CET CGAS-D Gas Detector Digital Transmitter Instruction Manual
- June 10, 2024
- CET
Table of Contents
CET CGAS-D Gas Detector Digital Transmitter
Product Information
The cGas Detector Digital Transmitter is a gas detector that is designed to
detect the presence of gas and provide digital output signals to a control
system. It is manufactured by Critical Environment Technologies and is
designed to be installed by a qualified electrician or factory trained
technician.
The device comes with a manual that provides detailed information on the
installation process, technical specifications, sensor options, and
troubleshooting. The manual also includes information on the exterior
enclosure and interior system layout, as well as general safety warnings and
protection against electrical and mechanical risks.
The transmitter is available in single-channel gas sensor options, dual- channel gas sensor options, and ESH-A-Remote sensor options. It also includes calibration-extending firmware (CEF) and sensor aging features.
Product Usage Instructions
- Read and understand the installation manual before using the instrument. Carefully read the warranty policy, service policy, notices, disclaimers, and revisions on the following pages.
- Install the cGas Detector Digital Transmitter by a qualified electrician or factory-trained technician according to instructions indicated in the manual.
- Inspect and calibrate the device regularly by a qualified and trained technician.
- Refer to the cGas Detector Operation Manual for more information on topics such as:
- General description
- Key features
- Technical specifications
- Enclosure dimensions
- Special considerations for different types of sensors
- Troubleshooting
Installation Manual
Rev. A | 2022.06
CGAS-D Gas Detector
Digital Transmitter www.critical-environment.com
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
NEED MORE INFORMATION?
This is the Installation Manual for the cGas Detector Digital Transmitter. If
you would like it in pdf form, click here to open and download it from our
website.
If you need more information, refer to the cGAS Detector Operation Manual,
which covers topics such as:
· Relays – enable/disable, set ON/OFF Delays · Enable/Disable Channels ·
Replacing Plug & Play Smart Sensors · Calibration · Accessories · Maintenance
· Troubleshooting
If you would like to view or download the cGAS Detector Operation Manual from
our website click here
2
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
© 2022 All rights reserved. Data subject to change without notice.
3
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
6.4 Protection Against Mechanical Risks…………………………………………. 25 6.5 Mounting the
Transmitter………………………………………………………….. 26
6.5.1 Wet Environment Considerations ………………………………………… 26 6.5.2 EMI and RF
Interference Considerations …………………………….. 27 6.5.3 Mounting Heights (Sensor
Dependent) ……………………………….. 27 6.6 Enclosure Mounting Components
……………………………………………… 30 6.6.1 Enclosure Base…………………………………………………………………….. 30
6.6.2 Enclosure Bottom ………………………………………………………………… 31 6.7 Wiring
Connections…………………………………………………………………… 31 6.7.1 Digital Wire Gauge vs Run
Length ……………………………………….. 34 6.7.2 Wiring the Relay Smart Board (models with
Option -RLY) …… 36 6.7.3 ESH-A Remote Sensor Wiring Connection…………………………… 36
7 BASIC SYSTEM OPERATION ……………………………………………………………..38 7.1 Power-up and Warm-up
Process from Factory ……………………………. 38 7.2 Navigating the Menu Structure
………………………………………………….. 39 7.3 Accessing the Menu with
Passcodes…………………………………………. 39 7.4 Display Settings…………………………………………………………………………
40 7.4.1 Adjust Display Brightness ……………………………………………………. 40 7.4.2 Display
Configurations…………………………………………………………. 41 7.5 Alarm Status, Fault Detection and
Communication Failure Alerts … 42 7.6 Change Units (oC or oF) of Temperature
Readings……………………….. 43 7.7 Temperature and/or Relative Humidity Offset
…………………………….. 44 7.8 Test Functions………………………………………………………………………….. 45 7.8.1
Test Readings / Digital Output …………………………………………….. 45 7.8.2 Test Relay (models
with Option -RLY)………………………………….. 46
8 TROUBLE SHOOTING………………………………………………………………………..47
4
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
POLICIES
1.1 Important Note Read and understand this manual prior to using this
instrument. Carefully read the warranty policy, service policy, notices,
disclaimers and revisions on the following pages.
This product must be installed by a qualified electrician or factory trained
technician and according to instructions indicated in this manual. This
instrument should be inspected and calibrated regularly by a qualified and
trained technician.
This instrument has not been designed to be intrinsically safe. For your
safety, do not use it in classified hazardous areas (explosion-rated
environments).
INSTRUMENT SERIAL NUMBER: __ PURCHASE DATE: __ PURCHASED FROM:
© 2022 All rights reserved. Data subject to change without notice.
5
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
Warranty Policy
Critical Environment Technologies Canada Inc. warrants the products we
manufacture (excluding sensors, battery packs, batteries, pumps, and filters)
to be free from defects in materials and workmanship for a period of two years
from the date of purchase from our facility. Sensors are consumable items and
once they leave our factory, we cannot reuse or resell them. As such, all
sensor sales are final. Should the sensor itself be faulty, there is a one-
year pro-rated warranty that would apply from the date of purchase from our
facility.
The warranty status may be affected if the instrument has not been used and
maintained as per the instructions in the manual or has been abused, damaged,
or modified in any way. The product is only to be used for the purposes stated
in the manual. Critical Environment Technologies is not liable for auxiliary
interfaced equipment or consequential damage.
Prior to shipping equipment to CETCI, contact our office for an RMA #. All
returned goods, regardless of reason, must be accompanied with an RMA number.
Please read our Warranty and Returns Policy and follow our RMA Instructions
and Form.
Due to ongoing research, development, and product testing, the manufacturer
reserves the right to change specifications without notice. The information
contained herein is based on data considered accurate. However, no warranty is
expressed or implied regarding the accuracy of this data.
1.3 Service Policy
CETCI maintains an instrument service facility at the factory. Some CETCI
distributors / agents may also have repair facilities; however, CETCI assumes
no liability for service performed by anyone other than CETCI personnel.
Repairs are warranted for 90 days after date of shipment (sensors have individual warranties). Should your instrument require non-warranty repair, you
6
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
may contact the distributor from whom it was purchased or you may contact
CETCI directly.
Prior to shipping equipment to CETCI, contact our office for an RMA #. All
returned goods, regardless of reason, must be accompanied with an RMA number.
Please read our Warranty and Returns Policy and follow our RMA Instructions
and Form.
If the product is deemed repairable, for liability reasons, CETCI will perform
all necessary repairs to restore the instrument to its full operating
condition.
1.4 Copyrights
This manual is subject to copyright protection; all rights are reserved. Under
international and domestic copyright laws, this manual may not be copied or
translated, in whole or in part, in any manner or format, without the written
permission of CETCI.
Modbus® is a registered trademark of Gould Inc. Corporation. BACnet® is a
registered trademark of American Society of Heating, Refrigeration and Air
Conditioning (ASHRAE).
