Midea CB1-09HRFN8-I Room Air Conditioner User Manual
- June 1, 2024
- Midea
Table of Contents
- Midea CB1-09HRFN8-I Room Air Conditioner
- Specifications
- Product Overview
- FAQs
- SAFETY PRECAUTIONS
- PRODUCT OVERVIEW
- CHOOSE THE RIGHT CABLE SIZE
- INSTALLATION
- MINIMUM BEND RADIUS
- Manual control button
- SET function
- CARE AND MAINTENANCE
- TROUBLESHOOTING
- TRADEMARKS, COPYRIGHTS AND LEGAL STATEMENT
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Midea CB1-09HRFN8-I Room Air Conditioner
Specifications
- Model Numbers: CB1-09HRFN8-I, CB1-12HRFN8-I, CB1-18HRFN8-I
- Product Type: Room Air Conditioner
- Brand: Midea
Product Overview
The Midea Room Air Conditioner is designed to provide efficient cooling for your space. With smart features and a user-friendly design, it offers convenience and comfort.
Product Installation
Install Your Indoor Unit
- Choose a suitable location on the wall for mounting the indoor unit.
- Securely mount the indoor unit using appropriate brackets and hardware.
- Connect the refrigerant piping following the provided instructions.
- Perform air evacuation and electrical checks as outlined in the manual.
- Test run the unit to ensure proper functioning.
Install Your Outdoor Unit
- Select a location for the outdoor unit with proper ventilation and support.
- Mount the outdoor unit securely on a stable surface.
- Connect the refrigerant piping to the indoor unit following guidelines.
- Complete electrical and gas leak checks before starting the unit.
Operation Instructions
Indoor Unit Display
The indoor unit display provides information on temperature settings, modes, and other functions. Use the remote control to adjust settings as needed.
Remote Control Operation
Use the remote control to change temperature settings, fan speed, mode selection, and other functions. Make sure the remote has clear line-of-sight to the indoor unit for proper operation.
App Setup And Operation
Download the MSmartHome app on your mobile device and follow the
instructions to connect it to your air conditioner. Use the app to
control settings, monitor energy usage, and set schedules for
convenience.
Care and Maintenance
Regularly clean the air filters and coils to ensure efficient operation. Follow the maintenance guidelines provided in the manual to prolong the life of your air conditioner.
Troubleshooting
If you encounter any issues with your air conditioner, refer to the troubleshooting section of the manual for common problems and solutions. If problems persist, contact your dealer or manufacturer for assistance.
FAQs
- Q: How often should I clean the air filters?
- A: It is recommended to clean the air filters every 2 weeks to maintain optimal performance.
- Q: Can I install the air conditioner myself?
- A: It is recommended to have a professional installer handle the installation to ensure proper setup and safety compliance.
EN GR
Room Air Conditioner
MSmartHome
Download the app & activate product
USER MANUAL
MODEL NUMBER: CB1-09HRFN8-I CB1-12HRFN8-I CB1-18HRFN8-I
Warning notices: Before using this product, please read this manual carefully and keep it for future reference. The design and specifications are subject to change without prior notice for product improvement. Consult with your dealer or manufacturer for details. The diagram above is just for reference. Please take the appearance of the actual product as the standard.
THANK YOU LETTER
Thank you for choosing Midea! Before using your new Midea product, please read
this manual thoroughly to ensure that you know how to operate the features and
functions that your new appliance offers in a safe way.
SAFETY PRECAUTIONS
It’s really important you read Safety Precautions Before Operation and
Installation Incorrect installation due to ignoring instructions can cause
serious damage or injury. The seriousness of potential damage or injuries is
classified as either a WARNING or CAUTION.
Explanation of Symbols
Warning of electrical voltage This symbol indicates that there is a danger to
life and health of persons due to voltage. Warning The signal word indicates a
hazard with a medium level of risk which, if not avoided, may result in death
or serious injury. Caution The signal word indicates a hazard with a low
degree of risk which, if not avoided, may result in minor or moderate injury.
Attention The signal word indicates important information (e.g. damage to
property), but not danger. Observe instructions This symbol indicates that a
service technician should only operate and maintain this appliance in
accordance with the operating instructions. Read these operating instructions
carefully and attentively before using/commissioning the unit and keep them in
the immediate vicinity of the installation site or unit for later use!
WARNING
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision(European Union countries).
This appliance is not intended for use by persons(including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
02
WARNING FOR PRODUCT USE
If an abnormal situation arises (like a burning smell), immediately turn off
the unit and disconnect the power. Call your dealer for instructions to avoid
electric shock, fire or injury. Do not insert fingers, rods or other objects
into the air inlet or outlet. This may cause injury, since the fan may be
rotating at high speeds. Do not use flammable sprays such as hair spray,
lacquer or paint near the unit. This may cause fire or combustion. Do not
operate the air conditioner in places near or around combustible gases.
Emitted gas may collect around the unit and cause explosion. Do not operate
your air conditioner in a wet room such as a bathroom or laundry room. Too
much exposure to water can cause electrical components to short circuit. Do
not expose your body directly to cool air for a prolonged period of time. Do
not allow children to play with the air conditioner. Children must be
supervised around the unit at all times. If the air conditioner is used
together with burners or other heating devices, thoroughly ventilate the room
to avoid oxygen deficiency. In certain functional environments, such as
kitchens, server rooms, etc., the use of specially designed air-conditioning
units is highly recommended.
ELECTRICAL WARNINGS
Only use the specified power cord. If the power cord is damaged, it must be
replaced by the manufacturer, its service agent or similarly qualified persons
in order to avoid a hazard. The product must be properly grounded at the time
of installation, or electrical shock may occur. For all electrical work,
follow all local and national wiring standards, regulations, and the
Installation Manual. Connect cables tightly, and clamp them securely to
prevent external forces from damaging the terminal. Improper electrical
connections can overheat and cause fire, and may also cause shock. All
electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units. All wiring must
be properly arranged to ensure that the control board cover can close
properly. If the control board cover is not closed properly, it can lead to
corrosion and cause the connection points on the terminal to heat up, catch
fire, or cause electrical shock. Disconnection must be incorporated in the
fixed wiring in accordance with the wiring rules. Do not pull power cord to
unplug unit. Hold the plug firmly and pull it from the outlet. Pulling
directly on the cord can damage it, which can lead to fire or electric shock.
Do not modify the length of the power supply cord or use an extension cord to
power the unit. Do not share the electrical outlet with other appliances.
Improper or insufficient power supply can cause fire or electrical shock. Keep
power plug clean. Remove any dust or grime that accumulates on or around the
plug. Dirty plugs can cause fire or electric shock. If connecting power to
fixed wiring, an all-pole disconnection device which has at least 3mm
clearances in all poles, and have a leakage current that may exceed 10mA, the
residual current device(RCD) having a rated residual operating current not
exceeding 30mA, and disconnection must be incorporated in the fixed wiring `
in accordance with the wiring rules.
03
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide
overcurrent protection. The specifications of the fuse are printed on the
circuit board , such as : T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC,
T5A/250VAC, T20A/250VAC, T30A/250VAC,etc.
UV-C lamp(Applicable to the unit contains an UV-C lamp only)
This appliance contains a UV-C lamp. Read the maintenance instructions before
opening the appliance.
Do not operate UV-C lamps outside of the appliance. Appliances that are
obviously damaged must not be operated. Unintended use of the appliance or
damage to the housing may result in the escape of dangerous UV-C radiation.
UV-C radiation may, even in small doses, cause harm to the eyes and skin.
Before opening doors and access panels bearing the ULTRAVIOLET RADIATION
hazard symbol for the conducting USER MAINTENANCE, it is recommended to
disconnect the power. The UV-C lamp can not be cleaned, repaired and replaced.
UV-C BARRIERS bearing the ULTRAVIOLET RADIATION hazard symbol should not be
removed.
WARNING
This appliance contains an UV emitter. Do not stare at the light source.
WARNINGS FOR PRODUCT INSTALLATION
Installation must be performed by an authorized dealer or specialist.
Defective installation can cause water leakage, electrical shock, or fire.
Installation must be performed according to the installation instructions. (In
North America, installation must be performed in accordance with the
requirement of NEC and CEC by authorized personnel only). Improper
installation can cause water leakage, electrical shock, or fire. Contact an
authorized service technician for repair or maintenance of this unit. This
appliance shall be installed in accordance with national wiring regulations.
Only use the included accessories, parts, and specified parts for
installation. Using non-standard parts can cause water leakage, electrical
shock, fire, and can cause the unit to fail. Install the unit in a firm
location that can support the unit’s weight. If the chosen location cannot
support the unit’s weight, or the installation is not done properly, the unit
may drop and cause serious injury and damage. Install drainage piping
according to the instructions in this manual. Improper drainage may cause
water damage to your home and property. For units that have an auxiliary
electric heater, do not install the unit within 1 meter (3 feet) of any
combustible materials. Do not install the unit in a location that may be
exposed to combustible gas leaks. If combustible gas accumulates around the
unit, it may cause fire. Do not turn on the power until all work has been
completed. When moving or relocating the air conditioner, consult experienced
service technicians for disconnection and reinstallation of the unit. How to
install the appliance to its support, please read the information for details
in “indoor unit installation” and “outdoor unit installation” sections .
04
CAUTION
Turn off the air conditioner and disconnect the power if you are not going to
use it for a long time. Turn off and unplug the unit during storms. Make sure
that water condensation can drain unhindered from the unit. Do not operate the
air conditioner with wet hands. This may cause electric shock. Do not use
device for any other purpose than its intended use. Do not climb onto or place
objects on top of the outdoor unit. Do not allow the air conditioner to
operate for long periods of time with doors or windows open, or if the
humidity is very high.
CLEANING AND MAINTENANCE WARNINGS
Turn off the device and disconnect the power before cleaning. Failure to do so
can cause electrical shock. Do not clean the air conditioner with excessive
amounts of water. Do not clean the air conditioner with combustible cleaning
agents. Combustible cleaning agents can cause fire or deformation.
Note about Fluorinated Gasses(Not applicable to the unit using R290
Refrigerant)
This air-conditioning unit contains fluorinated greenhouse gasses. For
specific information on the type of gas and the amount, please refer to the
relevant label on the unit itself or the “Owner’s Manual – Product Fiche ” in
the packaging of the outdoor unit. (European Union products only).
Installation, service, maintenance and repair of this unit must be performed
by a certified technician. Product uninstallation and recycling must be
performed by a certified technician. For equipment that contains fluorinated
greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more, but of
less than 50 tonnes of CO2 equivalent, If the system has a leak-detection
system installed, it must be checked for leaks at least every 24 months. When
the unit is checked for leaks, proper record-keeping of all checks is strongly
recommended.
WARNING FOR USING R32/R290 REFRIGERANT
When flammable refrigerant are employed, appliance shall be stored in a well
ventilated area where the room size corresponds to the room area as specifiec
for operation. For R32 frigerant models: Appliance shall be installed,
operated and stored in a room with a floor area larger than 4m2. For R290
refrigerant models, appliance shall be installed, operated and stored in a
room with a floor area larger than: <=2.6kW units: 17.33m2 >2.6kW and <=3.5kW
units: 25.4m 2 >3.5kW and <=5.2kW units: 34.67m 2 >5.3kW and <=7.1kW units:
47.33m2 Reusable mechanical connectors and flared joints are not allowed
indoors.
05
SPECIFICATIONS
PRODUCT OVERVIEW
NOTE ON ILLUSTRATIONS:
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
1 1
3 2
Air-break switch
2
3
4
4 6
5
7
9
8
10 5
6 7
8
11 11
(1)
(2)
1 Wall Mounting Plate 2 Front Panel 3 Power Cable(some units) 4 Louver
5
Functional Filter (On Back of Main Filter – Some Units)
6 Drainage Pipe
7 Signal Cable 8 Refrigerant Piping
9 Remote Controller
10
Remote controller Holder (not supplied)
11 Outdoor Unit Power Cable (some units)
07
PRODUCTION INSTALLATION
ACCESSORIES
The air conditioning system comes with the following accessories. Use all of
the installation parts and accessories to install the air conditioner.
Improper installation may result in water leakage, electrical shock and fire,
or cause the equipment to fail. The items are not included with the air
conditioner must be purchased separately.
