YELLOW JACKET 49984 Test and Charging Manifold Owner’s Manual
- June 1, 2024
- YELLOW JACKET
Table of Contents
Owner’s Manual TITAN® Test and Charging Manifold
49984 Test and Charging Manifold
Due to the unusually high pressures and hazardous gasses used in refrigeration
and air conditioning, only TRAINED refrigeration and air conditioning
technicians should use this equipment. Proper procedures must be used.
Section 608 of the Federal Clean Air Act requires that all persons who
maintain, service, repair, or dispose of appliances must be certified since
No-vember 14, 1994. Failure to comply can cost you and/or your company as much
as $25,000 per day, per violation. The EPA also offers a reward up to $10,000
for providing information concerning violations to the Act.
PROCEDURES
The various service and testing procedures below can be performed after the
manifold gauge set has been installed as shown in the following diagrams.
Key : I. TO PURGE HOSES BEFORE HOOKING UP
1 & 2 Connect hoses at
E & F Do not tighten
C&D _ Close valves
4 Connect hose G to refrigerant
A & B Open valves
D & G Crack D & G valve to begin purge
E & F Tighten hose II. TO OBSERVE OPERATING PRESSURES
A & B Close valves
C & D Close valves
1 & 2 Connect hoses as illustrated
E & F Crack open back seat
III. TO CHARGE REFRIGERA-TION SUCTION (VAPOR) SIDE WITH SCHRADERS
Purge as in I
Charge as in IV IV. TO CHARGE REFRIGERATION SUCTION (VAPOR) SIDE
Purge as in I
4 Connect hose G to refrigerant
A Open valve
B & C Close valves
D Open valve and throttle
F Crack front seat V. TO PULL VACUUM
D Close valve
H Connect hose 3 to pump
C Open valve
A & B Open valves
E & F Mid position valves Note: To improve pull down time, use core
removal tool (to minimize restrictions), and use minimum 3/8” or larger hose.
VI. TO SET LOW SIDE CONTROL BUILD UP PRESSURE
Disconnect pressure control line. Using flare union, screw union into control
line and other end of hose 1.
B,C & D Close valves
A Open valve
E Back seat then crack open
F Back seat F
B Open to regulate pressure; set control
REMOVING THE MANIFOLD FROM THE SYSTEM
After completing service operations, you must remove the manifold from the system without losing refrigerant or admitting air.
- Close valves E & C.
- Then open manifold valves A, B and D, 1/2 turn.
- Close valve F.
This arrangement will move all the high-pressure refrigerant from the line and the high-pressure gauge and put it into the low side. Close all manifold valves and remove hoses.
PARTS LIST
Test Equipment Depot
800.517.8431
TestEquipmentDepot.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>