CET CGAS-D Digital Gas Detectors Instruction Manual

June 1, 2024
CET

Modbus® Holding RegistersCET CGAS D Digital Gas
Detectors CET Digital
Gas Detectors
www.critical-environment.com

CGAS-D Digital Gas Detectors

The CGAS-D, CGAS-DP, LPT-M and LPT-P transmitters and the cGas-SC Self Contained Controller may be configured as part of a Modbus® RTU RS-485 network. In order for communication to be successful between devices, be sure your network connection is complete, the network termination switches are set appropriately and all the devices are configured with the same baud rate, character format, etc. Each device will have its own unique Modbus® ID.
NOTES:

  • CGAS-D and CGAS-DP can have up to 2 gas channels (or 1 gas and 1 particulate channel) plus an RH channel and a Temperature channel
  • The cGas-SC can have up to 3 gas channel plus a horn, strobe, buzzer, RH and Temperature channel
  • The LPT-P does not support a relay.
  • LPT-P and LPT-M can have up to 3 gas channels.

If you have specific requirements, have any questions or require clarification about these holding registers, please contact CET for assistance.
Holding Registers From 1 to 50,320

Register Description Information
1 Internal Relay 1 output status (excluding LPT-P)
2 Internal Relay 2 output status (cGas-SC only)
3 Strobe (cGas-SC only)
4 Internal or External Buzzer (cGas-SC only)
30,001 Channel 1 Reading present reading x scaler

 30,004
30,005| Channel 1 Alarm Status
Channel 2 Reading| present reading x scaler| LEL, PPM, %VOL, μg/m3
30,008| Channel 2 Alarm Status| |
30,009|  Channel 3 Reading| present reading x scaler| LEL, PPM, %VOL, DegC, DegF, %RH
30,012| Channel 3 Alarm Status| |
30,013| Channel 4 Reading| present reading x scaler| LEL, PPM, %VOL, DegC, DegF, %RH
30,016| Channel 4 Alarm Status| |
30,017| Channel 5 Reading| present reading x scaler| LEL, PPM, %VOL, μg/m3
30,020| Channel 5 Alarm Status| |
40,101| Number of Relays present (excluding LPT-P)| |
40,103| Number of Channels present| |
41,013 to 41,028| Model Name| 32 bytes|
41,035 to 41,042| Serial Number| 16 bytes|
41,045| Firmware Version| if changed by program, may require Reset|
41,113| Modbus ID| if changed by program, may require Reset|
41,114| Modbus Baud Rate| if changed by program, may require Reset|
45,002| Relay On Delay (excluding LPT-P)| seconds|
45,003| Relay Off Delay (excluding LPT-P)| seconds|

CHANGING ANY VALUES IN THE CHANNEL HOLDING REGISTERS WILL VOID ANY CALIBRATION OR LIABILITY FOR CORRECT OPERATION. THESE VALUES ARE FOR REFERENCE ONLY.

Register Description Sensor Scaler Information
50,004 Decimal Place multiplier (1, 10, 100, 1000)
50,005 Sensor Range decimals (0, 1, 2)
50,008 Low Alarm Set Point with scaler factor
50,011 Mid Alarm Set Point with scaler factor
50,012 High Alarm Set Point with scaler factor
50,013 Gas/Value Name with scaler factor
50,025 to 50,027 Gas/Value Units
50,028 to 50,030 eg. LEL, PPM, %VOL, DegC, DegF, %RH
50,033 Priority Membership
50,079 Channel 1 Warmup Timer

Repeat 50,004 to 50,079 for each channel that is present. Each channel has an offset of 80 from the previous channel’s equivalent register.
© 2024 All rights reserved. Data subject to change without notice.

SAFER AIR EVERYWHERE.
www.critical-enviroment.com
Unit 145, 7391 Vantage Way, Delta, BC V4G 1M3 Canada
Tel: +1.604.940.8741 Toll
Free: +1.877.940.8741
© 2024 All rights reserved. Data subject
to change without notice.