Name of Accessories Q’ty(pc)
Shape
Name of Accessories Q’ty(pc)
Shape
Manual
1-3
Remote controller
1
Drain joint
(for cooling &
1
heating models)
Seal
(for cooling &
1
heating models)
Mounting plate
1
Anchor
Mounting plate fixing screw
5~8 (depending on models)
5~8 (depending on models)
Battery
2
Remote controller
holder(purchase separately)
1
Fixing screw for
remote controller
holder(purchase
2
separately)
Small Filter
(Need to be installed on the back of main air filter by the authorized
technician while installing the machine)
1~2 (depending on models)
Name
Connecting pipe assembly
Magnetic ring and belt (if supplied ,please refer to the wiring diagram to
install it on the connective cable. )
Liquid side Gas side
1 2 3
Shape 6.35( 1/4in) 9.52( 3/8in) 9.52( 3/8in) 12.7( 1/2in) 16( 5/8in) 19( 3/4in)
Quantity(PC)
Parts you must purc hase separately. Consult the dealer about the proper pipe
size of the unit you purchased.
Pass the belt through the hole of the Magnetic ring to fix it on the cable
Varies by model
It would be perfect you had these tools
Gloves
Screwdriver & wrench
Percussion drill
Water drill
08
Goggles & masks
Vinyl tape
INSTALLATION SUMMARY – INDOOR UNIT
1
2
15cm (5-7/8″)
3
12cm (4-3/4″)
2.3m (7/8″)
12cm (4-3/4″)
Select Installation Location
4
Attach Mounting Plate
5
Determine Wall Hole Position
6
Drill Wall Hole
7
Connect Piping
8
Connect Wiring
(Not applicable for some locations in North America )
Prepare Drain Hose
9
Wrap Piping and Cable
(Not applicable for some locations in North America )
Mount Indoor Unit 09
Install You Indoor Unit
1 Select installation location
NOTE : Prior to installation
Before installing the indoor unit, refer to the label on the product box to
make sure that the model number of the indoor unit matches the model number of
the outdoor unit. The following are standards that will help you choose an
appropriate location for the unit. Proper installation locations meet the
following standards:
Good air circulation
Convenient drainage
Noise from the unit will not disturb other people.
Firm and solid–the location will not vibrate
Strong enough to support the weight of the unit
A location at least one meter from all other electrical devices (e.g., TV, radio, computer)
DO NOT install unit in the following locations:
Near any source of heat, steam, or combustible gas Near flammable items such
as curtains or clothing
Near any obstacle that might block air circulation
Near the doorway
In a location subject to direct sunlight
NOTE: FOR PRODUCT INSTALLATION
If there is no fixed refrigerant piping: While choosing a location, be aware
that you should leave ample room for a wall hole (see Drill wall hole for
connective piping step) for the signal cable and refrigerant piping that
connect the indoor and outdoor units. The default position for all piping is
the right side of the indoor unit (while facing the unit). However, the unit
can accommodate piping to both the left and right.
10
2
Drill wall hole for connective piping
Determine wall hole location
NOTE : The wall hole size
The size of the wall hole is determined by the connective pipes. When the size
of the gas side
connective pipe is 16mm(5/8″) or more, the wall hole should be 90mm(3-9/16″).
For the size of connective pipe is less than 16mm(5/8″), the wall hole should
be 65mm(2-1/2″).
Step 1 Remove the screw that attaches the mounting plate to the back of the
indoor unit.
Screw
Step 2 Different models have different mounting plates. For the different
customization requirements, the shape of the mounting plate may be slightly
different. But the installation dimensions are the same for the same size of
indoor unit. See Type A and Type B for example
NOTE : FOR CONCRETE OR BRICK WALLS
If the wall is made of brick, concrete, or similar material, drill 5mm-
diameter (0.2in-diameter) holes in the wall and insert the sleeve anchors
provided. Then secure the mounting plate to the wall by tightening the screws
directly into the clip anchors.
Step 4 Confirm the mounting plate you own. Determine the location of the wall
hole based on the position of the mounting plate.The dotted rectangular box
above shows the size of your product
Type A
Type B
426mm(16.8in) 153mm(6.0in) 169mm(6.6in) 169mm(6.6in) 140mm(5.5in)
Step 3
Secure the mounting plate to the wall with the screws provided. Make sure that
mounting plate is flat against the wall.
812mm(40.0in) Wall hole 65mm(2.56in) Indoor unit demensions(WxH): 812mm(40.0in)x299mm(11.8in)
Correct orientation of Mounting Plate
299mm(11.8in)
43mm (1.7in)
11
CAUTION
When drilling the wall hole, make sure to avoid wires, plumbing, and other
sensitive components.
Drill wall hole
65mm (2-1/2″)
90mm (3-9/16″)
Using a 65mm (2-1/2″) or 90mm(3-9/16″) core drill(depending on models )
Wall
Indoor
Outdoor
5-7mm (3/16-5/16″)
Drill the wall hole
Step 1
Using a 65mm (2.5″) or 90mm(3.54″) core drill(depending on models ), drill a
hole in the wall. Make sure that the hole is drilled at a slight downward
angle, so that the outdoor end of the hole is lower than the indoor end by
about 5mm to 7mm (3/16-5/16″). This will ensure proper water drainage.
wall hole.
the protective wall cuff
Place the protective wall cuff in the hole.
Step 2
Place the protective wall cuff in the hole. This protects the edges of the
hole and will help seal it when you finish the installation process.
12
3 Install refrigerant pipe & drain hose
NOTE
The refrigerant piping is inside an insulating sleeve attached to the back of
the unit. You must prepare the piping before passing it through the hole in
the wall.
Prepare refrigerant piping
Left-hand side
Right-hand side
Left rear
Right rear
Four chooses to exit the piping
Step 1
Based on the position of the wall hole relative to the mounting plate, choose
the side from which the piping will exit the unit. You have four options for
the exit direction of the piping. The description of the piping angle below
for details.
Knock-out Panel on the left & right side
Knock-out Panel
Step 2
needle nose pliers
If the wall hole is behind the unit, keep the knock-out panel in place. If the wall hole is to the side of the indoor unit, remove the plastic knock-out panel from that side of the unit.Use needle nose pliers if the plastic panel is too difficult to remove by hand. Note: Groove has been made in the knock- out panel in order to cut it conveniently. The size of the slot is determined by the diameter of pipings.
Step 3
connect the indoor unit’s refrigerant piping to the connective piping that
will join the indoor and outdoor units. Refer to the Refrigerant Piping
Connection section of this manual for detailed instructions.
NOTE If existing connective piping is
already embedded in the wall, proceed directly to the Connect Drain Hose step.
CAUTION
Be extremely careful not to dent or damage the piping while bending them away
from the unit. Any dents in the piping will affect the unit’s performance.
13
Connect drain hose
Drain hose
vinyl tape
Connecting cable
Drain hose
Gas side piping
Liquid side piping
Make sure the drain hose is at the bottom
Drain pipe
Vinyl tape(narrow)
Drain pipe extension
Step 1
The drain hose can be attached to the left or right side To ensure proper
drainage, attach the drain hose on the same side that your refrigerant piping
exits the unit. Attach drain hose extension (purchased separately) to the end
of drain hose.
Wrap the connection point firmly with Teflon tape to ensure a good seal and to
prevent leaks.
For the portion of the drain hose that will remain indoors, wrap it with foam
pipe insulation to prevent condensation.
Remove the air filter and pour a small amount of water into the drain pan to
make sure that water flows from the unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to the following figures.
CORRECT
Make sure there are no kinks or dent in drain hose to ensure proper drainage.
NOT CORRECT
Kinks in the drain hose will create water traps.
NOT CORRECT
Kinks in the drain hose will create water traps.
NOT CORRECT
Do not place the end of the drain hose in water or in containers that collect
water. This will prevent proper drainage.
CAUTION
PLUG THE UNUSED DRAIN HOLE
To prevent unwanted leaks you must plug the unused drain hole with the rubber
plug provided.
14
4 Electrical work preparation
WARNING
BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE REGULATIONS BEFORE
PERFORMING ANY ELECTRLCAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE
SYSTEM.
1. All wiring must comply with local and national electrical codes,
regulations and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical
Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work
immediately. Explain your reasoning to the client, and refuse to install the
unit until the safety issue is properly resolved.
4. If connecting power to fixed wiring, a switch or circuit breaker that
disconnects all poles and has a contact separation of at least 1/8in (3mm)
must be incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
5. Only connect the unit to an individual branch circuit outlet. Do not
connect another appliance to that outlet.
6. Make sure to properly ground the air conditioner. 7. Every wire must be
firmly connected. Loose
wiring can cause the terminal to overheat, resulting in product malfunction
and possible fire. 8. Do not let wires touch or rest against refrigerant
tubing, the compressor, or any moving parts within the unit. 9. To avoid
getting an electric shock, never touch the electrical components soon after
the power supply has been turned off. After turning off the power, always wait
10 minutes or more before you touch the electrical components. 10 Power
voltage should be within 90-110% of rated voltage. Insufficient power supply
can cause malfunction, electrical shock, or fire.
Connect signal and power cables
The signal cable enables communication between the indoor and outdoor units.
You must first choose the right cable size before preparing it for connection.
Cable Types(Not applicable for North America) · Indoor Power Cable (if
applicable):
H05VV-F or H05V2V2-F · Outdoor Power Cable: H07RN-F or H05RN-F
· Signal Cable: H07RN-F
Minimum Cross-Sectional Area of
Power and Signal Cables (For reference)
Rated Current of Appliance (A)
3 and 6 > 6 and 10 > 10 and 16 > 16 and 25 > 25 and 32 > 32 and 40
Nominal Cross-Sectional Area (mm²)
0.75 1
1.5 2.5
4 6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch.
WARNING
All wiring must be performed strictly in accordance with the wiring diagram
located on the back of the Indoor Unit’s front panel.
1. Open front panel of the indoor unit. 2. Using a screwdriver, open the wire
box cover on
the right side of the unit. This will reveal the terminal block. 3. Unscrew
the cable clamp below the terminal block and place it to the side.
15
4. Facing the back of the unit, remove the plastic panel on the bottom left-
hand side.
5. Feed the signal wire through this slot, from the back of the unit to the
front.
6. Facing the front of the unit, connect the wire according to the indoor
unit’s wiring diagram, connect the u-lug and firmly screw each wire to its
corresponding terminal.
7. After checking to make sure every connection is secure, use the cable
clamp to fasten the signal cable to the unit. Screw the cable clamp down
tightly.
8. Replace the wire cover on the front of the unit, and the plastic panel on
the back.
In North America
NOTE: Choose the cable type according to the local electrical codes and
regulations. Please choose the right cable size according to the Minimum
Circuit Ampacity indicated on the nameplate of the unit.
1. Facing the back of the unit, remove the plastic panel on the bottom left-
hand side.
2. As shown in the illustration, insert the wires including the ground wire
into the conduit and secure them with lock nut onto the conduit mounting
plate.
3. Match wire colors with terminal numbers on indoor and outdoor unit’s
terminal blocks and firmly screw wires to the corresponding terminals.
4. Connect the ground wires to the corresponding terminals.
5. Pull the wires and check that the wires are securely fixed to the terminal
block.
DO NOT MIX UP LIVE AND NULL WIRES This is dangerous, and can cause the air
conditioning unit to malfunction.
Terminal block Wire cover
Screw Cable clamp
Conduit
16
5 Wrap piping & Cables
NOTE
Before passing the piping, and drain hose and the signal cable through the
wall hole, you must bundle them together to save space, protect them, and
insulate them.
Indoor Unit
Signal wire
Drain hose
Vinyl tape Pipe (narrow)
Wrap with insulation tape
Space behind unit
Step 1
Bundle the drain hose, refrigerant pipes, and signal cable as shown in the
figure(Not applicable for some locations in North America ).
Refrigerant piping Insulation tape
Step 2
Using adhesive vinyl tape, attach the drain hose to the underside of the refrigerant pipes.
Step 3
Using insulation tape, wrap the refrigerant pipes, signal wire and drain hose
tightly together. Double-check that all items are bundled.
Drain hose
Do not intertwine signal calbe with other wires
While bundling these items together,do not intertwine or cross the signal
cable with any other wiring.
DRAIN HOSE MUST BE ON BOTTOM
Make sure that the drain hose is at the bottom of the bundle. Putting the
drain hose at the top of the bundle can cause the drain pan to overflow, which
can lead to fire or water damage.
DO NOT WRAP ENDS OF PIPING
When wrapping the bundle, keep the ends of the piping unwrapped. You need to
access them to test for leaks at the end of the installation process (refer to
Electrical Checks and Leak Checks section of this manual).
16
6 Mount indoor unit
Hook it
Connecting cable
Drain hose
Put pipes in wall hole
Hook it and press down lightly to secure
Check that the unit is firmly mounted
If you installed new connective piping to the outdoor unit, do the following: If you have already passed the refrigerant piping through the hole in the wall, proceed to Step 4. Otherwise, double-check that the ends of the refrigerant pipes are sealed to prevent dirt or foreign materials from entering the pipes. Slowly pass the wrapped bundle of refrigerant pipes, drain hose, and signal wire through the hole in the wall. Hook the top of the indoor unit on the upper hook of the mounting plate. Check that unit is hooked firmly on mounting by applying slight pressure to the left and right-hand sides of the unit. The unit should not jiggle or shift. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate. Again, check that the unit is firmly mounted by applying slight pressure to the left and the right-hand sides of the unit.