Disclaimer
Under no circumstances will CETCI be liable for any claims, losses or damages
resulting from or arising out of the repair or modification of this equipment
by a party other than CETCI service technicians, or by operation or use of the
equipment other than in accordance with the printed instructions contained
within this manual or if the equipment has been improperly maintained or
subjected to neglect or accident. Any of the forgoing will void the warranty.
Under most local electrical codes, low voltage wires cannot be run within the
same conduit as line voltage wires. It is CETCI policy that all wiring of our
© 2022 All rights reserved. Data subject to change without notice.
7
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
products meet this requirement. It is CETCI policy that all wiring be within properly grounded (earth or safety) conduit.
1.6 Revisions
This manual was written and published by CETCI. The manufacturer makes no
warranty or representation, expressed or implied including any warranty of
merchantability or fitness for purpose, with respect to this manual.
All information contained in this manual is believed to be true and accurate
at the time of printing. However, as part of its continuing efforts to improve
its products and their documentation, the manufacturer reserves the right to
make changes at any time without notice. In addition, due to improvements made
to our products, there may be information in this manual that does not exist
in the version of the product the user has. Should you detect any error or
omission in this manual, or should you want to inquire regarding upgrading the
device’s firmware, please contact CETCI at the following address:
Critical Environment Technologies Canada Inc. Unit 145 – 7391 Vantage Way,
Delta, BC V4G 1M3 Canada
Toll Free: +1.877.940.8741 Telephone: +1.604.940.8741 Email:
marketing@cetci.com Website: www.critical-environment.com
In no event will CETCI, its officers or employees be liable for any direct,
special, incidental or consequential damages resulting from any defect in any
manual, even if advised of the possibility of such damages.
8
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
2 INTRODUCTION
2.1 General Description
Thank you for purchasing our cGas Detector Transmitter. The cGas Detector is a
one or two channel gas detection transmitter that offers flexible
customization options with the purpose of meeting your specific application
and budgetary requirements. Ideal for monitoring toxic, combustible and
refrigerant gases in non-hazardous (non-explosion rated) environments such as
enclosed parking facilities, commercial HVAC, greenhouses, recreational
facilities, refrigeration plants, manufacturing plants and other light
industrial applications.
The sensors utilized in this device are accurate enough to measure to
Occupational Health & Safety (OHS) hazardous levels for toxic gases. The
transmitter operates by diffusion.
Key Features
· 1 or 2 gas channel operation · User configurable Modbus® RS-485 RTU or
BACnet® MS/TP
communication protocols for communication with a Controller or Building
Automation System (BAS) · Easy Plug & Play Smart sensor replacement at end of
life · Customizable sensor and option combinations to meet specific
application requirements · 24 volt DC or (ground referenced) AC power ·
4-conductor shielded network wiring (daisy-chain) · In-field upgradable
firmware/configuration via USB stick · LCD display · Option -LT*: Low
temperature package for improved usability in cold
© 2022 All rights reserved. Data subject to change without notice.
9
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
environments · Option -RHT: Relative Humidity and Temperature sensor ·
Option -RLY**: One SPDT dry contact relay, rated 30 volts, 2 amps · Option
-S: Splash guard, factory installed, IP54 rated enclosure · Option -SN: Splash
guard for sticky gas sensors, factory installed · Standard water / dust tight,
corrosion resistant enclosure (drip proof) · Copper coated interior to reduce
RF interference · RoHS compliant circuit boards · Auto resetting fuse
NOTE: Options may be restricted to certain models and/or gas configurations.
Option -LT is a low temperature package with OLED display and internal heater for cold environment applications down to -40°C / -40°F. Available with all models except CGAS-D-EETO.
Option -RHT is an RH & Temperature sensor (oC or oF). Available with all
internal gas sensor configurations except sticky gas sensors (Cl2, ClO2, HCI,
HCN, O3, PH3). Available with dual channel configurations that have a standard
CO sensor.
***Option -RLY is a one SPDT dry contact relay, rated 30 volts, 2 amps max.
Available with all internal gas sensor configurations except CO2 and sticky
gas sensors (Cl2, ClO2, HCI, HCN, O3, PH3). Options -RHT and -RLY are both
available with CGAS-D-CO only
If after reading through the manual, you have any questions, please do not
hesitate to contact our Technical Support department at help@cetci.com.
10
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
3 INSTRUMENT SPECIFICATIONS
3.1 Technical Specifications
MECHANICAL
Enclosure
Weight Size Conduit Entry Points
Mounting Holes
ABS / Polycarbonate, IP54 rating with splash guard installed. Copper coated
interior to reduce RF interference.
400 g / 14 oz
127 mm x 127 mm x 71 mm / 5.0 in x 5.0 in x 3.0 in
12.7 mm / 1/2 in diameter
4.47 mm / 0.175 in diameter maximum head diameter 8 mm / 0.32 in #8 or 4 mm
screw
USER INTERFACE Display (standard) Display (Option -LT) USB Port Push Buttons Audible Alarm
2-line by 16-character graphic LCD, user configurable to suppress reading
display and/or alter brightness
Optional OLED display for improved usability in low temperature applications,
2-line by 16-character
Internal port for USB memory stick connection for field configuration/firmware
upgrades
Initiate calibration and menu options with internal UP, DOWN and ENTER push
buttons
none
© 2022 All rights reserved. Data subject to change without notice.
11
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
ELECTRICAL Power Requirement
Digital Wiring Fuses
16 – 30 VDC, 3 W, Class 2 12 – 27 VAC, 50-60 Hz, 3 VA, Class 2 24V
recommended. Refer to Section 6.7 Wiring Connections
VDC or VAC (ground referenced) four-conductor shielded 16 AWG stranded within
conduit, network wiring (daisy-chain)
Automatic resetting thermal
INPUT/OUTPUT Communication Modbus® RTU (version 1.1b3) RS-485
Communication BACnet® MS/TP (version 1 rev 14) RS-485
12
Modbus® ID: 100 (default, configurable) Baud rate: 19,200 (default,
configurable) Data bits: 8 Start bits: 1 Stop bits: 1 Parity: none, odd or
even
BACnet® MS/TP; ANSI/ASHRAE standard 135 BACnet® Communication protocol:
135-2012 Baud Rate: 76,800 (default, configurable) Base Address: 270 (default,
configurable) MAC Address: 100 (default, configurable) Parity: none (default,
configurable) Stop bits: 1 Data bits: 8
100 is the default for transmitters only *101 increasing sequentially is the default for a system controller and transmitters
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
Relay (Option – RLY)
RH and Temperature (Option -RHT)
1 SPDT dry contact relay, rated 30 volts @ 2 amps (not available with CO2,
CL2, CLO2, HCI, HCN, O3 or PH3 sensor configurations)
User selectable units (oC or oF), user selectable display or hide readings
((not available with CO2, CL2, CLO2, HCI, HCN, O3 or PH3 sensor
configurations)
ENVIRONMENTAL Operating Temperature Operating Humidity Pollution Degree Altitude
0°C to 40°C / 32°F to 104°F (standard) -40°C to 40°C / -40°F to 104°F (with Option -LT) 15 – 90% RH non-condensing Degree 2 below 2,000 m
CERTIFICATION
Model: CGAS-D-XXX S/N: CGASD1807B00010
Rating: 16-30 VDC, 3W, Class 2 12-27 VAC, 50-60 Hz, 3VA, Class 2
CERTIFIED FOR ELECTRIC SHOCK & ELECTRICAL FIRE HAZARD ONLY. LA CERTIFICATION
ACNOR COUVRE UNIQUEMENT LES RISQUES DE CHOC ELECTRIQUE ET D’INCENDIE D’ORIGINE
ELECTRIQUE.
