red SMOKE ALARMS R240ACB Isolated Base Instruction Manual
- June 3, 2024
- red Smoke Alarms
Table of Contents
INSTRUCTION MANUAL
R240ACB ISOLATOR BASE
Mains Powered R230V
Product Description
R240ACB (isolator base) is designed to be installed with R240 series and
R240RC series smoke alarms and Red Smoke Alarm RAC240 to function with
Test/Locate/Silence capabilities. R240ACB must be used where a four-wire
circuit is installed with the isolator feature.
The standard R240/R240RC mounting plate cannot be used in a four wire
smoke/heat alarm system and must be replaced with the isolator base R240ACB.
Mode of Operation
The R240ACB mounting plate retains all the functionality of a standard
mounting plate but has additional features required where the isolator
function is to be used. It can be easily distinguished from the standard
plate by the warning label.
The R240AC base separates the switch wire (disconnect) and neutral connections
to provide a 4-wire circuit where the isolator feature is required in a
smoke/heat alarm system.
Installation
Terminate the wiring from the Isolator units or R240/ R24ORC to the terminal
block of R240ACB as follows:
I: Interconnect- connects to I between smoke alarms
N: Neutral- connects to the Neutral incoming wire from the Isolator N
SW: Switch- disconnects the Switch wire from the Isolator
A: Live- connects to the Active incoming wire from the Isolator A
Refer to respective manuals for wiring details.
NOTE: Switch wire must be fitted to “SW” terminal.
R240 Series and R240R Series smoke alarm heads, lock onto the R240ACB with a
click sound heard. Refer to respective smoke alarm manuals for details of head
removal and attachment.
Choose a suitable mounting hole on the Isolator Base to secure with screws
onto the ceiling.
Instruction Leaflet
Contains important information on unit operation and installation. Read
carefully and retain for your records. If you are an installer, this leaflet
must be given to the householder.
Warning
Mixing the Active and Neutral (Switch) connections will damage the alarm.
Ensure that the same colours are used throughout the premises for Active,
Neutral, Switch and Interconnect wires.
The R240ACB must be installed by a licensed electrician in accordance with
regulations for electrical Installation (AS3000). Failure to install the
alarms correctly may expose the user to shock or fire hazard.
RED SMOKE ALARMS Pty Ltd
35 Hitech Drive
KUNDA PARK QLD 4556
service@redsmokealarms.com.au
www.redsmokealarms.com.au
1300 316 552