17
Wedge 30°
If refrigerant piping is already embedded in the wall, do the following:
Hook the top of the indoor unit on the upper hook of the mounting plate. Use a
bracket or wedge to prop up the unit, giving you enough room to connect the
refrigerant piping, signal cable, and drain hose.
Connect drain hose and refrigerant piping (refer to Refrigerant Piping
Connection section of this manual for instructions). Keep pipe connection
point exposed to perform the leak test (refer to Electrical Checks and Leak
Checks section of this manual).
After the leak test, wrap the connection point with insulation tape. Remove
the bracket or wedge that is propping up the unit.
Using even pressure, push down on the bottom half of the unit. Keep pushing
down until the unit snaps onto the hooks along the bottom of the mounting
plate.
NOTE : UNIT IS ADJUSTABLE
Keep in mind that the hooks on the mounting plate are smaller than the holes
on the back of the unit. If you find that you don’t have ample room to connect
embedded pipes to the indoor unit, the unit can be adjusted left or right by
about 30-50mm (1.18-1.96in), depending on the model.
30-50mm 1-3/16~2in
30-50mm 1-3/16~2in
Move to left or right
CAUTION
For the units adopt the following pipe connectors, please strictly perform the
piping work in accordance with the following instructions.
Connector A
Connector B
Cross-shape part
Red point protruding
Before performing the refrigerant piping connection, always wear work gloves and goggles, and remember that the connectors A and B are not allowed to face people directly. Keep pressing the cross-shape part of connector B with a tool for about 5~10 seconds until the red protuding point of connector A retracts completely. Remove connectors A and B, then perform the refrigerant piping connection between indoor unit and outdoor unit.
18
Install Your Outdoor Unit
INSTALLATION
Select installation location
NOTE : PRIOR TO INSTALLATION
Before installing the outdoor unit, you must choose an appropriate location.
The following are standards that will help you choose an appropriate location
for the unit.
Proper installation locations meet the following standards:
60cm24″ above
30cm12″ on left
30cm12″ from back wall
Good air circulation Firm and solid–the
Noise from the unit
and ventilation.
location can support the will not disturb other
unit and will not vibrate. people.
200cm79″ in front
60cm24″ on right
Long-term
Meets all spatial requirements shown in Installation Protected from prolonged periods Where snowfall is anticipated, take
Space Requirements above.
of direct sunlight or rain.
appropriate measures to prevent
ice buildup and coil damage.
NOTE
Install the unit by following local codes and regulations , there may be differ slightly between different regions.
CAUTION:
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind:
Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds. See Figures below.
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow
around the unit.
If the unit is frequently exposed to salty air(seaside):
Use outdoor unit that is specially designed to resist corrosion.
Strong wind
Wind Baffle
Shelter
Strong wind
90° angle to the direction of the wind
Strong wind
Build a wind Baffle to protect the unit
Build a shelter to protect the unit
DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets
Near a public street, crowded areas, or where noise from the unit will disturb
others.
Near animals or plants that will be harmed by hot air discharge.
Near any source of combustible gas.
19
In a location that is exposed to large amounts of dust
In a location exposed to a excessive amounts of salty air.
2 Install drain joint(Heat pump unit only)
NOTE : PRIOR TO INSTALLATION
Before bolting the outdoor unit in place, you must install the drain joint at
the bottom of the unit. For the units with base pan built-in with multiple
holes for proper draining during defrost, the drain joint is no need to be
installed.
Step 1 Find out the base pan hole of outdoor unit.
Seal
Base pan hole of outdoor unit
Step 2 Fit the rubber seal on the end of the drain joint that will connect to
the outdoor unit. Insert the drain joint into the hole in the base pan of the
unit. The drain joint will click in place. Connect a drain hose extension (not
included) to the drain joint to redirect water from the unit during heating
mode.
NOTE : IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to
ensure swift water drainage. If water drains too slowly, it can freeze in the
hose and flood the unit.
20
3 Anchor Outdoor Unit
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIME.
The outdoor unit can be anchored to the ground or to a wall-mounted bracket
with bolt(M10). Prepare the installation base of the unit according to the
dimensions below.
The following is a list of different outdoor unit sizes and the distance
between their mounting feet. Prepare the installation base of the unit
according to the dimensions below.
A Air inlet
Air inlet
H
D B
Air outlet
Top view
Outdoor Unit Dimensions (mm) W x H x D
680x542x248 (26.8″x 21.3″x 9.8″) 720x495x270 (28.3″x 19.5″x 10.6″) 765x555x303
(30.1″x 21.8″x 11.9″) 805x554x330 (31.7″x 21.8″x 12.9″) 890x673x342 (35.0″x
26.5″x 13.5″) 946x810x420 (37.2″x 31.9″x 16.5″) 946x810x410 (37.2″x 31.9″x
16.1″)
W
Front view
Mounting Dimensions
Distance A (mm)
452 (17.8″) 452 (17.8″) 452 (17.8″) 511 (20.1″) 663 (26.1″) 673 (26.5″) 673
(26.5″)
Distance B (mm)
230 (9.1″) 255 (10.0″) 286(11.3″) 317 (12.5″) 354 (13.9″) 403 (15.9″) 403
(15.9″)
If you will install the unit on the
ground or on a concrete mounting
platform, do the following
Mark the positions for four expansion bolts based on dimensions chart. Pre-
drill holes for expansion bolts. Place a nut on the end of each expansion
bolt. Hammer expansion bolts into the pre-drilled holes. Remove the nuts from
expansion bolts, and place outdoor unit on bolts. Put washer on each expansion
bolt, the replace the nuts. Using a wrench, tighten each nut until snug.
If you will install the unit on a wall-mounted
bracket , do the following:
Mark the position of bracket holes based on dimensions chart. Pre-drill the
holes for the expansion bolts. Place a washer and nut on the end of each
expansion bolt. Thread expansion bolts through holes in mounting brackets, put
mounting brackets in position, and hammer expansion bolts into the wall. Check
that the mounting brackets are level. Carefully lift unit and place its
mounting feet on brackets. Bolt the unit firmly to the brackets. If allowed,
install the unit with rubber gaskets to reduce vibrations and noise.
CAUTION
Make sure that the wall is made of solid brick, concrete, or of similarly
strong material. The wall must be able to support at least four times the
weight of the unit.
21
4 Connect signal and power cables
WARNING – Before the Operation
ALL WIRING WORK MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING
DIAGRAM LOCATED INSIDE OF WIRE COVER OF THE OUTDOOR UNIT. BEFORE PERFORMING
ANY ELECTRICAL OR WIRING WORK,TURN OFF THE MAIN POWER TO THE SYSTEM.
Prepare the cable for connection
Please choose the right cable according to the “Cable types” in page 24.
Using wire strippers, strip the rubber jacket from both ends of cable to
reveal about 40mm (1.57in) of the wires inside. Strip the insulation from the
ends of the wires. Using a wire crimper, crimp u-lugs on the ends of the
wires.
Choose the right cable size
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit.
Pay attention to live wire
While crimping wires, make sure you clearly distinguish the Live (“L”) Wire
from other wires.
The outside unit’s terminal block is protected by an electrical wiring cover
on the side of the unit. A comprehensive wiring diagram is printed on the
inside of the wiring cover.
Unscrew the electrical wiring cover and remove it. Unscrew the cable clamp
below the terminal block and place it to the side. Connect the wire according
to the wiring diagram, and firmly screw the u-lug of each wire to its
corresponding terminal. After checking to make sure every connection is
secure, loop the wires around to prevent rain water from flowing into the
terminal. Using the cable clamp, fasten the cable to the unit. Screw the cable
clamp down tightly. Insulate unused wires with PVC electrical tape. Arrange
them so that they do not touch any electrical or metal parts. Replace the wire
cover on the side of the unit, and screw it in place.
NOTE: If the cable clamp looks like the following, please select the
appropriate through-hole according to the diameter of the wire.
Cover Screw
Buckle Three size hole: Small, Large, Medium
When the calbe is not fasten enough, use the buckle to prop it up , so it can
be clamped tightly.
22
In North America
The outside unit’s terminal block is protected by an electrical wiring cover
on the side of the unit. A comprehensive wiring diagram is sticked on the
inside of the wiring cover.
Remove the wire cover from the unit by loosening the 3 screws. Dismount caps
on the conduit panel. Temperarily mount the conduit tubes(not included) on the
conduit panel. Properly connect both the power supply and low voltage lines to
the corresponding terminals on the terminal block. Ground the unit in
accordance with local codes. Be sure to size each wire allowing several inches
longer than the required length for wiring. Use lock nuts to secure the
conduit tubes.
NOTE: Please choose the right cable size according to the Minimum Circuit
Ampacity indicated on the nameplate of the unit.
Terminal block
(O40vmerm1-)9/16″
G
Wire Cover
Connecting cable Power supply cord
Conduit panel
Please select the appropriate through-hole according to the diameter of the wire.
How to properly connect the wire lines.
Strip 25mm(15/16″) Strip 10mm(3/8″)
Loop
Insulation Solid wire
Round terminal
Strand wire
Wire
Screw with special washer Round terminal Terminal plate
Wire
Screw with special washer Round terminal
Step 1 The treatment about the end of the wire.
Wall receptacle or Air break switch(North America)
(purchased seperately)
Outdoor unit power wires
Indoor & Outdoor connective wires
(purchased seperately)
Step 2
connecting the line to the corresponding terminals on the terminal block.
Indoor unit power wires
Wall receptacle or
Air break switch
(North America) (purchased seperately)
Outdoor unit
Indoor unit
(A)
Outdoor unit
Indoor unit
Indoor & Outdoor connective wires (purchased seperately)
(B)
24
Refrigerant Piping Connection
1
Piping Connection Precautions
WARNING
WHEN CONNECTING REFRIGERANT PIPING, DO NOT LET SUBSTANCES OR GASES OTHER THAN
THE SPECIFIED REFRIGERANT ENTER THE UNIT. THE PRESENCE OF OTHER GASES OR
SUBSTANCES WILL LOWER THE UNIT’S CAPACITY, AND CAN CAUSE ABNORMALLY HIGH
PRESSURE IN THE REFRIGERATION CYCLE. THIS CAN CAUSE EXPLOSION AND INJURY.
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy
efficiency of the unit. Nominal efficiency is tested on units with a pipe
length of 5 meters (16.5ft). A minimum pipe run of 3 metres is required to
minimise vibration & excessive noise. Connection Instructions Refrigerant
Piping.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model R410A,R32 Inverter Split Air Conditioner
R22 Fixed-speed Split Air Conditioner
R410A, R32 Fixed-speed Split Air Conditioner
Capacity (BTU/h)
< 15,000
15,000 and < 24,000 24,000 and < 36,000 36,000 and < 60,000
< 18,000
18,000 and < 21,000 21,000 and < 35,000 35,000 and < 41,000
< 18,000
18,000 and < 36,000 36,000 and < 60,000
Max. Length (m)
25 (82ft) 30 (98.5ft) 50 (164ft) 65 (213ft) 10 (33ft) 15 (49ft) 20 (66ft) 25
(82ft) 20 (66ft) 25 (82ft) 30 (98.5ft)
Max. Drop Height (m)
10 (33ft) 20 (66ft) 25 (82ft) 30 (98.5ft) 5 (16ft) 8(26ft) 10(33ft) 10 (33ft)
8(26ft) 10(33ft) 15 (49ft)
Connection Instructions Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them
properly. This will ensure efficient operation and minimize the need for
future maintenance.
Measure the distance between the indoor and outdoor units. Using a pipe
cutter, cut the pipe a little longer than the measured distance. Make sure
that the pipe is cut at a perfect 90° angle.
90°
Oblique Rough Warped
DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This
will drastically reduce the heating efficiency of the unit.
23
CAUTION
MUST BE CHECK OVER THE END OF THE PIPE FOR CRACKS AND EVEN FLARING. ENSURE THE
PIPE IS SEALED.
Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They
must be completely removed.
Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
Using a reamer or deburring tool, remove all burrs from the cut section of the
pipe.
Pipe Reamer
Point down
Remove PVC tape from ends of pipe when ready to perform flaring work. Clamp
flare form on the end of the pipe. The end of the pipe must extend beyond the
edge of the flare form in accordance with the dimensions shown in the table
below.