© 2022 All rights reserved. Data subject to change without notice.
13
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
Conforms to: CSA-C22.2 No. 205-12, UL508 (Edition 18):2018 Conforms to: EMC
Directive 2014/30/EU, EN 50270:2015, Type 1, EN61010 Conforms to: FCC. This
device complies with part 15 of the FCC Rules, Operation is subject to the
following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including
interference that may cause undesired operation.
3.2 Enclosure Dimensions
Above dimensions are shown with optional standard splash guard. Without splash guard, thickness is 71 mm / 3.0 in. The area required for enclosure door to be open 90 degrees is 178 mm / 7.0 in or 254 mm / 10.0 in for fully open. With the optional splash guard installed, the enclosure is IP54 rated.
14
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
4 SENSOR SPECIFICATIONS
4.1 Single Channel Gas Sensor Options
Internal Infrared Sensors Part Number
CGAS-D-CO2-5K
Carbon Dioxide (CO2)
CGAS-D-CO2-5K CGAS-D-CO2-5%
Range 0 – 2,000 ppm 0 – 5,000 ppm 0 – 5% vol
Lifespan ~ 8 yrs
Internal Electrochemical Sensors
Part Number
Range
Lifespan
Ammonia (NH3) Carbon Monoxide (CO)
CGAS-D-NH3 CGAS-D-CO 1
0 – 500 ppm 0 – 200 ppm
~2 yrs ~6 yrs
Chlorine (Cl2)
CGAS-D-CL2 CGAS-D-CL2-10
0 – 5.0 ppm 0 – 10 ppm
~3 yrs ~3 yrs
Chlorine Dioxide (ClO2)
CGAS-D-CLO2
0 – 1 ppm
~2 yrs
Ethylene (C2H4) *
CGAS-D-C2H4 *
0 – 200 ppm ~2 yrs
- not suitable for use in applications with continuous exposure to ethylene, i.e. ripening rooms, use LPT-A, LPT-B or LPT-M instead
Fluorine (F2) Formaldehyde (CH2O) Hydrogen (H2) Hydrogen Sulphide (H2S)
CGAS-D-F2 CGAS-D-CH2O CGAS-D-EH2 CGAS-D-H2S
0 – 1 ppm 0 – 5 ppm 0 – 2,000 ppm 0 – 50 ppm
~2 yrs ~2 yrs ~2 yrs ~2 yrs
© 2022 All rights reserved. Data subject to change without notice.
15
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
Hydrogen Chloride (HCl) CGAS-D-HCL
Hydrogen Cyanide (HCN) CGAS-D-HCN
Hydrogen Fluoride (HF) CGAS-D-HF
Nitric Oxide (NO)
CGAS-D-NO
Nitrogen Dioxide (NO2) Oxygen (O2) Ozone (O3) Phosphine (PH3) Silane (SiH4) Sulphur Dioxide (SO2)
CGAS-D-NO2 CGAS-D-O2 CGAS-D-O3 CGAS-D-PH3 CGAS-D-SIH4 CGAS-D-SO2
0 – 30 ppm 0 – 30 ppm 0 – 10 ppm 0 – 100 ppm 0 – 10 ppm 0 – 25% Vol 0 – 1 ppm 0 – 5 ppm 0 – 20 ppm 0 – 20 ppm
~2 yrs ~2 yrs ~2 yrs ~2 yrs ~3+ yrs ~3 yrs ~2 yrs ~2 yrs ~2 yrs ~2 yrs
Internal Solid State Sensors Refrigerant R22 Refrigerant R134A Refrigerant
R402A Refrigerant R404A Refrigerant R407C Refrigerant R410A Refrigerant R422D
Refrigerant R438A
16
Part Numbers
CGAS-D-SR22 CGAS-D-SR134A CGAS-D-SR402A CGAS-D-SR404A CGAS-D-SR407C
CGAS-D-SR410A CGAS-D-SR422D CGAS-D-SR438A
Range
Lifespan
0 – 2,000 ppm 0 – 2,000 ppm 0 – 2,000 ppm 0 – 2,000 ppm 0 – 2,000 ppm 0 – 2,000 ppm 0 – 2,000 ppm 0 – 2,000 ppm
~5 yrs ~5 yrs ~5 yrs ~5 yrs ~5 yrs ~5 yrs ~5 yrs ~5 yrs
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
Refrigerant R507A Refrigerant R513A Refrigerant R514A TVOC (Isobutylene)
cGas Detector Digital Transmitter – Installation Manual
CGAS-D-SR507A CGAS-D-SR513A CGAS-D-SR514A CGAS-D-STVOC
0 – 2,000 ppm 0 – 2,000 ppm 0 – 2,000 ppm 0 – 500 ppm
~5 yrs ~5 yrs ~5 yrs ~5 yrs
Internal Catalytic (Combustible) Sensors
Part Number
Ethanol or Dimethyl Ether CGAS-D-
(C2H6O)
CC2H6O-100
Ethane (C2H6)
CGAS-DCC2H6-100
Hydrogen (H2) Methane (CH4)
Methanol (CH4O)
CGAS-D-CH2-100
CGAS-D-CCH4-100
CGAS-DCCH4O-100
Propane (C3H8)
CGAS-DCC3H8-100
Range 0 – 100% LEL 0 – 100% LEL 0 – 100% LEL 0 – 100% LEL 0 – 100% LEL 0 – 100% LEL
Lifespan ~5 yrs ~5 yrs ~5 yrs ~5 yrs ~5 yrs ~5 yrs
Internal PID Sensors TVOC TVOC
Part Number CGAS-D-SPL CGAS-D-SPH
Range 0 – 30 ppm 0 – 300 ppm
usage / application dependent
© 2022 All rights reserved. Data subject to change without notice.
