s and can be changed from 0 s to 32 s.
    For example, in the case where the temperature should range from 0 ° C to 100 ° C, if you consider the factory settings, after 1.0 s the temperature value shall be equal to 63 °C. A zero value disables this function.

  9. Enable Write protection: When activated, the configuration is not allowed.

  10. Send Configuration: It applies to the new setup. Once sent, the setup will be immediately applied to the transmitter.

  11. Read Configuration: Reads the current configuration in the transmitter connected. The screen now presents the current setup that may be changed by the user.

  12. Polling Address: Dynamic (i.e., configurable) address that allows devices to be quickly identified on a network.

  13. Enable Current Loop: When disabled, the current remains at 4 mA.

FACTORY SETTINGS

  • Sensor: Pt100 3-wire, range 0 to 100 °C
  • Sensor failure: Upscale (maximum)
  • 0 °C zero correction
  • Unit: °C
  • Filter: 1.0 s
  • Address: 0
  • Current Loop: Enabled
    | It is possible to configure the device through third-party software and with the help of an FSK modem to perform HART® communication.
    An EDD (Electronic Device Descriptor) file is available, which can be used with compatible systems and allows access to the settings and supervising the transmitter.
    ---|---
    To put the devices on the same network (or put them in multidrop mode), they must have different polling addresses and the current loop must be disabled.

novus TxIsoRail HRT Temperature Transmitter - Handheld terminal
connection

MECHANICAL INSTALLATION

The TxIsoRail-HRT transmitter is suitable to be installed in a 35 mm DIN rail. Vibrations, moisture and extreme temperatures, electromagnetic interference, high voltage, and other interferences can permanently damage the unit and could cause an error in the measured value.
DIMENSIONS

novus TxIsoRail HRT Temperature Transmitter -
DIMENSIONS

ELECTRICAL INSTALLATION
Fig. 5 shows the electrical connections required. The TxIsoRail-HRT wiring for thermocouple, RTD, resistance, and voltage is done according to Fig. 4. novus TxIsoRail HRT Temperature Transmitter - ELECTRICAL
INSTALLATION

LOAD represents the 4-20 mA current measuring device (indicator, controller, register, etc.).

  • Polyamide enclosure.
  • Section of the cable used: 0.14 to 1.5 mm ².
  • Recommended torque in the terminal: 0.8 Nm.

RECOMMENDATIONS FOR INSTALLATION

  • Conductors of small electrical signals must be distant from activation or high-tension/current conductors, preferably passing through grounded conduits.
  • A specific electrical power supply network should be provided for instrument use only.
  • In controlling and monitoring applications, possible consequences of any system failure must be considered in advance.
  • RC filters (47 Ω and 100 nF) in inductor charges (contactors, solenoids, etc.) are recommended.

ELECTRICAL CONNECTIONS
The figures below show the electrical connections required. Terminals 1, 2, 3, and 4 are dedicated to the sensor connection. LOAD represents the 4-20 mA current measuring device (indicator, controller, recorder, etc.).
Pt100 2-WIRE
Note: When the Pt100 2-wire the terminals 1 and 3 must be interconnected, according to the figure below.
To use the Pt100 2-wire, you must configure the Pt100 3-wire option in TxConfig II.
The Pt100 wire length should be less than 30 cm to maintain the measurement error within specifications (electrical resistance). novus TxIsoRail HRT
Temperature Transmitter - ELECTRICAL CONNECTIONS

Pt100 3 and 4-wire / Pt1000 3 and 4-wire: The use of wires with the same length and gauge is recommended for better resistance compensation. The transmitter compensates for up to 25 ohms per wire. novus TxIsoRail HRT
Temperature Transmitter - ELECTRICAL CONNECTIONS 1

OPERATION

The transmitter is factory calibrated with standardized sensors, not requiring any adjustment by the user.
Fine corrections can be accomplished through the TxConfig II software (in units of temperature).
The user may choose the sensor and the span that best fits its application. The sensor span must lie within the range specified for the selected sensor.
It is important to note that the accuracy of the transmitter refers to the maximum range of the sensor used, regardless of the actual span.
Example:

  • The sensor Pt100 has a maximum range of -200 to 650 °C and typical accuracy of 0.08 %.
  • Thus, we can have a typical error up to 0.68 °C (0.08 % of 850 °C).
  • This error is the same, no matter if the total span is used (-200 to 650 °C) or a narrower user-defined span is used, like 0 to 100 °C.

WARRANTY

Warranty conditions are available on our website www.novusautomation.com/warranty.