Handle
Bar Yoke
Cone
Clamp handle
Red arrow mark
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
After removing burrs from cut pipe, seal the ends with PVC tape to prevent
foreign materials from entering the pipe. Sheath the pipe with insulating
material. Place flare nuts on both ends of pipe. Make sure they are facing in
the right direction, because you can’t put them on or change their direction
after flaring.
Flare nut
Copper pipe
PIPING EXTENSION BEYOND FLARE FORM
Outer Diameter of Pipe (mm)
Ø 6.35 (Ø 1/4″) Ø 9.52 ( Ø 3/8″) Ø12.7 ( Ø 1/2″) Ø 16 ( Ø 5/8″) Ø 19 ( Ø 3/4″)
A (mm)
Min.
MMaaxx..
0.7 (0.0275″) 1.3 (0.05″)
1.0 (0.04″)
1.6 (0.063″)
1.0 (0.04″)
1.8 (0.07″)
2.0 (0.078″)
2.2 (0.086″)
2.0 (0.078″)
2.4 (0.094″)
Flare form
A
Pipe
Place flaring tool onto the form. Turn the handle of the flaring tool
clockwise until the pipe is fully flared. Remove the flaring tool and flare
form, then inspect the end of the pipe for cracks and even flaring.
24
2 Refer to Torque Requirement to connect pipes
CAUTION
WHEN CONNECTING REFRIGERANT PIPES, BE CAREFUL NOT TO USE EXCESSIVE TORQUE OR
TO DEFORM THE PIPING IN ANY WAY. YOU SHOULD FIRST CONNECT THE LOW-PRESSURE
PIPE, THEN THE HIGH-PRESSURE PIPE.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, the minimum bending radius is 10cm.
Radius
10cm (4″)
Instructions for Connecting Piping to Indoor Unit
Step 1
Align the center of the two pipes that you will connect.
Step 2
Tighten the flare nut as tightly as possible by hand. Using a spanner, grip
the nut on the unit tubing. While firmly gripping the nut on the unit tubing,
use a torque wrench to tighten the flare nut according to the torque values in
the Torque Requirements table below. Loosen the flaring nut slightly, then
tighten again.
Indoor unit tubing
Flare nut Pipe
Torque wrench
Indoor unit tubing
Spanner (fixed) Flare nut
Connection pipe
TORQUE REQUIREMENTS
Outer Diameter of Pipe(mm) Tightening Torque(N·m) Flare dimension(B)(mm)
Ø 6.35 (Ø 1/4″) Ø 9.52 (Ø 3/8″) Ø 12.7 ( Ø 1/2″)
18~20(180~200kgf.cm) 32~39(320~390kgf.cm) 49~59(490~590kgf.cm)
8.4~8.7 (0.33~0.34″) 13.2~13.5 (0.52~0.53″) 16.2~16.5 (0.64~0.65″)
Ø 16 ( Ø 5/8″) Ø 19 (Ø 3/4″)
57~71(570~710kgf.cm) 67~101(670~1010kgf.cm)
19.2~19.7 (0.76~0.78″) 23.2~23.7 (0.91~0.93″)
Flare shape
90°+_ 4 B 45 °+_2 R0.4~0. 8
DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must
not exceed torque requirements shown in the table above.
25
3 Connecting Piping to Outdoor Unit
NOTE
This section still needs to be operated according to the TORQUE REQUIREMENTS
chart on the previous page.
Unscrew the cover Valve cover
Outdoor unit
Liquid side piping (Smaller diameter)
(Bigger
Torque wrench
Step 1 Unscrew the cover from the packed valve on the side of the outdoor
unit.
Step 2 Remove protective caps from ends of valves. Align flared pipe end with
each valve, and tighten the flare nut as tightly as possible by hand. Using a
spanner, grip the body of the valve. Do not grip the nut that seals the
service valve.
USE SPANNER TO GRIP MAIN BODY OF VALVE Torque from tightening the flare nut
can snap off other parts of valve.
Connect all pipes
Step 3
While firmly gripping the body of the valve, use a torque wrench to tighten
the flare nut according to the correct torque values. Loosen the flaring nut
slightly, then tighten again. Repeat Steps 1 to 3 for the remaining pipe.
26
Air Evacuation
NOTE : PREPARATIONS AND PRECAUTIONS
Air and foreign matter in the refrigerant circuit can cause abnormal rises in
pressure, which can damage the air conditioner, reduce its efficiency, and
cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant
circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is
relocated.
BEFORE PERFORMING EVACUATION Make sure the connective pipes between the indoor
and outdoor units are connected properly. Check to make sure all wiring is
connected properly.
Evacuation Instructions
Indoor unit
Outdoor unit
Manifold valve
-76cmHg
Compound gauge
Pressure gauge
Low pressure
valve Pressure hose
or Charge hose
High pressure valve Charge hose
Low pressure valve
Step 1
Connect the charge hose of the manifold gauge to service port on the outdoor
unit’s low pressure valve. Connect another charge hose from the manifold gauge
to the vacuum pump. Open the Low Pressure side of the manifold gauge. Keep the
High Pressure side closed. Turn on the vacuum pump to evacuate the system. Run
the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG
(-10 Pa). Close the Low Pressure side of the manifold gauge, and turn off the
vacuum pump. Wait for 5 minutes, then check that there has been no change in
system pressure.
Vacuum pump
27
Flare nut
valve body
valve stem
Step 2
If there is a change in system pressure, refer to Gas Leak
Check section for information on how to check for leaks.
If there is no change in system pressure, unscrew the cap
from the packed valve (high pressure valve).
Insert hexagonal wrench into the packed valve(high
pressure valve) and open the valve by turning the wrench
in a 1/4 counterclockwise turn. Listen for gas to exit the
system, then close the valve after 5 seconds.
Watch the Pressure Gauge for one minute to make sure
Cap
that there is no change in pressure. The Pressure Gauge
should read slightly higher than atmospheric pressure.
Remove the charge hose from the service port.
Using hexagonal wrench, fully open both the high
pressure and low pressure valves.
Tighten valve caps on all three valves (service port, high
pressure, low pressure) by hand. You may tighten it
further using a torque wrench if needed.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the
stopper. Do not try to force the valve to open further.
NOTE ON ADDING REFRIGERANT
Some systems require additional charging depending on pipe lengths. The
standard pipe length varies according to local regulations. For example, in
North America, the standard pipe length is 7.5m (25′). In other areas, the
standard pipe length is 5m (16`). The refrigerant should be charged from the
service port on the outdoor unit’s low pressure valve. The additional
refrigerant to be charged can be calculated using the following formula:
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe Air Purging
Length (m)
Method
< Standard pipe length Vacuum Pump
Additional Refrigerant
N/A
Standard pipe length
Vacuum Pump
Liquid Side: Ø 6.35 (1/4″)
Liquid Side: Ø 9.52 (3/8″)
R410A: (Pipe length standard length) x 15g/m
R410A: (Pipe length standard length) x 30g/m
(Pipe length standard length) x 0.16oZ/ft R32:
(Pipe length standard length) x 12g/m
(Pipe length standard length) x 0.32oZ/ft R32:
(Pipe length standard length) x 24g/m
(Pipe length standard length) x 0.13oZ/ft (Pipe length standard length) x 0.26oZ/ft
R22: (Pipe length standard length) x 20g/m
(Pipe length standard length) x 0.21oZ/ft
R22: (Pipe length standard length) x 40g/m
(Pipe length standard length) x 0.42oZ/ft
DO NOT MIX REFRIGERANT TYPES.
28
Electrical And Gas Leak Checks
WARNING – RISK OF ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL CODES, AND MUST BE
INSTALLED BY A LICENSED ELECTRICIAN.
BEFORE TEST RUN
Only perform test run after you have completed the following steps: ·
Electrical Safety Checks Confirm that the unit’s electrical system is safe
and operating properly · Gas Leak Checks Check all flare nut connections and
confirm that the system is not leaking · Confirm that gas and liquid (high and
low pressure) valves are fully open
Electrical Safety Checks
After installation, confirm that all electrical wiring is installed in
accordance with local and national regulations, and according to the
Installation Manual.
BEFORE TEST RUN
Check Grounding Work Measure grounding resistance by visual detection and with
grounding resistance tester.
DURING TEST RUN
Check for Electrical Leakage During the Test Run, use an electroprobe and
multimeter to perform a comprehensive electrical leakage test. If electrical
leakage is detected, turn off the unit immediately and call a licensed
electrician to find and resolve the cause of the leakage. Note: This may not
be required for some locations in North America.
Gas Leak Checks
There are two different methods to check for gas leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe
connection points on the indoor unit and outdoor unit. The presence of bubbles
indicates a leak.
Leak Detector Method
If using leak detector, refer to the device’s operation manual for proper
usage instructions.
Check-point of outdoor unit
Check-point of indoor unit
D
B
C
A
A: Low pressure stop valve B: High pressure stop valve C& D: Indoor unit flare
nuts
AFTER PERFORMING GAS LEAK CHECKS After confirming that the all pipe connection
points DO NOT leak, replace the valve cover on the outside unit.
29
Test Run
Test Run Instructions
You should perform the Test Run for at least 30 minutes.
Connect power to the unit.
Press the ON/OFF button on the remote controller to turn it on.
Press the MODE button to scroll through the following functions, one at a
time:
· COOLSelect lowest possible temperature
· HEATSelect highest possible temperature
Let each function run for 5 minutes, and perform the following checks:
List of Checks to Perform
No electrical leakage
PASS/FAIL
Unit is properly grounded
All electrical terminals properly covered
Indoor and outdoor units are solidly installed
All pipe connection points do not leak
Outdoor (2):
Indoor (2):
Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function properly
Unit performs HEAT function properly
Indoor unit louvers rotate properly
Indoor unit responds to remote controller
DOUBLE-CHECK PIPE CONNECTIONS
During operation, the pressure of the refrigerant circuit will increase. This
may reveal leaks that were not present during your initial leak check. Take
time during the Test Run to double-check that all refrigerant pipe connection
points do not have leaks. Refer to Gas Leak Check section for instructions.
After the Test Run is successfully completed, and you confirm that all checks
points in List of Checks to Perform have PASSED, do the following: a. Using
remote control, return unit to
normal operating temperature. b. Using insulation tape, wrap the indoor
refrigerant pipe connections that you left uncovered during the indoor unit
installation process.
IF AMBIENT TEMPERATURE IS BELOW 16°C(60°F) You can’t use the remote controller
to turn on the COOL function when the ambient temperature is below 16°C/62°F.
In this instance, you can use the MANUAL CONTROL button to test the COOL
function.
Lift the front panel of the indoor unit, and raise it until it clicks in
place. The MANUAL CONTROL button is located on the right-hand side of the
unit. Press it 2 times to select the COOL function. Perform Test Run as
normal.
Manual control button
30
Packing And Unpacking The Unit
Instructions for packing and unpacking the unit:
Unpacking: Indoor unit:
1. Cut the sealing tape on the carton with a knife, one cut on the left, one
cut in the middle and one cut on the right.
2.Use the vice to take out the sealing nails on the top of the carton. 3.Open
the carton. 4.Take out the middle support plate if it is included. 5.Take out
the accessory package, and take out the connecting wire if it is included.
6.Lift the machine out of the carton and lay it flat. 7.Remove the left and
right package foam or the upper and lower packaging foam, untie the
packaging bag.
Outdoor Unit
1.Cut the packing belt. 2.Take the unit out of the carton. 3.Remove the foam
from the unit. 4.Remove the packaging bag from the unit.
Packing: Indoor unit:
1.Put the indoor unit into the packing bag. 2.Attach the left and right
package foam or the upper and lower packaging foam to the unit. 3.Put the unit
into the carton, then put accessory package in. 4.Close the carton and seal it
with the tape. 5.Using the packing belt if necessary.
Outdoor unit:
1.Put the outdoor unit into the packing bag. 2.Put the bottom foam into the
box. 3.Put the unit into the carton, then put the upper packaging foam on the
unit. 4.Close the carton and seal it with the tape. 5.Using the packing belt
if necessary.
NOTE: Please keep all packaging items if you may need in the future.
31
OPERATION INSTRUCTIONS
NOTE
Different models have different front panel and display window. Not all the
indicators describing below are available for the air conditioner you
purchased. Please check the indoor display window of the unit you purchased.
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
Indoor Unit Display
Front Panel
Display window
Air Outlet
Functional Filter
(On Back of Main FilterSome Units)
Display window
Air Filter
Remote Control Remote Control Holder
(purchase separately)
Display Code
for 3s when for 3s when
Display Code Meanings Displays temperature, operation feature and Error codes.
When Wireless Control feature is activated.
When Air magic or UV lamp(if any) feature is activated.
When ECO feature is activated.
TIMER ON is set (if the unit is OFF, ”
” remains on when TIMER ON is set ).