17
cGas Detector Digital Transmitter – Installation Manual
Internal RH & Temp Sensor
Relative Humidity and Temperature
Part Number CGAS-D-RHT
Rev. A | 2022.06
No Internal Sensor
Add a remote ESH-A sensor
Add a remote analog transmitter
Part Number CGAS-D-R CGAS-D-RT
4.2 Dual Channel Gas Sensor Options
Two Internal Electrochemical Sensors
Part Number
Carbon Monoxide (CO) and Nitrogen Dioxide (NO2)
Carbon Monoxide (CO) and Ethylene (C2H4)
Carbon Monoxide (CO) and Hydrogen Sulphide (H2S)
CGAS-D-CO-NO2 1 CGAS-D-CO-C2H4 1 CGAS-D-CO-H2S 1
Range
0 – 200 ppm 0 – 10 ppm
0 – 200 ppm 0 – 200 ppm 0 – 50 ppm
Lifespan
~6 yrs ~3+ yrs ~6 yrs ~2 yrs ~6 yrs ~2 yrs
18
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
Carbon Monoxide (CO) and Oxygen (O2)
Carbon Monoxide (CO) and Nitric Oxide (NO)
CGAS-D-CO-O2 1 CGAS-D-CO-NO 1
0 – 200 ppm
0 – 25% vol 0 – 200 ppm 0 – 100 ppm
~6 yrs
~3 yrs ~6 yrs ~3 yrs
Hydrogen Sulphide (H2S) and Sulphur Dioxide (SO2)
CGAS-D-H2S-SO2
0 – 50 ppm 0 – 20 ppm
~2 yrs
1UL2075 Approved Carbon Monoxide sensor is available except for dual channel configurations that have Option -RHT.
One Internal Sensor and One Remote Sensor
Choose internal sensor and add remote ESH-A sensor
Choose internal sensor and add remote analog transmitter
Part Number
CGAS-D--R add ESH-A
CGAS-D--RT add ESH-A
4.3 ESH-A Remote Gas Sensor Options
Catalytic Sensors Part Number
Acetylene (C2H2) ESH-A-CC2H2-100
Hydrogen (H2) Methane (CH4)
ESH-A-CH2-100 ESH-A-CCH4-100
Range
Lifespan
0 – 100% LEL ~5 years
0 – 100% LEL ~5 years
0 – 100% LEL ~5 years
© 2022 All rights reserved. Data subject to change without notice.
19
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
Propane (C3H8)
ESH-A-CC3H8-100 0 – 100% LEL ~5 years
Infrared Sensors Propane (C3H8)
Part Number ESH-A-JET
Range
Lifespan
0 – 100% LEL ~8 years
PID Sensors TVOCs
Part Number ESH-A-SPL ESH-A-SPH
Range 0 – 30 ppm 0 – 300 ppm
Lifespan
usage / application dependent
4.4 Calibration Extending Firmware (CEF) and Sensor Aging
The cGas Detector with integral electrochemical sensor(s) have been programmed
with our CEF. This firmware takes into consideration the aging of the
electrochemical CO and NO2 sensors so that less frequent calibrations are
required in less-critical applications such as parking garages. The system
tracks the age of the sensor and automatically compensates for the reduced
output of the sensor as it ages.
20
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
5 INSTRUMENT FEATURES
5.1 Exterior Enclosure
NUMBER
FEATURE Door Hinge
Display Sensor Opening Door Screw Lock Slot
FUNCTION Secures door to base and allows easy opening and closing LCD display
(standard display)
Allows gas diffusion into sensor
Secures door shut
For security padlock or tie
© 2022 All rights reserved. Data subject to change without notice.
21
cGas Detector Digital Transmitter – Installation Manual
5.2 Interior System Layout
Rev. A | 2022.06
NUMBER FEATURE
Programming Buttons
RS-485
Communication
Terminals
USB Connection
Termination Resistor
Sockets for
sensors and
Options boards
A
B
FUNCTION
Access menu options and program functions using buttons inside the enclosure.
(Arrow up, Enter, Arrow down)
Pluggable power and signal terminal for connection to controller and next
transmitter.
For firmware and configuration upgrades
Network termination resistor. “IN” position includes 120 ohm resistor.
Sensor boards and Options boards plug into the main board using these sockets
22
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
6 INSTALLATION
The sensor(s) in the cGas Detector go through a burn in period at our factory
prior to shipping so it is ready for operation upon arrival. When installing
the cGas Detector for the first time, the sensor may require a long warm up
time (24 to 48 hours) to stabilize and provide accurate readings.
NOTE: CETCI suggests that upon power-up, all sensors be left to warm up for
24 hours prior to considering the gas readings to be accurate. except,
Ammonia which should be left to warm up for 48 hours.
NOTE: All sensors are calibrated in the factory and should not require
calibration at the time of a routine installation or replacement.
NOTE: If the sensor is being used in an extreme temperature range, calibration
should be done in that same temperature range.
6.1 Special Considerations for Different Types of Sensors If the cGas Detector
is being installed in an environment that is different than ambient room
temperature, you may want to do a full calibration. This will allow for the
device to compensate for the new environment in which it is being installed.
After installing a cGas Detector with an Oxygen sensor, leave it to warm up
for 2 – 6 hours before looking at the readings. If after a minimum of 24 hours
the gas reading is not 20.9%, you should do a respan.
After a substantial warm up period, an Ethylene Oxide sensor should be zeroed
on site if the ambient temperature is above 22°C (71.6°F). This particular
sensor has a drift factor that can be as much as 1 ppm if the temperature
rises to 25°C (77°F). With the low set point you could experience false
alarms.
© 2022 All rights reserved. Data subject to change without notice.
23
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
Ammonia sensors should be left to warm up for 48 hours so the sensor can
stabilize.
Ozone sensors are sensitive and may be reactive to temperature changes causing
them to drift.
Silicone, lead and chlorinated hydrocarbon vapours can poison catalytic
sensors.
A bump test will help you determine if a sensor requires calibration. If the
sensor still does not respond as it should after a successful calibration, it
probably requires replacing.
6.2 General Safety Warnings
The cGas Detector is intended for indoor use, permanently mounted at a height
that is appropriate for the type of gas being monitored. Refer to Section 6.5
Mounting the Transmitter. The cGas Detector should be protected from extreme
weather conditions.
The cGas Detector requires no assembly and virtually no maintenance other than
regular calibration of the internal and/or remote sensors and ensuring that
excess water or dust are not somehow entering the enclosure and physically
damaging the circuit board or internal components. There are no serviceable
elements other than the calibration instructions outlined in this manual.
There are no replaceable components except the plug and play smart sensor
boards.
6.3 Protection Against Electrical Risks
Disconnect all power before servicing. There may be multiple power sources.
Power supply may have a building installed circuit breaker / switch that is
suitably located and easy to access when servicing is required and should be
labelled as cGas Detector supply (disconnecting power to the cGas Detector).
24
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
Appropriate markings should be visible at the circuit breaker / switch that is
supplying power to the cGas Detector.
This device may interfere with pacemakers. Modern pacemakers have built-in
features to protect them from most types of interference produced by other
electrical devices you might encounter in your daily routine. If you a have a
pacemaker, follow your healthcare provider’s instructions about being around
this type of equipment.
