ABBA DA-600S-12W4-1 600W Stainless Steel Transformer Instruction Manual

June 3, 2024
ABBA

!! ATTENTION !!

Please read and understand thoroughly this installation guide to ensure safe and efficient operation of this Power Module.

Open

Open shipping carton, and carefully remove the transformer.
Open the side flap inside of shipping canon and remove the Bottom Plate and Bottom Plate hardware bag if supplied with unit.
Inspect shipping carton contents for any damage that may have been incurred during shipment.
The Bottom Plate has pluged holes for adapting to standard conduit sizes, as well as a 1-3/4″ diameter access hole to allow for a larger centrally located 1-112° conduit for a cleaner. more professional looking installation.

Mount the Unit

Mount the Transformer to a solid surface using keyhole slots in the mounting bracket. (NOTE: The transformer must be mounted at least one foot above ground level, with the wire terminals facing down,)

Secure the Transformer using the appropriate wall anchors for the wall surface used.

Determine the Load

These transformers are equipped with secondary circuit breakers that are connected to the COM Each circuit can be loaded up to a maximum of 300 watts.
A) Add up your fixture’s wattage. Divide your load into 300W max. per wire run. DO NOT EXCEED 300W PER RUN!! (Example.5x6OW or 3x100W)
B) Measure the approx. distance from the transformer to the last fixture on each run. Refer to Chart 1 to pick the correct tap for each run. You may use one two, three or all taps at once.

Voltage/
Watt| TAP 1
12V| TAP 2
1W| TAP 3
14V| TAP 4
15V
---|---|---|---|---
AWG
12| AWG
10| AWG
12| AWG
10| AWG
12| AWG
10| AWG
12| AWG
10
100 – 149| 38| 60| 76| 120| 113| 180| 151| 240
150 – 199| 25| 40| 50| 80| 76| 120| 101| 160
200 – 249| 19| 30| 38| 60| 57| 90| 76| 120
250 – 300| NA| 24| NA| 48| NA| 72| NA| 96

CHART 1 (WIRE RUNS IN FEET)

Once you find the correct tap for each run, See Chart 2 to calculate the cable losses.

Cable loss = (loss per foot X distance )
= (0.293 X 40ft) +(0.855 X 57ft) (0.293 X 80ft)
= (11.72) + (48.735) + (23.44)
= 83.895 watt losses total.

Determining Maximum Lamp Load:

All of our Transformers are designed to provide up to maximum wattage rating.
However, you must take into account the cable losses.

Example Maximum Lamp Load = (Transformer rating mumus (cable losses)
= (600W) – (83.895)
= approximately 516W Lamp Load. Your maximum 4amp load should not exceed approximately 516W

CHART 2 (WATT AGE LOSSES PER FOOT)

AWG 100W 150W 200W 300W
12 0.210 0.461 0.855 N/A
10 0.131 0.293 0.537 1.2

Connecting the Cables

Loosen the screws that hold the unit bottom cover side in place, and turn the bottom cover out and remove plug hole.
Run lighting cables through knockouts in Bottom Plate.
Connect the low voltage cables to the COMs and low voltage taps labeled on the Terminal blocks Make sure that all connecting screws are secure and tight.

Using Minimum 12AWG(or suitable) for connection. the cable may be used type SPT-3. (To order additional wire contact an electrical supply company) The cable is intended for shallow burial – less than 6 inches(152mm)

REMEMBER!! Maximum 300W per circuit!!

Turn off ALL the circuit breakers in the transformer unit Plug the 120V line cord into a grounded 120V outlet. Turn on one breaker at a time to ensure that your low voltage cable runs are connected per Chart 1. and to ensure that there are not any short circuits.

Checking the Output AMPS

Once you have checked all the runs for correct voltages, use a clamp-on Amp Meter and check the output current on the low-voltage cable at the transformer.
REMEMBER!! Maximum 25Amp per circuit!!

Checking the input AMPS

Your Transformer is provided with a long loop that you may utilize to measure the input current Simply apply the clamp on the Amp Meter around the loop and measure the current (See Chart 3)
REMEMBER!! Do not exceed the maximum input current!! The Transformer is marked with a label showing the maximum input current.

Added Features Installation Instructions

Installing the Photo-control:

  1. Make sure power is off and transformer is not plugged into an electrical outlet
    NOTE: No splice or wiring is required if transformer is equipped with jumper connector.

  2. Turn out the clip of transformer case and open front cover and remove one (1) of the 7/8″ plug hole on the side of the enclosure

  3. Locate and disconnect the white jumper connector inside the housing *Save the jumper connector with these instructions for future use.

  4. Remove the photo-control star lock-up nut and push the photo-control white connector through the plug hole Replace the star lock-up nut.

  5. Plug photo-control white connector into the inside panel connector. Ensure that the side latch locks the connector in place. Arrange wires carefully inside the housing Push the front cover back and replace clip into position and secured Turn on the power.

  6. Locate transformer and position photo-control so that no artificial light will cause the photo-control to cycle on and off ‘In the unlikely event that the photo-control should fail, the lighting fixtures will remain on, even in the daytime If this should happen, follow these instructions and remove the defective photo-control and place the jumper connector in its place.
    Contact your local Distributor to order replacement photo-control.

Installing the 24 Hour Time Clock

  1. Open the front cover of the transformer housing
  2. Unplug the cord from the receptacle
  3. Plug the cord into the 24 Hour Time Clock.
  4. Plug the 24 Hour Time Clock into the transformer receptacle
  5. Set the time on the 24 Hour Time Clock per the instructions provided with the Time Clock.

Important Safety Instructions

When using electrical products, basic precautions should always be practiced including the following.

  1. Read and follow all safety instructions.
  2. Read and follow all instructions that are on the product or provided with the product
  3. This product can be installed either indoor or outdoor use.
  4. For use with low voltage landscape lighting systems only.
  5. The load connected to each circuit can be loaded up to a maximum of 300 watts.
  6. “WARNING – Risk of Electric Shock Install power unit 5 feet (1.5 m) or more from a pool. spa, or fountain Where the power unit is installed (a) indoors within 10 feet (3.0 m) of a pool, spa, or fountain or (b) outdoors connect power unit to a receptacle protected by a GFCI For Outdoors – the power unit shall be connected to a GFCI protected hooded flush type cover plate receptacle marked “Wet Location” while in use.
  7. Do not use with an extension cord.
  8. Always plug the transformer into a grounded 120 volt GFCI receptacle.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ABBA User Manuals

Related Manuals