UV lamp, Fresh, Brezzeless, SWING, TURBO, or SILENCE features is turned on.
TIMER OFF is set. UV lamp, Fresh, Brezzeless, SWING, TURBO, or SILENCE features is turned off.
When defrosting(cooling & heating units). When active clean function is turned on. When 8°C(46°F) heating mode is turned on.
32
Operating Temperature
When your air conditioner is used outside of the following temperature ranges,
certain safety protection features may activate and cause the unit to disable.
Inverter Split Type
Room Temp.
COOL Mode
16°C~32°C(60°F~90°F)
HEAT Mode
0°C~30°C(32°F~86°F)
DRY Mode
10°C~32°C(50°F~90°F)
Outdoor Temp.
0°C~50°C(32°F~122°F)
-15°C~50°C(5°F~122°F)
For models withlow temp. cooling systems.
-15°C~24°C(5°F~75°F)
0°C~50°C(32°F~122°F)
-15°C~50°C(5°F~122°F)
For special tropical models
-15°C~24°C(5°F~75°F)
0°C~52°C(32°F~126°F)
For special tropical models
FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER
When outside temperature is below 0°C (32°F ), we strongly recommend keeping
the unit plugged in at all time to ensure smooth ongoing performance.
Fixed-speed Type
COOL Mode
Room Temp.
16°C~32°C (60°F~90°F)
HEAT Mode
0°C~30°C (32°F~86°F)
Outdoor Temp.
18°C~43°C (64°F~109°F)
-7°C~43°C (19°F~109°F)
For models with low-temp cooling systems
-7°C~24°C(19°F~75°F)
DRY Mode
10°C~32°C(50°F~90°F) 11°C~43°C (52°F~109°F) 18°C~43°C (64°F~109°F)
18°C~52°C (64°F~126°F)
For special tropical models
-15°C~24°C(5°F~75°F)
18°C~52°C (64°F~126°F)
For special tropical models
NOTE: Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
33
To further optimize the performance of your unit, do the following:
Keep doors and windows closed. Limit energy usage by using TIMER ON and TIMER
OFF functions. Do not block air inlets or outlets. Regularly inspect and clean
air filters.
More features
Auto-Restart If the unit loses power, it will automatically restart with the
prior settings once power has been restored.
Anti-mildew(some units) When turning off the unit from COOL, AUTO (COOL), or
DRY modes, the air conditioner will continue operate at very low power to dry
up condensed water and prevent mildew growth.
Wireless Control (Model dependent)
Wireless control allows you to control your air conditioner using your mobile
phone and a wireless connection. For the USB device access, replacement,
maintenance operations must be carried out by professional staff.
· Active Clean function(some units)
— The Active Clean Technology washes away dust when it adheres to the heat
exchanger by automatically freezing and then rapidly thawing the frost. A “pi-
pi” sound will be heard. The Active clean operation is used to produce more
condensed water to improve the cleaning effect, and the cold air will blow
out. After cleaning, the internal wind wheel then keeps operating with hot air
to blow-dry the evaporator, thus keeping the inside clean.
— When this function is turned on, the indoor unit display window appears “CL
” , after 20 to 130 minutes, the unit will turn off automatically and cancel
Active Clean function.
— For some units, the system will start hightemperature cleaning process, and
the temperature of air outlet is very high. Please keep away from it. And this
would lead to the rising of the room temperature .
Louver Angle Memory
When turning on your unit, the louver will automatically resume its former
angle.
Air Magic+ function(some units)
Under the effect of electric field generated by outer double-tube emitter,
millions of negative Ions are formed as Super Negative Ion Shockwave to
eradicate bacteria and viruses in wider extent.
Coolflash function Cool Flash technology can drive your whole room to the
instant cool. With large air volume and long airflow, the temperature of the
whole room can be reduced in a short time.
Heatflash function With fast and strong heating airflow, the Heat Flash
technology can warm up your whole room in a short time.
Refrigerant Leakage Detection
The indoor unit will automatically display “EL0C” when it detects refrigerant
leakage.
UV-C lamp function(some units)
When the UV lamp function is initiated, the UV lamp emit UV-C radiation to
help to purify the air inside.
Breezeless function – The revolutionary double deflectors can
bend, veer and soften the airflow to provide multiple levels of softness as
you demand. – Enjoy the cozy coolness with breeze billowing away from you,
with mild breeze, or eventually without a noticeable breeze. – The deflector
consist of thousands of mini-holes can transform the strong airflow into
thousands of tiny strings of air that gives you softest touch of cooling.
34
Breezeless Operation
The air conditioner will adjust the louver angle and fan speed automatically
on the basis of room temperature and humidity variable. There are four
different operation state, See Fig. 1, Fig. 2, Fig. 3, Fig. 4 .
Breeze billowing away
Mild breeze
Fig. 1 Breezeless
Fig. 2 Breezeless
Sleep Operation
The SLEEP function is used to decrease energy use while you sleep (and don’t
need the same temperature settings to stay comfortable).
Press the SLEEP button on remote control when in COOL mode, the unit will
increase the temperature by 1°C (2°F) after 1 hour, and will increase an
additional 1°C (2°F) after another hour. When in HEAT mode, the unit will
decrease the temperature by 1°C (2°F) after 1 hour, and will decrease an
additional 1°C (2°F) after another hour.
The sleep feature will stop after 8 hours and the system will keep running
with final situation.
SLEEP Operation
Cool mode(+1 C/2 F) per hour for the first two hours
Set
temperature
1hr
1hr
Keep running
Heat mode( -1 C/2 F) per hour for the first two hours
Fig. 3
Fig. 4
NOTE: For the rooms with large heat load or the outdoor temperature is too high, you’d better not choose breezeless operation, this may result in uncomfortable feeling.
Saving energy during sleep
Setting Angle of Air Flow
NOTE : Setting angle of air flow(Remote control)
While the unit is on, use the SWING button on remote control to set the
direction (vertical/horizontal angle) of airflow. Please refer to the Remote
Control operation for details.
NOTE ON LOUVER ANGLES
Do not set louver at too vertical an angle for long periods of time When using COOL or DRY mode. It would be condense the water on the louver blade, which will drop on your floor or furnishings.
Setting the louver at too small an angle when using COOL or HEAT mode, can reduce the performance of the AC due to restricted air flow.
35
According to the relative standards requirement, please sets the vertical air flow louver to its maximum angle under heating capacity test.
Heating Capacity
Test
NOTE
Do not move louver by hand. This will cause the louver to become out of sync.
If this occurs, turn off the unit and unplug it for a few seconds, then
restart the unit. This will reset the louver.
CAUTION
Do not put your fingers in or near the blower and suction side of the unit.
The high-speed fan inside the unit may cause injury.
Manual Operation(without remote)
CAUTION : For product use
The manual button is intended for testing purposes and emergency operation
only. Please do not use this function unless the remote control is lost and it
is absolutely necessary. To restore regular operation, use the remote control
to activate the unit. Unit must be turned off before manua operation.
To operate your unit manually:
Open the front panel of the indoor unit. Locate the MANUAL CONTROL button on
the right-hand side of the unit. Press the MANUAL CONTROL button one time to
activate FORCED AUTO mode. Press the MANUAL CONTROL button again to activate
FORCED COOLING mode. Press the MANUAL CONTROL button a third time to turn the
unit off. Close the front panel.
Manual control button
36
Remote Control Operation
Quick Start Guide
1 FIT BATTERIES
6 PRESS POWER BUTTON
2 SELECT MODE
AUTO COOL DRY HEAT FAN
3 SELECT TEMPERATURE
5 POINT REMOTE TOWARD UNIT
4 SELECT FAN SPEED
AU-100%
NOT SURE WHAT A FUNCTION DOES? Refer to the How to Use Basic Functions and How
to Use Advanced Functions sections of this manual for a detailed description
of how to use your air conditioner.
SPECIAL NOTE
· Button designs on your unit may differ slightly from the example shown. · If
the indoor unit does not have a particular function, pressing that function’s
button on
the remote control will have no effect.
37
Handling the Remote Controller
Inserting and Replacing Batteries
Your air conditioning unit may come with two batteries(some units). Put the batteries in the remote control before use.
1. Slide the back cover from the remote control
downward, exposing the battery compartment. Insert the batteries, paying attention to match
up the (+) and (-) ends of the batteries with
3. the symbols inside the battery compartment.
Slide the battery cover back into place.
BATTERY NOTES
For optimum product performance: · Do not mix old and new batteries, or
batteries of different types. · Do not leave batteries in the remote
control if you don’t plan on using the device for more than 2 months.
BATTERY DISPOSAL Do not dispose of batteries as unsorted municipal waste.
Refer to local laws for proper disposal of batteries.
NOTES FOR USING REMOTE CONTROL
The device could comply with the local national regulations. · In Canada, it
should comply with
CAN ICES-3(B)/NMB-3(B). · In USA, this device complies with part 15 of
the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful
interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation. This
equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception,which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures: · Reorient or relocate the receiving antenna. ·
Increase the separation between the equipment and receiver. · Connect the
equipment into an outlet on a circuit different from that to which the
receiver is connected. · Consult the dealer or an experienced radio/TV
technician for help. · Changes or modifications not approved by the party
responsible for compliance could void user’s authority to operate the
equipment.
TIPS FOR USING REMOTE CONTROL
· The remote control must be used within 8 meters of the unit.
· The unit will beep when remote signal is received.
· Curtains, other materials and direct sunlight can interfere with the
infrared signal receiver.
· Remove batteries if the remote will not be used more than 2 months.
38
Buttons and Functions
1
4
5
8
9
LED
12
Cool/Heat Swing
Flash
3s
Air magic
Model A
Description
No.1
ON/OFF Turn the unit on or off.
No.2
2 No.3
3
6 No.4 7
10 No.5 11 13 No.6 14
No.7
MODE Auto > Cool > Dry > Heat > Fan NOTE: HEAT mode is not supported by the
cooling only appliance.
BREEZE Breezeless > Breeze away > Breeze mild>Stop
TEMP. Increases temperature in 0.5°C (1°F) increments. Max. temperature is
30°C (86°F). (Press together & buttons at the same time for 3 seconds will
alternate the temperature display between the °C & °F).
SET Active clean>Sleep > Follow Me > AP mode > Active clean
OK Used to confirm the selected functions
TEMP. Set timer to turn unit on or off
15 No.8
TEMP. Decreases temperature in 0.5°C (1°F) increments. Min. temperature is 16°C (60°F)
No.9
FAN SPEED AU > 20% > 40% >60% > 80% > 100% Press the TEMP or button to increase/ decrease the fan speed in 1% increments.
No.10 No.11
LED LED Turns LED display & air conditioner buzzer on and off
ECO/GEAR ECO > GEAR(75%) > GEAR(50%) > Previous setting mode > ECO
No.12 No.13
Cool/Heat Flash
Cool/Heat Flash
Reduce(cool mode) or rise(heat mode) temperature in a
short time.
SWING Swing Starts and stops the horizontal louver movement. Hold 3s down for
3 seconds to initiate vertical louver auto swing
feature(some units).
No.14
Air Air magic+ magic Used to start/stop the Air magic and UV-C lamp (if any)
function.
Cool/Heat Flash
Air magic +
No.15
LOCK
Press together these two buttons simultaneously for 5 seconds to lock the
keyboard. Press together these two buttons for 2 seconds to unlock the
keyboard.
39
Buttons and Functions
1
4
5
8
9
LED
12
Cool/Heat Swing
Swing
Flash
Model B
Description
No.1
ON/OFF Turn the unit on or off.
No.2
2 No.3
3
6 No.4 7
MODE Auto > Cool > Dry > Heat > Fan
NOTE: HEAT mode is not supported by the cooling only appliance.
BREEZE Breezeless > Breeze away > Breeze mild>Stop
TEMP. Increases temperature in 0.5°C (1°F) increments. Max. temperature is
30°C (86°F). (Press together & buttons at the same time for 3 seconds will
alternate the temperature display between the °C & °F).
10 No.5 11
13 14
No.6
SET Active clean > Sleep > Follow Me > AP mode > Active clean []: Model
dependent
OK Used to confirm the selected functions
No.7
TEMP. Set timer to turn unit on or off
15 No.8
TEMP. Decreases temperature in 0.5°C (1°F) increments. Min. temperature is 16°C (60°F)
No.9
FAN SPEED AU > 20% >40% >60% > 80% > 100% Press the TEMP or button to increase/ decrease the fan speed in 1% increments.
No.10 No.11 No.12
No.13
LED LED Turns LED display & air conditioner buzzer on and off
ECO/GEAR
ECO > GEAR(75%) > GEAR(50%) > Previous setting mode > ECO
Cool/Heat Flash
Cool/Heat Flash
Reduce(cool mode) or rise(heat mode) temperature in a
short time.