6.4 Protection Against Mechanical Risks
The door of the enclosure can be removed if absolutely necessary to facilitate
installation of the base but it is not recommended on this model. Extreme care
and caution must be exercised when removing the door to avoid damaging the
hinges. The door should only be removed when absolutely required. Any damage
occurring from door removal procedure will not be covered under warranty.
If the unit is installed on a wall or column, open the enclosure fully, grasp
the door, keeping it open and being careful not to make contact with any of
the internal components (circuit board). If the base is not mounted, grasp the
base with your other hand. Tug on the door, pulling towards you making sure
the door is still open and straight. DO NOT TWIST. The section of the hinges
located on the base should “snap” apart from the part of the hinges located on
the door.
After installation, place the door hinges over the installed base hinges, with
the unit fully open and push towards the wall. The hinges should easily “snap”
back into place.
The enclosure has one screw securing the door to the base for electrical
safety and provides an opening to allow the user to apply a padlock or tie
wrap if they desire the transmitter to be locked.
© 2022 All rights reserved. Data subject to change without notice.
25
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
Be aware that the hinged door that could potentially pinch fingers and the sharp edges and/or jumper pins on the board could potentially prick or cut fingers if not handled carefully.
6.5 Mounting the Transmitter
The cGas Detector should be installed vertically and upright on a flat surface
like a wall of column. Secure the transmitter using the the four 4.4 mm /
0.175 in diameter mounting holes provided to maintain water tight status. Care
should be taken to ensure that the face of the cGas Detector is not obstructed
in order to maximize the sensor’s exposure to the environment being monitored.
Do not mount the transmitter upside down, sideways or flat on the floor or
other surface.
Two ½ in / 12.7 mm conduit entry points are provided in the enclosure. Both
are located in the enclosure base. One in the rear of the base and one on the
bottom edge of the base. Refer to Section 6.6 Enclosure Mounting Components.
The clearance from the PCA to the base enclosure is 12.7 mm / ½ in. Do not use
a conduit connector that has more than 12.7 mm (½ in) of thread length.
NOTE: When mounting the enclosure, allow enough room to allow the end user to
open the door fully to access the internal adjustments.
6.5.1 Wet Environment Considerations If the cGas Detector is to be installed
in a potential hose-down application or any application whereby liquid could
be directed towards the sensor opening, the cGas Detector should be ordered
with an optional attached splash guard (factory installed).
If used in a wet or wash down application, the conduit hub entering the cGas
Detector enclosure must be liquid tight type. Water damage is not covered
under warranty. Any physical damage to the transmitter or interior components
26
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
that occurs from the installer drilling the installation holes will not be
covered under warranty.
6.5.2 EMI and RF Interference Considerations All electronic devices are
susceptible to EMI (Electromagnetic Interference) and RFI (Radio Frequency
Interference). Our detectors have been designed to reduce the effects of these
interferences and we meet CSA FCC and CE requirements for these type of
devices. However there are still circumstances and levels of interference that
may cause our equipment to respond to these interferences and cause them to
react as if there has been gas detected.
There are some installation procedures that will reduce the likelihood of
getting faulty readings:
1. Locate the detectors and controllers out of the way from normal foot
traffic and high energy equipment.
2. Confirm the devices are properly grounded using conduit and shielded
cabling.
3. Inform operators and technical staff working in the surrounding area to be
aware of these possible conditions and that two way radios, cell phones and
other electrical equipment may interfere with the response of the gas
detectors.
6.5.3 Mounting Heights (sensor and application dependent) The gas detector
needs to be mounted where it will best detect the target gas. Some
applications may require some adjustments, but generally speaking, the
mounting height will depend on the density of the target gas relative to air.
Heavier than air gases fall towards the floor and collect in low lying areas.
Thus heavier than air gas sensors should be mounted 6 in / 15 cm from the
floor. Lighter than air gases float upwards and collect at the ceiling.
Lighter than air sensors should be placed on or near the ceiling. Gases that
have a density
© 2022 All rights reserved. Data subject to change without notice.
27
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
close to that of air should have the sensors installed in the breathing zone. The breathing zone refers to the area 1.2 – 1.8 m / 4 – 6 ft from the floor, where most human breathing takes place. This is a good default location for sensors, as many gases are often well dispersed in air.
Typical Mounting Height by Gas:
GAS TYPE
MOUNTING HEIGHT
Ammonia (NH3)
on or near the ceiling
Carbon Dioxide (CO2)
breathing zone
Carbon Dioxide (CO2)
breathing zone
Carbon Monoxide (CO) breathing zone
Chlorine (Cl2)
6 in (15 cm) from floor
Ethane (C2H6) (combustible)
6 in (15 cm) from floor
Propane (C3H8) (combustible)
6 in (15 cm) from floor
Methane (CH4) (combustible)
on or near the ceiling
Hydrogen (H2) (combustible)
on or near the ceiling
Ethanol (C2H6O) (alcohol)
6 in (15 cm) from floor
COVERAGE (ft2)
3000
COVERAGE (m2)
279
3000 3000 5000 – 7500 3000
279 279 465 – 697 279
3000
279
3000
279
5000
465
5000
465
3000
279
28
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
Methanol (CH4O) (alcohol)
6 in (15 cm) from floor
Hydrogen (H2)
application dependent
Ethylene (C2H4)
breathing zone
Fluorine (F2)
6 in (15 cm) from floor
Formaldehyde (CH2O)
breathing zone
Hydrogen Chloride (HCl)
12 in (30 cm) from floor
Hydrogen Cyanide (HCN)
12 in (30 cm) from floor
Hydrogen Sulphide (H2S)
3 ft (91 cm) from floor
Nitric Oxide (NO)
breathing zone
Nitrogen Dioxide (NO2) breathing zone
Oxygen (O2)
breathing zone
Ozone (O3)
6 in (15 cm) from floor
Phosphine (PH3)
breathing zone
Silane (SiH4)
breathing zone
Sulphur Dioxide (SO2)
6 in (15 cm) from floor
© 2022 All rights reserved. Data subject to change without notice.
3000
3000
5000 3000
3000 3000
3000
3000
5000 5000 5000 3000
3000 3000 3000
279 279 465 279 279 279 279 279 465 465 465 279 279 279 279
29
cGas Detector Digital Transmitter – Installation Manual
All freon refrigerants All freon refrigerants R123 refrigerant (only) TVOCs
12 in (30 cm) from floor
12 in (30 cm) from floor
12 in (30 cm) from floor
target gas dependent
6.6 Enclosure Mounting Components 6.6.1 Enclosure Base
Rev. A | 2022.06
3000
279
3000
279
3000
279
3000
279
NUMBER
FEATURE Door Hinge
30
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
Conduit Entry Points 12.7 mm / 1/2 in diameter
Mounting Holes 4.47 mm / 0.175 in diameter
maximum head diameter 8 mm / 0.32 in, #8 or 4 mm
screw
6.6.2 Enclosure Bottom
NUMBER
FEATURE Door Hinge Conduit Entry Points 12.7 mm / 1/2 in diameter
6.7 Wiring Connections
The cGas Detector transmitter is a low voltage powered device. Any application
of operating voltages higher than indicated in the specification may result in
damage. Double check wiring connections prior to powering the transmitter.