SWING(up and down) Swing Starts and stops the horizontal louver movement. Hold
down for 2 seconds to initiate horizontal louver auto swing
feature(some units).
SWING(left and right) No.14 Swing Starts and stops the vertical louver movement.
Cool/Heat Flash
Swing
No.15
LOCK
Press together these two buttons simultaneously for 5 seconds to lock the
keyboard. Press together these two buttons for 2 seconds to unlock the
keyboard.
40
Buttons and Functions
1
4
5
8
9
LED
12
Cool/Heat Flash
Swing 3s
Fresh
Model C
Description
No.1
ON/OFF Turn the unit on or off.
No.2
2 No.3
3
6 No.4 7
MODE Auto > Cool > Dry > Heat > Fan
NOTE: HEAT mode is not supported by the cooling only appliance.
BREEZE Breezeless > Breeze away > Breeze mild>Stop
TEMP. Increases temperature in 0.5°C (1°F) increments. Max. temperature is
30°C (86°F). (Press together & buttons at the same time for 3 seconds will
alternate the temperature display between the °C & °F).
10 No.5 11
13 14
No.6
SET Active clean >Sleep > Follow Me > AP mode> Active clean []: Model
dependent
OK Used to confirm the selected functions
No.7
TEMP. Set timer to turn unit on or off
15 No.8
TEMP. Decreases temperature in 0.5°C (1°F) increments. Min. temperature is 16°C (60°F)
No.9
FAN SPEED AU > 20% >40% > 60% > 80% > 100% Press the TEMP or button to increase/ decrease the fan speed in 1% increments.
No.10 No.11 No.12
No.13
LED LED Turns LED display & air conditioner buzzer on and off
ECO/GEAR
ECO > GEAR(75%) > GEAR(50%) > Previous setting mode > ECO
Cool/Heat Flash
Cool/Heat Flash
Reduce(cool mode) or rise(heat mode) temperature in a
short time.
SWING Swing Starts and stops the horizontal louver movement. Hold 3s down for
3 seconds to initiate vertical louver auto swing
feature(some units).
FRESH No.14 Fresh Starts and stops the UV lamp function.
Cool/Heat Flash
Fresh
No.15
LOCK
Press together these two buttons simultaneously for 5 seconds to lock the
keyboard. Press together these two buttons for 2 seconds to unlock the
keyboard.
41
Remote Screen Indicators
Information are displayed when the remote controller is power up.
Wind flow
Breeze Breeze
follow people* Away
mild
*: Not available for this unit.
Breezeless
Intelligent eye *
Low battery (If flashes)
Active clean
Not available for this unit.
Sleep mode
Follow me
*: Model dependent
MODE display Displays the current mode
Air magic+ mode *
Wireless control *
AUTO COOL DRY
HEAT
FAN
Transmission ECO GEAR Timer Indicator Feature Feature ON
Timer Lock OFF Feature
Slience Feature
Temperature/Timer/Fan speed display
Displays the set temperature by default, or fan speed or timer setting when
using TIMER ON/OFF functions.
FAN SPEED AUTO
SLIENCE
LOW
MED
HIGH
1% 2-20% 21-40% 41-60% 61-80% 81-100% NOTE: The fan speed can not be adjusted
in AUTO or DRY mode.
Not available for this unit
Horizontal louver swing
Cool/Heat Flash mode
Vertical louver auto swing Not available for this unit
NOTE 1. All indicators shown in the figure are for the purpose of clear
presentation. But during the actual
operation, only the relative function signs are shown on the display window.
42
How to Use Basic Functions
NOTE
Before operation, please ensure the unit is plugged in and power is available.
AUTO Mode Select AUTO mode
Set your desired temperature
MODE
Turn on the air conditioner
NOTE: 1. In AUTO mode, the unit will automatically select the COOL, FAN, or
HEAT function based on the set
temperature. 2. In AUTO mode, fan speed can not be set.
COOL or HEAT Mode Select COOL/HEAT mode
Set the temperature
Set the fan speed
Turn on the air conditioner
MODE
DRY Mode Select DRY mode
Set your desired temperature
MODE
Turn on the air conditioner
NOTE: In DRY mode, fan speed can not be set since it has already been automatically controlled.
FAN Mode Select FAN mode
Set the fan speed
Turn on the air conditioner
MODE
NOTE: In FAN mode, you can’t set the temperature. As a result , no temperature displays in remote screen. 43
Setting the TIMER
TIMER ON/OFF – Set the amount of time after which the unit will automatically
turn on/off.
TIMER ON setting
Press TIMER button to initiate the ON time sequence.
Press Temp. up or down button for for multiple times to set the desired time
to turn on the unit.
x5
Point remote to unit and wait 1sec, the TIMER ON will be activated.
1 sec
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMER OFF
TIMER OFF setting
Press TIMER button to initiate the OFF time sequence.
Press Temp. up or down button for for multiple times to set the desired time
to turn off the unit.
x5
Point remote to unit and wait 1sec, the TIMER OFF will be activated.
1 sec
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMER OFF
NOTE: 1. When setting the TIMER ON or TIMER OFF, the time will increase by 30
minutes increments with each
press, up to 10 hours. After 10 hours and up to 24, it will increase in 1 hour
increments. (For example, press 5 times to get 2.5h, and press 10 times to get
5h,) The timer will revert to 0.0 after 24. 2. Cancel either function by
setting its timer to 0.0h.
TIMER ON & OFF setting(example) Keep in mind that the time periods you set for both functions refer to hours after the current time.
xn
xn
1 sec
Timer starts
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMER OFF
Unit turns
ON
Unit turns
OFF
Current time 1PM
2:00PM 3:00PM 3:30PM
2.5 hours later 5 hours later
4PM
5PM
6PM
44
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMER OFF
Example: If current timer is 1:00PM, to set the timer as above steps, the unit will turn on 2.5h later (3:30PM) and turn off at 6:00PM.
How to Use Advanced Functions
Swing function Press Swing button
Swing 3s
Set airflow direction Swing 3s
3s Swing 3s
The horizontal louver will swing up and down automatically when pressing Swing button.
If continue to press the SWING button, five different airflow directions can be set. The louver can be move at a certain range each time you press the button. Press the button until the direction you prefer is reached.
Keep pressing this button more than 3 seconds, the vertical louver swing function is activated. (Model dependent)
Press Swing button Swing
Set airflow direction Swing
Swing
The horizontal louver will swing up and down automatically when pressing Swing button.
If continue to press the SWING button, five different airflow directions can be set. The louver can be move at a certain range each time you press the button. Press the button until the direction you prefer is reached.
Press this button , the vertical louver swing function is activated.
LED DISPLAY LED
5s LED
Press this button more than 5 seconds(some units)
Press this button to turn on and turn off the display on the indoor unit.
Keep pressing this button more than 5 seconds, the indoor unit will display the actual room temperature. Press more than 5 seconds again will revert back to display the setting temperature.
45
Cool/Heat Flash Function
Press this button
CoFolal/sHheat
When you press this button in COOL mode, the Cool Flash technology can drive your whole room to the instant cool. With large air volume and long airflow, the temperature of the whole room can be reduced in a short time.
When you press this button in HEAT mode, with fast and strong heating airflow, the Heat Flash technology can warm up your whole room in a short time.
ECO/GEAR function
Press this button to enter the energy efficient mode in a sequence of
following: ECO GEAR(75%) GEAR(50%) Previous setting mode ECO……
Note:This function is only available under COOL mode.
ECO operation:
Under cooling mode, press this button, the remote controller will adjust the
temperature automatically to 24OC/75OF, fan speed of Auto to save energy (only
when the set temperature is less than 24 OC/75OF). If the set temperature is
above 24 OC/75OF, press the ECO button, the fan speed will change to Auto, the
set temperature will remain unchanged.
NOTE: Pressing the ECO button, or modifying the mode or adjusting the set temperature to less than 24OC/75 OF will stop ECO operation. Under ECO operation, the set tmeperature should be 24O C/75OF or above, it may result in insufficient cooling. If you feel uncomfortable, just press the ECO button again to stop it.
GEAR operation:
Press the ECO/GEAR button to enter the GEAR operation as following: 75%(up to 75% electrial energy consumption) 50%(up to 50% electrial energy consumption) Previous setting mode.
Under GEAR operation, the display on the remote controller will alternate between electical energy consumption and set temperature.
Silence function 2s
FP function 2
Keep pressing Fan button for more than 2 seconds to activate/disable Silence
function.
Due to low frequency operation of compressor, it may result in insufficient
cooling and heating capacity. Press ON/OFF, Mode, Sleep, Boost or Clean button
while operating will cancel silence function.
Press this button 2 times during one second under HEAT Mode and setting
temperature of 16O C/60 OF to activate the FP function.
The unit will operate at high fan speed (while compressor on) with temperature
automatically set to 8OC/46OF.
46
SET function
SET
SET or
OK
Press the SET button to enter the function setting, then press SET button or
TEMP or TEMP button to select the desired function. The selected symbol will
flash on the display area, press the OK button to confirm.
To cancel the selected function, just perform the same procedures as above.
Press the SET button to scroll through operation functions as follows:
Active clean( ) Sleep( ) Follow Me( ) AP mode *( )
Active clean function The Active Clean Technology washes away dust, and mold
that may cause odors when it adheres to the heat exchanger by automatically
freezing and then rapidly thawing the frost. When this function is turned on,
the indoor unit display window appears “CL”, after 20 to 130 minutes, the unit
will turn off automatically and cancel CLEAN function.
Sleep function( ) : The SLEEP function is used to decrease energy use while
you sleep(and don’t need the same temperature settings to stay comfortable).
NOTE: The SLEEP function is not available in FAN and DRY mode.
AP function( )(some units) : Choose AP mode to do wireless network
configuration. For some units, it doesn’t work by pressing the SET button. To
enter the AP mode, continuously press the LED button seven times in 10
seconds.
Follow me function( ):
The FOLLOW ME function enables the remote control to measure the temperature
at its current location and send this signal to the air conditioner every 3
minutes interval. When using AUTO, COOL or HEAT modes, measuring ambient
temperature from the remote control(instead of from the indoor unit itself)
will enable the air conditioner to optimize the temperature around you and
ensure maximum comfort.
NOTE: Press and hold Cool/Heat Flash
button for seven seconds to start/stop
memory feature of Follow Me function. If the memory feature is activated, On,,
,, ,,
displays for 3 seconds If the memory feature
iosnsttohpepsecdre, enO. F,,
displays for 3 seconds on the screen.
While the memory feature is activated,
press the ON/OFF button, shift the mode
or power failure will not cancel the Follow
me function.
47
App Setup And Operation
Wireless control feature
Applicable system: iOS, Android
Please keep your APP up to date with the latest version. Due to special
situation may be occurred, we explicitlyclaims below: Not all of the Android
and iOS system are compatible with APP. We will not be responsible for any
issue as a result of the incompatibility.
Wireless safety strategy
Smart kit only support WPA-PSK/WPA2-PSK encryption and none encryption. WPA-
PSK/WPA2-PSK encryption is recommended.
CAUTIONS:
Due to different network situation, control process may return time-out
sometimes. If this situation occurs, the display between board and APP maynot
be the same, please do not feel confused. Smart Phone camera needs to be 5
million pixelsor above to make sure scan QR code well. Due to different
network situation, sometimes, request time-out could happen, thus, it is
necessary to do network configuration again. The APP system is subject to
update without prior notice for product function improvement. The actual
network configuration process may be slightly differentfrom the manual, the
actual process shall prevail. Please check the Service Website for more
information.
SPECIFICATION:
APP control module model: EU-SK110, US-SK110 Antenna Type: Printed PCB Antenna
Frequency Band: 2400-2483.5MHz Operation Temperature:0 C~45 C/32 F~113 F
Operation Humidity: 10%~85% Power Input: DC 5V/500mA Maximum TX Power: <20dBm
PREPARATION
Please ensure your mobile device is connected to wireless router. Also, the
wireless router has already connected to Internet before doing user
registration and network configuration. Make sure your mobile device has
already been connected to the wireless network which you want to use. Also,
you need to forget other irrelevant wireless network in case it influences
your configuration process.
Download and install app
1. Ensure the mobile phone is connected to your home network.
2. Scan the QR code or search for the MSmartHome application from the Google
Play Store or Apple App Store on a smart device.
MSmartHome
Download the app & activate product
48
Network configuration
CAUTIONS:
It is necessary to forget any other around network and make sure the Android
or iOS device just connect to the wireless network you want to configure. Make
sure the Android or iOS device wireless function works well and can be
connected back to your original wireless network automatically.