Damage from incorrect wiring connections or from too much voltage applied is
not covered under warranty.
All wiring should be run in EMT (or better) conduit properly earth grounded. All communications (network) wiring must be in shielded cabling. Wire shielding must be connected together at each device and taped off so it cannot cause
© 2022 All rights reserved. Data subject to change without notice.
31
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
a short on the circuit board when the door is closed. The wiring shield should
be connected to ground only at the controller, have a contiguous connection
throughout the network and be left taped and floating at the last device in
the network. CETCI recommends 4 conductor, 16 AWG, shielded stranded wire
cable types like AlphaWire 79220, Belden 5202FE 008500 or equivalent.
To ensure robust data communications, a daisy chain wiring configuration must
be used. No tee taps. No star configurations. This means, four wires run from
one end of the digital network to the other, through the same connections
along the entire run. From one digital device to the next digital device, A
goes to A; B goes to B; GND goes to GND; 24V goes to 24V. Do not mix up the
individual wires or the two groups of four wires.
An end of line jumper must be installed at both ends of the digital network.
To terminate, you must place a 120 ohm resistor on the IN (or sometimes
labelled EN) termination jumper position ON the TERM jumper on the FIRST
DIGITAL DEVICE (which might not be the Controller) and the LAST DIGITAL DEVICE
in the wire run. The termination resistor jumper on all other digital devices
in the network should be in the disabled position. Every CETCI digital device
has a termination resistor jumper. The factory default setting of the
termination resistor on all digital devices disabled.
The wiring should be 4-conductor shielded 16 awg stranded within conduit in a
network wiring (daisy-chain) configuration. Suggested 4-conductor, 16 AWG,
shielded stranded wire cable types are AlphaWire 79220, Belden 5202FE 008500
or equivalent.
32
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
Wiring Example: 4-Wire VAC If the cGas Detector is being connected to a BAS, DDC or other control panel then either a 24 VDC power supply or 24 VAC Class 2 or better transformer needs to be used.
Wiring Example: 4-Wire VDC If the cGas Detector is being connected to an FCS the supply voltage will be supplied by the FCS and any additional power requirements of the system will be supplied by RPS-24VDC Remote Power Supply devices.
© 2022 All rights reserved. Data subject to change without notice.
33
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
6.7.1 Digital Wire Gauge vs Run Length It is important to use the appropriate gauge of wire for the required length of the run to ensure sufficient available voltage, noise reduction, dissipation of heat, and overall optimum performance along the entire wire run. Large wire sizes will have less voltage drop than smaller wires sizes of the same length. Similarly, shorter wire lengths will have less voltage drop than longer wires for the same wire size. The longer the wire run, the more attention there should be made to preventing voltage drop. The addition of an RPS-24VDC Remote Power Supply is recommended as follows:
For single channel and low consumption dual channel devices, an RPS24VDC Remote Power Supply should be installed every 32 devices (ie. CGAS-D-CO-NO2). For transmitters connected to ESH-A remote sensors, a remote power supply should be installed every 16 devices (pairs of devices ie. CGAS-D-CO-R + ESH-A-CH2-100).
CETCI strongly recommends a 4-conductor, 16 AWG, shielded, stranded wire cable type such as AlphaWire 79220, AlphaWire 5534, Belden 9954 or equivalent.
34
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
NOTE: When wiring transmitters or the FCS WAN to a third party controller /
control panel / BAS / DDC and there is a discrepancy between CETCI’s
recommended wire gauge and the third party specifications, we recommend
following the recommendations of the third party.
NOTE: WARRANTY VOID IF SOLID-CORE WIRE IS USED AT THE WIRING TERMINAL STRIP.
When using solid core wiring for distribution (in the conduit), use stranded
wire pigtails 14 – 18 AWG within the enclosure to connect to the circuit
board. The rigidity of solid-core wire can pull a soldered terminal strip
completely off a circuit board and this will not be covered under warranty.
Cable Length, Size (AWG) and Maximum Number of Sensors for Digital
Communication and Power Supply between the cGas Detector and the Controller
Cable Length
Meters
Feet
of Sensors
4
6
8
10 12 14 16
0 – 152
1 – 500
AWG # 18 18 18 18 18 18 18
153 – 305 501 – 1, 000 AWG # 18 18 18 18 18 18 18
306 – 457 1,001 – 1,500 AWG # 18 18 18 16 16 16 16
458 – 914 1,501 – 3,000 AWG # 18 16 16 16 16 16 16
In large system applications, if the recommended maximum cable length needs to be exceeded, an LNK-XT Network Extender can be used to boost the decreasing signal strength. One LNK-XT extends the network length up to an additional 914 m (3,000 ft). It is recommended that an LNK-XT be installed when a drop in signal strength is detected.
© 2022 All rights reserved. Data subject to change without notice.
35
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
6.7.2 Wiring the Relay Smart Board (Option -RLY) The cGas Detector is designed to be fail-safe. Equipment to be controlled by the relay smart board should be wired to the “NC” (Normally closed) and “COM” (Common) terminals. With this wiring, the connection will be open under normal, low gas concentration conditions. When the gas concentration rises to the configured alarm point or if there is a power failure, the connection relay will close. The relay coils are normally energized in a non-alarm state for failsafe operation. Refer to cGas Detector Operation Manual for more information.
6.7.3 ESH-A Remote Sensor Wiring Connection Each ESH-A is given the same
serial number as the device it is being connected to. Make sure to connect the
ESH-A to the CGAS-D that has the same serial number or the cGas factory
calibration will be void.
Four-conductor, 16 AWG stranded shielded cable is recommended for the ESH-A
remote sensor wiring. This wiring should be run in a conduit, separate from
the signal output, and should not exceed 15 m (50 ft). The voltage at the
remote sensor (Red V+ to Black GND) should not be below 4.5 volts. If this
voltage is not met after installation, the wrong gauge wire may have been used
or the wiring run is too long.
36
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
Wiring Example: ESH-A Remote Sensor Note: The maximum length of wire between the ESH-A Remote Sensor and the cGas Detector should not exceed 15 m (50 ft).
© 2022 All rights reserved. Data subject to change without notice.
37
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
7 BASIC SYSTEM OPERATION
The cGas Detector continuously monitors target gas concentrations on one or
two configured channels. It must be connected to a controller, control panel
or BAS / BMS / DDC system; the cGas Detector is not a standalone gas detection
system.
NOTE: For functions that do not appear in this section, refer to the cGAS
Detector Operation Manual.
7.1 Power Up and Warm-up Process from the Factory Upon application of power to
a cGas Detector shipped from the factory, the LCD display will turn on and
rotate through several info screens that differ depending
on the configuration of the transmitter. The warm-up period takes between 2
and 5 minutes depending on the gas sensors type.
NOTE: The cGas Detector will be visible on the controller / BAS / DDC system
during the warm-up countdown and will output a default value to prevent
alarms. The accurate reading will show up when the unit has finished the
warmup period and the sensor(s) has stabilized.
All alarms will be disabled during the system warm-up period. After the warm-
up period, the system may exhibit gas alarm condition(s) if one or both of the
sensors has not completely stabilized during the warm up period. This is
normal and the length of time the gas alarms exist is dependent upon the
length of time since the unit was last powered up, and the state of the
environment it is installed in. Refer to Section 6.1 Special Considerations
for Different Types of Sensors for more information about sensor warm up time.
Upon power-up, all sensors* should be left to warm up for 24 hours prior to considering the gas readings to be accurate.
38
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
*except, Ammonia, which should be left to warm up for 48 hours.
All sensors are calibrated in the factory prior to shipping and should not
require calibration at the time of a routine installation or replacement.
7.2 Navigating the Menu Structure The three programming push-buttons inside
the enclosure are used to navigate through the cGas Detector menu structure.
Refer to Section 5.1 Exterior Enclosure for location photo.
ENTER begins a process or moves you to the next screen in the same menu.
The UP or DOWN buttons are used to enter characters/numbers and to navigate to
the next menu item. For simplicity’s sake, directions in this manual use the
UP button.
A line under a character or number indicates that is the space into which you
are entering a character or number. Use the ENTER button to move to the next
space. Or use the UP or DOWN button to change the value in that space.
The > symbol indicates that you are in the edit mode as opposed to scrolling
through available menu items.
After entering and confirming a value you can either Exit the menu or press
the UP button to move to the next item in that menu. All menus are circular
and will bring you back to the Exit screen. Press ENTER to Exit.
7.3 Accessing the Menu with Passcodes
You have to enter a passcode to access the menu. From the normal operation
screen, press ENTER to access the password entry screen. Use the UP or DOWN
arrow to scroll to the desired number. Press ENTER to move to the next
© 2022 All rights reserved. Data subject to change without notice.
39
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
position. Continue until the full code is entered and press ENTER when finished.
CODE 0001
1014
NAME Test Menu
Display Menu
DESCRIPTION
· Test Reading (Digital Output) · Test Relay (if Option -RLY is installed)
· Display Type · Brightness · Selected Channel · Hide Channel · Scroll Delay
7.4 Display Settings
The LCD display can display up to 2-lines of 16-characters. The backlight can
be turned off, but in normal operation, as configured from the factory, the
display is backlit. After warm-up and upon normal operation, the display will
show the current gas level reading for each channel that it has been
configured. Pressing the UP or DOWN button allows you to scroll through a
series of information screens showing the model name, serial number and
firmware version; the gas type and AD counts; the channel number, gas type and
gas level; and
temperature and relative humidity (if option -RHT is installed).
7.4.1 Adjust Display Brightness The brightness of the display and the
information displayed can be changed as per your preference.
From the main display, press ENTER. Enter passcode 1014 using the UP button
and ENTER button.
Enter Password 1014
Press ENTER to access the Display Menu.
40
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
DisplayMenu Press Enter
Brightness 100
Press ENTER. Use the UP button to change the numeric value. Move to the next
digit by pressing ENTER. When finished, press ENTER to confirm and Exit.
Brightness >050
Confirm?
N
50
Y
NOTE: You cannot enter a number higher than 100. Entering a value of 000 turns the backlight off completely. With ambient light the text can still be read on the display.
7.4.2 Display Configurations The default display set from the factory is normal mode which displays the gas
type, gas reading and gas units for CH1.
CO
0 PPM
The information can be reduced to just the gas type by changing the setting to
the minimal mode display.
****-CO*****
From the main display, press ENTER. Enter passcode 1014 using the UP button
and ENTER button.
Enter Password 1014
Press ENTER to access the Display Menu.
DisplayMenu Press Enter
Display Type Normal
Press ENTER. Use the UP button to change the display type and press ENTER
to save and Exit.
Display Type >Minimal
© 2022 All rights reserved. Data subject to change without notice.
41
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
7.5 Alarm Status, Fault Detection and Communication Failure Notifications If a
channel is in alarm, the following letters will be displayed at the end of the
line for that channel.
· low for low alarm · mid for mid alarm · high for High alarm
CO
0 PPM CO
0 PPM CO
0 PPM
NO2
0.7 low NO2
1.0 mid NO2
1.5 high
The cGas Detector has built in fault detection, and in the event of a problem with the measurement circuitry the transmitter will indicate a fault condition on the display. Normal operation will resume once the fault condition has been corrected.
NOTE: If a question mark ? is displayed, the system is reading slightly negative but not enough to adversely affect the alarm functionality; a re- zeroing is recommended.
If there is a communication failure between the cGas Detector and the controller or BAS, the screen will display COMM at the end of the line.
CO
0 COMM
NO2
0 COMM
For a list of Fault Codes, refer to Section 8 Troubleshooting.
42
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
7.6 Change Units (oC or oF) of Temperature Readings
NOTE: This menu item only applies if the cGas Detector has the -RHT option
installed.
You can change the factory configured temperature unit type from Celsius to Fahrenheit (or vice versa) very easily.
From the main display, press ENTER. Enter passcode 3032 using the UP button and ENTER button.
Enter Password 3032
Press ENTER to access the Calibrate Menu.
Calibrate Menu Press Enter
In the Selected Channel menu, if Temperature is not displayed, press ENTER and
use the UP button to scroll to find Temperature. Press ENTER.
Selected Channel CO
Selected Channel >Temperature
Use the UP button to find Temperature Unit. If you want to change the unit type, press ENTER.
Temperature Unit Celsius
Press the UP button to choose Fahrenheit press ENTER and ENTER to exit.
Temperature Unit >Fahrenheit
Confirm?
N
Confirm?
N
-4.0 degC
Y >+2 %RH
Y
© 2022 All rights reserved. Data subject to change without notice.
43
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
7.7 Temperature and / or Relative Humidity Offset
NOTE: This menu item only applies if the cGas Detector has the -RHT option
installed.
NOTE: Depending on the configuration, the device will show the temperature in either Celsius or Fahrenheit. The units can be changed at any time, refer to Section 7.6 Change Units (oC or oF) of Temperature Readings.
The temperature and relative humidity sensor is calibrated prior to shipping. If the readings on the cGas Detector are higher or lower than another device measuring the ambient temperature or relative humidity, you can adjust the reading by setting an offset value so the reading is more accurate. The Temperature offset value is a number of degrees in either direction of 0 and the Humidity offset value is a percentage between 0 or 100.
From the main display, press ENTER. Enter passcode 3032 using the UP button and ENTER button.