Kindly reminder: User must finish all the steps in 8 minutes after powering on
air conditioner, otherwise you need to power on it again.
NOTE:
Make sure your devices are powered on. Keep your mobile phone close enough to
your device when you are connecting network to your device. Connect your
mobile phone to the wireless network at home, and make sure you know the
password of the network. Check if your router supports 2.4 GHz wireless band
and turn it on. If you are not sure whether the router supports 2.4 GHz band,
please contact the router manufacturer. The device cannot connect to the
wireless that requires authentication, and it usually appears in public area
such as hotels, restaurants, etc. Please connect to a wireless network that
does not require authentication. It is recommended to use a wireless network
name that only contains letters and numbers. If your wireless network name
contains special characters, please modify it in the router. Turn off the
WLAN+ (Android) or WLAN Assistant (iOS) function of your mobile phone when
connecting network to your devices. In the case that your device connected to
wireless network before but it needs to reconnect, please click “+” on app
Home page, and add your device again by the device category and model
according to the instructions on app.
Register and log in
Open the MSmartHome app, and create a new account to start ( you can also
register through a third-party account). If you already had an existing
account, use the account to log in.
Login
Enter email XXXXXXXXX Enter password
Login
Login
49
Connect your devices to MSmartHome
1. Please make sure your mobile phone is connected to wireless network. If
not, go to Settings and turn on the wireless connection, select and connect to
a wireless network. Also please turn on the Bluetooth on your phone. If not,
go to Settings and turn it on.
2. Please power on your devices. 3. Open MSmartHome app on your phone. 4. If
a message of “Smart devices discovered nearby”
appears, click to add.
… Washing machine
5. If no message appears, select “+” on the page and select your device in
the list of nearby devices available. If your device is not listed, please add
your device manually by the device category [Air Conditioner] and device model
[Split AC].
6. Connect your device to APP according to the instructions on app. If the
connection fails, please follow the instructions provided by the app to
continue with the operation.
50
How to use APP
Please ensure both your mobile device and air conditioner are connected to the
Internet before using app to control the air conditioner via internet, please
follow the steps:
Login
Enter email XXXXXXXXX Enter password
Login
Login
MSmartHome
NOTE: Not all the function of the APP is available on air conditioner. For example: ECO, Boost, Swing function, please check the user manual to find more information.
1. Click “Login”
2. Choose the Air Conditioner.
3. Thus, user can control air conditioners on/off status, operation mode,
temperature, fan speed and so on.
Special functions
Including: Schedule, Sleep curve, Energy Monitor,Bill Control and Check. NOTE:
Not all the unit can use these special function on the APP. Thus, if the air
conditioner do not support the above function, the function will be hided from
the function list.
51
Schedule Weekly, user can make an appointment to turn on or off the air
conditioner on specific time. User also can choose circulation to keep the air
conditioner under schedule control every week.
Every day
Sleep
Users can customize their own comfortable sleep by setting target temperature.
Energy Monitor(Only for some units )
User can simply monitor the electricity consumption of air conditioner by
checking the chart and history record.
Bill Control(Only for some units )
User can set parameters to limit the electricity consumption over a period of
time.
Done
Check User can simply check the air conditioner running status with this
function. When finishing this procedure, it can display the normal items,
abnormal items, and detail information.
52
APP DECLARATION
Hereby, we declare that this Smart kit is in compliance with the essential
requirements and other relevant provisions of Directive 2014/53/EU. A copy of
the full DoC is attached. (European Union products only)
CAUTIONS:
Wireless module models: US-SK110,EU-SK110: FCC ID: 2ADQOMDNA23 IC: 12575A-
MDNA23 This device complies with Part 15 of the FCC Rules and it contains
licence-exempt transmitter(s)/ receiver(s) that comply with Innovation,
Science and Economic Development Canada’s licenceexempt RSS(s).
Operation is subject to the following two conditions: 1. This device may not
cause interference; and 2. This device must accept any interference, including
interference that may cause
undesired operation of the device.
Only operate the device in accordance with the instructions supplied. Changes
or modifications to this unit not expressly approved by the party responsible
for compliance could void the user’s authority to operate the equipment. This
device complies with FCC radiation exposure limits set forth for an
uncontrolled environment. In order to avoid the possibility of exceeding the
FCC radio frequency exposure limits, human proximity to the antenna shall not
be less than 20cm (8 inches) during normal operation.
NOTE: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures: -Reorient or relocate the receiving antenna.
-Increase the separation between the equipment and receiver. -Connect the
equipment into an outlet on a circuit different from that to which the
receiver
is connected. -Consult the dealer or an experienced radio/TV technician for
help.
53
CARE AND MAINTENANCE
CAUTION
· The cooling efficiency of your unit and your health would be damaged for the
glogged AC Make sure to clean the filter every two weeks.
· Always TURN OFF your AC system and disconnect its power supply before
cleaning or maintenance.
· Do not touch air freshening (Plasma) filter at least 10 minutes after
turning off the unit. · Only use a soft, dry cloth to wipe the unit clean. You
can use a cloth soaked in warm water to wipe
it clean if the unit is especially dirty. · Do not use chemicals or chemically
treated cloths to clean the unit · Do not use benzene, paint thinner,
polishing powder or other solvents to clean the unit. They can
cause the plastic surface to crack or deform. · Do not use water hotter than
40°C (104°F) to clean the front panel. This can cause the panel to
deform or become discolored.
Cleaning Your Indoor Unit, Air Filter
Step 1
Grab the clasp and lift
Lift the front panel of the indoor unit.
Filter Tabs
Step 2
Grip the tab on the end of the filter, lift it up, then pull it towards
yourself and pull the filter out.
(Front)
(Back)
1. Flip to back
2. Remove air 3. Clean it by freshening filter vacuum cleaner off (some units)
Step 3
If your filter has a small air freshening filter, unclip it from the larger
filter. Clean this air freshening filter with a hand-held vacuum.
54
Don’t forget to install me back
Step 4
Clean the large air filter with warm, soapy water. Be sure to use a mild
detergent. Rinse the filter with fresh water, then shake off excess water. Dry
it in a cool, dry place, and refrain from exposing it to direct sunlight.
Step 5
When dry, re-clip the air freshening filter to the larger filter, then slide
it back into the indoor unit. Finally, Close the front panel of the indoor
unit.
CAUTION
· Before changing the filter or cleaning, turn off the unit and disconnect its
power supply. · When removing filter, do not touch metal parts in the unit.
The sharp metal edges can cut you. · Do not use water to clean the inside of
the indoor unit. This can destroy insulation and cause
electrical shock. · Do not expose filter to direct sunlight when drying. This
can shrink the filter. · Any maintenance and cleaning of outdoor unit should
be performed by an authorized dealer
or a licensed service provider. · Any unit repairs should be performed by an
authorized dealer or a licensed service provider.
Air Filter Reminders (Optional)
Display window: “CL” Display window: “nF”
Air Filter Cleaning Reminder · After 240 hours of use, the display window on
the indoor unit will flash “CL.”
This is a reminder to clean your filter. After 15 seconds, the unit will
revert to its previous display. · To reset the reminder, press the LED button
on your remote control 4 times, or press the MANUAL CONTROL button 3 times. If
you don’t reset the reminder, the “CL” indicator will flash again when you
restart the unit.
Air Filter Replacement Reminder · After 2,880 hours of use, the display window
on the indoor unit will flash “nF.”
This is a reminder to replace your filter. After 15 seconds, the unit will
revert to its previous display. · To reset the reminder, press the LED button
on your remote control 4 times, or press the MANUAL CONTROL button 3 times. If
you don’t reset the reminder, the “nF” indicator will flash again when you
restart the unit.
Maintenance your AC.
Maintenance Long Periods of Non-Use
If you plan not to use your air conditioner for an extended period of time, do
the following:
Maintenance Pre-Season Inspection
After long periods of non-use, or before periods of frequent use, do the
following:
Clean all filters
Turn on FAN function until unit dries out completely
Check for damaged wires Clean all filters
Check for leaks
Turn off the unit and disconnect the power
Remove batteries from remote control
Make sure nothing is blocking all air inlets and outlets
Replace batteries
55
TROUBLESHOOTING
CAUTION
If any of the following conditions occurs, turn off your unit immediately! ·
The power cord is damaged or abnormally warm · You smell a burning odor · The
unit emits loud or abnormal sounds · A power fuse blows or the circuit breaker
frequently trips · Water or other objects fall into or out of the unit DO NOT
ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER
IMMEDIATELY
Common Issues
The following problems are not a malfunction and in most situations will not
require repairs.
Issue Unit does not turn on when pressing ON/OFF button
The unit changes from COOL/HEAT mode to FAN mode
Possible Causes
The Unit has a 3-minute protection feature that prevents the unit from
overloading. The unit cannot be restarted within three minutes of being turned
off.
The unit may change its setting to prevent frost from forming on the unit.
Once the temperature increases, the unit will start operating in the
previously selected mode again.
The set temperature has been reached, at which point the unit turns off the
compressor. The unit will continue operating when the temperature fluctuates
again.
The indoor unit emits white mist
Both the indoor and outdoor units emit white mist
The indoor unit makes noises
In humid regions, a large temperature difference between the room’s air and
the conditioned air can cause white mist.
When the unit restarts in HEAT mode after defrosting, white mist may be
emitted due to moisture generated from the defrosting process.
A rushing air sound may occur when the louver resets its position.
A squeaking sound may occur after running the unit in HEAT mode due to
expansion and contraction of the unit’s plastic parts.
Both the indoor unit and outdoor unit make noises
Low hissing sound during operation: This is normal and is caused by
refrigerant gas flowing through both indoor and outdoor units.
Low hissing sound when the system starts, has just stopped running, or is
defrosting: This noise is normal and is caused by the refrigerant gas stopping
or changing direction.
Squeaking sound: Normal expansion and contraction of plastic and metal parts
caused by temperature changes during operation can cause squeaking noises.
56
Issue
The outdoor unit makes noises
Dust is emitted from either the indoor or outdoor unit
Possible Causes
The unit will make different sounds based on its current operating mode.
The unit may accumulate dust during extended periods of non-use, which will be
emitted when the unit is turned on. This can be mitigated by covering the unit
during long periods of inactivity.
The unit emits a bad odor
The unit may absorb odors from the environment (such as furniture, cooking,
cigarettes, etc.) which will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.
The fan of the outdoor unit does not operate
During operation, the fan speed is controlled to optimize product operation.
Operation is erratic, unpredictable, or unit is unresponsive
Interference from cell phone towers and remote boosters may cause the unit to
malfunction.
In this case, try the following:
· Disconnect the power, then reconnect. · Press ON/OFF button on remote
control to restart operation.
NOTE: If problem persists, contact a local dealer or your nearest customer
service center. Provide them with a detailed description of the unit
malfunction as well as your model number.
CAUTION
When troubles occur, please check the following points before contacting a
repair company.
Problem
Poor Cooling Performance
Possible Causes Temperature setting may be higher than ambient room
temperature
The heat exchanger on the indoor or outdoor unit is dirty
The air filter is dirty
The air inlet or outlet of either unit is blocked
Doors and windows are open
Excessive heat is generated by sunlight
Too many sources of heat in the room (people, computers, electronics, etc.)
Low refrigerant due to leak or long-term use
SILENCE function is activated (optional function)
Solution
Lower the temperature setting
Clean the affected heat exchanger
Remove the filter and clean it according to instructions
Turn the unit off, remove the obstruction and turn it back on Make sure that
all doors and windows are closed while operating the unit Close windows and
curtains during periods of high heat or bright sunshine
Reduce amount of heat sources
Check for leaks, re-seal if necessary and top off refrigerant SILENCE function
can lower product performance by reducing operating frequency. Turn off
SILENCE function.
57
Problem
The unit is not working
The unit starts and stops frequently
Poor heating performance
Indicator lamps continue flashing Error code appears and begins with the
letters as the following in the window display of indoor unit: · E(x), P(x),
F(x) · EH(xx), EL(xx), EC(xx) · PH(xx), PL(xx), PC(xx)
Possible Causes Power failure
Solution Wait for the power to be restored
The power is turned off
Turn on the power
The fuse is burned out Remote control batteries are dead
Replace the fuse Replace batteries
The Unit’s 3-minute protection has been activated
Wait three minutes after restarting the unit
Timer is activated
Turn timer off
There’s too much or too little refrigerant in the system
Incompressible gas or moisture has entered the system.
The compressor is broken
The voltage is too high or too low
Check for leaks and recharge the system with refrigerant.