Enter Password 3032
Press ENTER to access the Calibrate Menu.
Calibrate Menu Press Enter
In the Selected Channel menu, if Temperature (or Humidity) is not displayed,
press ENTER and use the UP button to scroll to find the item you are looking
for. Press ENTER.
Selected Channel CO
Selected Channel >Temperature
Selected Channel >Humidity
Use the UP button to find Temperature Adj (or Humidity Adj). If you want to change the offset value, press ENTER. Change the offset value using the UP or DOWN and ENTER buttons.
44
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
Temperature Adj >-4.0 degC
Humidity Adj >+02 %RH
Press ENTER to confirm the value is correct. If you entered the wrong value, press the UP button to move the cursor to N and press ENTER and reenter the value.
Confirm?
N
Confirm?
N
-4.0 degC
Y >+2 %RH
Y
7.8 Test Functions
7.8.1 Test Reading / Test Digital Output For each gas channel, you can
manually enter a gas reading value of your choice (within the range of the
sensor) that will be sent over the digital network to test the connection and
configured responses between the cGas Detector and the DDC/BAS. You can do the
same for relative humidity and temperature if the -RHT option is installed.
From the main display, press ENTER. Enter passcode 0001 using the UP button
and ENTER button.
Enter Password 0001
Press ENTER to access the Test Menu.
Test Menu Press Enter
In the Selected Channel menu, confirm the correct channel is showing.
Selected Channel CO
If you want to choose a different channel, press ENTER and use the UP button
to scroll to the next value. Press ENTER and continue.
© 2022 All rights reserved. Data subject to change without notice.
45
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
Selected Channel >NO2
The list to choose from will depend on included sensors and options: · Gas
Type (ie. CO) · Gas Type (ie. NO2) · Temperature · Humidity
Press the UP button to find Test Reading. To make a change, press ENTER and
then use the UP, DOWN and ENTER buttons to enter the value.
Test Reading 0 PPM NO2
Test Reading >10.0 PPM NO2
Press ENTER and then again to Confirm Y.
Confirm? >10.0 PPM NO2
N Test Reading >Y 10.0 PPM NO2
The test will start as soon as you press ENTER to confirm. To stop the test,
press the UP or DOWN button. To test another analog output value repeat the
process by pressing ENTER.
7.8.2 Test Relay (models with Option -RLY installed) NOTE: Before testing the
relay, notify the appropriate people so unnecessary distress or response is
not caused by activating fans or equipment or inadvertently calling the fire
department or other emergency response team.
From the main display, press ENTER. Enter passcode 0001 using the UP button
and ENTER button.
Enter Password 0001
Press ENTER to access the Test Menu.
Test Menu Press Enter
46
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
In the Test Relay menu, the default entry is Untripped. Press ENTER and use the UP button to change to Tripped. Press ENTER. You will hear a soft click and the relay will activate accordingly, respecting its failsafe setting.
Test Relay Untripped
Test Relay >Tripped
To stop the relay test, press the UP or DOWN button. You will hear a soft click and the relay will deactivate.
Test Relay:SB >Untripped
When finished, press the UP button and press ENTER on the Exit menu item.
8 TROUBLE SHOOTING
cGas Detector won’t power up. (blank display) Is the power properly connected?
Check the wiring connections. Refer to Section 6.7 Wiring Connections.
cGas Detector display shows “COMM” message. Modbus® or BACnet output signal
has not been connected properly; will also occur if no requests are being made
from the controller to the transmitter, ie addressing is not proper. Check the
wiring connections and the network settings.
Device cannot be seen by the Controller and/or the BAS / DDC on the Modbus®
network. Check the Baud rate. All devices in the network must have the same
Baud rate.
· Check that local area network wiring is correct, especially the A and B
lines to make sure they are not swapped between devices on the network.
· Check the Modbus® ID. Each device must have a unique ID assigned to it.
Device cannot be seen by the Controller and/or the BAS / DDC on the BACnet®
network.
© 2022 All rights reserved. Data subject to change without notice.
47
cGas Detector Digital Transmitter – Installation Manual
Rev. A | 2022.06
· Check the Baud rate. All devices in the network must have the same Baud
rate.
· Check to make sure the device has a unique ID assigned to it, the factory
default is made up of the MAC ID and the Base ID
· Check that local area network wiring is correct, especially the A and B
lines to make sure they are not swapped between devices on the network.
Frequent, unexpected alarm reading reported to BAS/DDC. Check to see if EMI and RF interference is causing the equipment to react this way. Refer to Section 6.5.2 EMI and RF Interference Considerations.
List of Possible cGas Error Codes
CODE
DESCRIPTION
F01
Negative Fault Reading
Check to make sure the smart sensor board is present and installed properly in
the socket. If installed, the cGas detects the sensor signal
is too far below its zeroAD. May be caused by a sensor that is temperature or
humidity sensitive or the device wasn’t warmed up for a minimum 24 hours.
After an appropriate warm
up period, zeroing the sensor will normally resolve this.
F02
Smart Board Fault
cGas cannot communicate with the smart board. Ensure the smart board is installed and installed on the correct side (left) if a single channel unit. Otherwise power cycle or replace the sensor smart board.
48
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
cGas Detector Digital Transmitter – Installation Manual
F03
CO2 Communication Fault
cGas cannot communicate with the CO2 sensor even though it can communicate with the smart board. Power cycle or replace the sensor smart board.
F04
POT chip has failed
The internal smart sensor board gainPOT chip has failed. If a power cycle does not resolve this, replace the sensor smart board.
F05
Error in reading Smart Board
cGas detected an error in the smart board ID. Use “Write to Sensor” for the indicated channel (passcode 3022).
FO6
SB ID Mismatch
Firmware expected a different smart board than what is in the sensor socket.
cGas cannot communicate with the sensor.
FO7
RH & Temp Fault
Ensure the smart board is installed correctly. If unresolved, contact our Technical Support
Department
FO8 DAC COMM
This is a hardware fault. Contact our Technical Support Department.
Check to make sure the relay board is present
F20
RLY GPIO chip is not responding
and installed properly in the socket. If installed, main board is unable to communicate with the relay board and may be damaged A
replacement relay board may be required.
The error code will appear on the display in place of the units for a channel.
© 2022 All rights reserved. Data subject to change without notice.
49
cGas Detector Digital Transmitter – Installation Manual
NOTES
Rev. A | 2022.06
50
© 2022 All rights reserved. Data subject to change without notice.
Rev. A | 2022.06
NOTES
cGas Detector Digital Transmitter – Installation Manual
© 2022 All rights reserved. Data subject to change without notice.
51
SAFER AIR EVERYWHERE.
www.critical-enviroment.com
CGAS-D-202206277-Rev-A Unit 145, 7391 Vantage Way, Delta, BC V4G 1M3 Canada
Tel: +1.604.940.8741 Toll Free: +1.877.940.8741 © 2022 All rights reserved.
Data subject to change without notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>