Evacuate and recharge the system with refrigerant
Replace the compressor
Install a manostat to regulate the voltage
The outdoor temperature is extremely low
Use auxiliary heating device
Cold air is entering through doors and windows
Low refrigerant due to leak or long-term use
Make sure that all doors and windows are closed during use
Check for leaks, re-seal if necessary and top off refrigerant
The unit may stop operation or continue to run safely. If the indicator lamps continue to flash or error codes appear, wait for about 10 minutes. The problem may resolve itself. If not, disconnect the power, then connect it again. Turn the unit on. If the problem persists, disconnect the power and contact your nearest customer service center.
NOTE: If your problem persists after performing the checks and diagnostics above, turn off your unit mmediately and contact an authorized service center.
58
TRADEMARKS, COPYRIGHTS AND LEGAL STATEMENT
logo, word marks, trade name, trade dress and all versions thereof are
valuable assets of Midea Group and/or its affiliates (“Midea”), to which Midea
owns trademarks, copyrights and other intellectual property rights, and all
goodwill derived from using any part of an Midea trademark. Use of Midea
trademark for commercial purposes without the prior written consent of Midea
may constitute trademark infringement or unfair competition in violation of
relevant laws.
This manual is created by Midea and Midea reserves all copyrights thereof. No
entity or individual may use, duplicate, modify, distribute in whole or in
part this manual, or bundle or sell with other products without the prior
written consent of Midea.
All the described functions and instructions were up to date at the time of
printing this manual. However, the actual product may vary due to improved
functions and designs.
DISPOSAL AND RECYCLING
Important instructions for environment(European Disposal Guidelines)
Compliance with the WEEE Directive and Disposing of the Waster Product: This
product complies with EU WEEE Directive (2012/19/EU). This product bears a
classification symbol for waster electrical and electronic equipment (WEEE).
This symbol indicates that this product shall not be disposed with other
household wastes at the end of its service life. Used device must be returned
to official collection point for recycling of electrical electronic devices.
To find these collection systems please contact to your local authorities or
retailer where the product was purchased. Each household performs important
role in recovering and recycling of old appliance. Appropriate disposal of
used appliance helps prevent potential negative consequences for the
environment and human health.
59
DATA PROTECTION NOTICE
For the provision of the services agreed with the customer, we agree to comply
without restriction with all stipulations of applicable data protection law,
in line with agreed countries within which services to the customer will be
delivered, as well as, where applicable, the EU General Data Protection
Regulation (GDPR).
Generally, our data processing is to fulfil our obligation under contract with
you and for product safety reasons, to safeguard your rights in connection
with warranty and product registration questions. In some cases, but only if
appropriate data protection is ensured, personal data might be transferred to
recipients located outside of the European Economic Area.
Further information are provided on request. You can contact our Data
Protection Officer via MideaDPO@midea.com. To exercise your rights such as
right to object your personal date being processed for direct marketing
purposes, please contact us via MideaDPO@midea.com. To find further
information, please follow the QR Code.
The design and specifications are subject to change without prior notice for
product improvement. Consult with the sales agency or manufacturer for
details. Any updates to the manual will be uploaded to the service website,
please check for the latest version.
Importer: FG EUROPE SA 128, VOULIAGMENIS AVE 16674 GLYFADA, GREECE
Manufacturer: GD Midea Air-Conditioning Equipment Co,.Ltd. Lingang Road
Beijiao Shunde Foshan Guangdong People’s Republic of China 528311
60
RED Declaration of Conformity (DoC)
Unique identification of this DoC: …………….
We,
GD Midea Air-Conditioning Equipment Co., Ltd. Lingang Road, Beijiao, 528311
Shunde, Foshan, Guangdong, PEOPLE’S REPUBLIC OF CHINA
declare under our sole responsibility that the product:
product name: Split type air conditioner trade name: Midea type or model: EU-
SK110Split type air conditioner relevant supplementary information:
……………………………………………………………………
(e.g. lot, batch or serial number, sources and numbers of items)
to which this declaration relates is in conformity with the essential
requirements and other relevant requirements of the RE Directive (2014/53/EU).
The product is in conformity with the following standards and/or other
normative documents: HEALTH & SAFETY (Art. 3(1)(a)): EN IEC 62311:2020, EN
60335-240:2003+A11:2004+A12:2005+A1:2006+A2:2009+A13:2012,EN
603351:2012+A11:2014+A13:2017+A1:2019+A14: 2019+A2: 2019+A15:2021,EN
62233:2008
EMC (Art. 3(1)(b)): EN 301 489-1 V2.2.3: 2019,EN 301 489-17 V3.2.4 :2020, EN
IEC 55014-1:2021, EN IEC 55014-2:2021, EN IEC 61000-3-2:2019+A1:2021,EN
61000-3-3:2013+A1:2019+A2:2021
SPECTRUM (Art. 3(2)): EN 300 328 V2.2.2 (2019-07)
OTHER (incl. Art. 3(3) and voluntary specs): ………………………………………………………
(title and/or number and date of issue of the standard(s) or other normative
document(s))
Limitation of validity (if any): …………………………………………………………………………….
Supplementary information:
Notified body involved: N/A………………………………………………………………………………
………………………………………………………………………………………………………………..
……………………………………………………………………………………………………………….. Technical file held by: GD Midea
Air-Conditioning Equipment Co., Ltd.
………………………………………………………………………………………………………………..
………………………………………………………………………………………………………………..
………………………………………………………………………………………………………………..
Place and date of issue (of this DoC): Foshan/2023-01-07 Signed by or for the
manufacturer: ………………………………………………………………………
(Signature of authorised person)
Name (in print): Silvia Su………………………………………………………………… Title:
…………………………………………………………………………………………………
61
CS021UI-CB(OBM)
Split Tye
MSmartHome
:
&
CB1-09HRFN8-I
CB1-12HRFN8-I CB1-18HRFN8-I
: ,
.
.
.
.
.
Midea! Midea, .
———————————— 65 ——————————— 66 ———————————————— 70 ———————————— 71 ———————————
72
——————————————— 74 ——————————————— 84 ———————————————— 89
———————————————————————- 93 —————————– 95 ———————————————————– 96 ——————————–
97
————————————— 98
—————————————————– 98 —————————————————– 1 03 ——————————————— 114
——————————– 120 ——————————- 122 , ——————————————— 125 ——————————- 125
—————-126
65
. .
. “” . «» . «» . .
/ !
8 , . . ( ). ( ) , , , ‘ , . .
66
(.. ),
.
, , .
, . ,
.
, .
.
. .
.
.
. .
.
,
.
, , , , .
.
, ,
.
,
.
,
, .
,
.
.
.
.
,
, .
.
.
. ,
, .
.
.
.
.
.
.
,
3 ,
10 mA, (RCD)
30mA
.
67
(PCB) . , : T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC,etc.
UV-C ( UV-C )
UV-C. . UV-C . .
UV-C. UV-C , , . , . UV-C , . UV-C .
UV. .
. , .
. , , .
. .
. , , .
. , .
. , , .
, 1 (3 ) .
. , .
.
.
.
68
.
.
.
.
.
.
.
.
. , .
. .
. .
(
R290)
. , ” – ” . ( ).
, , .
.
5CO2-, , 50CO2, 24 .
, .
R32/R290
, .
R32: , 4m2.
R290, , : <=2,6kW : 17,33m2 >2,6kW <=3,5kW : 25,4m2 >3,5kW <=5,2kW : 34,67m2
5,3kW <=7,1kW : 47,33m2
.
69
70
. .
1 1
3 2
2
3
4
4 6
5
7
9
8
10 5
6 7
8
11 11
(1)
(2)
( )
( )
( ) ( )
71
. . , , .
Q’ty (pc)
Q’ty (pc)
1-3
1
( )
1
( )
1
1
5 ~ 8 ( ) 5 ~ 8 ( )
2
( )
1
( 2 )
( )
1 ~ 2 ( )
1 2 3
6,35 (1/4in) 9,52 (3/8in) 9,52 (3/8in) 12,7 (1/2in) 16 (5/8in) 19 (3/4in)
(PC)
.
( . , )
( )
.
&
&
72
–
1
2
3
15cm (5-7/8″)
12cm (4-3/4″)
2,3m (7/8″)
12cm (4-3/4″)
4
5
6
7
8
( )
9
( )
73
1
:
, , .
. :
(.. , , )
: ,
:
: , (. ) . ( ). , .
74
2
:
. 16mm (5/8″) , 90mm (3-9/16″). 16mm (5/8″), 65mm (2-1/2″).
1: .
2: . , . . :
:
, , 5mm (0,2in-) . .
4:
. . .
426mm (16,8in)
153mm (6,0in)
169mm (6,6in)
169mm (6,6in)
140mm (5,5in)
39mm 1,5in
3: . .
H
W
65mm (2,56in)
(x): 812mm (40,0in) x 299mm (11,8in)
91mm (3,6in)
561mm (22,1in)
253mm (9,97in) 132mm (5,2in)
43mm (1,7in)
39mm (1,5in) 43mm (1,7in)
H
65mm (2,56in)
W (x):
968mm (38,1in) x 322mm (12,7in)
75
, , .
65mm (2-1/2″)
90mm (3-9/16″)
65mm (2-1/2″) 90mm (3-9/16″) ( )
1: 65mm (2,5″) 90mm (3,54″) ( ), . , 5mm 7mm (3/16-5/16in). .
5-7mm (3/16-5/16″)
.
2: . .
.
76
3
. .
–
Four
1: , . . .
2: , . , . . : . .
3: . , . : , .
. .
77
,
.
.
.
.
()
1: . , . ( ) .
.
.
. .
, .
78
4
,
.
,
.
1. .
2. .
3. , . .
4. , 1/8 (3mm). .
.
. . ( ) (
): H05VV-F H05V2V2-F : H07RN-F H05RN-F : H07RN-F ( )
5. .
6. .
7. . , .
8. , .
9. , . , 10 .
10. 90-110% . , , .
(A)
3 6 > 6 10 > 10 16 > 16 25 > 25 32 > 32 40
(mm²)
0,75
1 1,5 2,5
4 6
, , . . , .
1. .
2. , . .
3. .
79
4. ( ).
5. , .
6. , , u .
7. , . .
8. .
. : . . 1. ,
. 2. , . 3. . 4. . 5. .
.
80
5 &
, , / , .
()
1: , ( ).
2: , .
3: , , . .
, .
. .
, . ( ).
81
6
, : ,
4. ,
. ,
.
. ,
. . , . . , .
82
30°
, :
.
, , . ( ). ( ). , . . , . .
:
. , 30-50mm (1,18-1,96in), .
30-50mm 1-3/16~2in
30-50mm (1-3/16~2in)
, .
, .
5~10 .
A B , , .
83
1
:
, . .
:
60cm24″
30cm (12″)
30cm (12″)
–
200cm (79″)
60cm (24″)
.
, .
, .
:
: 90° . , . .
: . .
( ): .
90°
:
,
84
2
( )
:
, . , .
1: .
2:
.
. . ( )
.
:
, . , .
85
3
, . (10)
.
.
(mm) W x H x D
680x542x248 (26,8″x21,3″x9,8″) 720x495x270 (28,3″x19,5″x10,6″) 765x555x303
(30,1″x21,8″x11,9″) 805x554x330 (31,7″x21,8″x12,9″) 890x673x342
(35,0″x26,5″x13,5″) 946x810x420 (37,2″x31,9″x16,5″) 946x810x410
(37,2″x31,9″x16,1″)
A (mm)
452 (17,8″)
B (mm)
230 (9,1″)
452 (17,8″)
255 (10,0″)
452 (17,8″)
286 (11,3″)
511 (20,1″)
317 (12,5″)
663 (26,1″)
354 (13,9″)
673 (26,5″)
403 (15,9″)
673 (26,5″)
403 (15,9″)
, :
. – . . . . . , .
, :
. .
.
, . . . . , .
, . .
86
4
–
.
, .
: « » 24. ,
40mm (1,57in) . . , u .
, (“L”) . . .
.
. , u . , . , . . PVC. . . : , .
, , . .
: , ,
, , .
87
. . .
3 . .
( ) . . . . . : .
1-9/16″ (40mm)
G
.
.
25mm (15/16″)
10mm (3/8″)
1: :
( ) ( )
( )
2: .
( ) ( )
(A)
( )
(B) 88
1
, . . .
. 5 (16,5 ). 3 .
R410A, R32
R22 . R410A, R32
(BTU / h)
< 15.000 15.000 < 24.000 24.000 < 36.000 36.000 < 60.000
< 18.000 18.000 < 21.000 21.000 < 35.000 35.000 < 41.000
< 18.000 18.000 < 36.000 36.000 < 60.000
(m)
25 (82ft) 30 (98,5ft) 50 (164ft) 65 (213ft)
10 (33ft) 15 (49ft) 20 (66ft) 25 (82ft) 20 (66ft) 25 (82ft) 30 (98,5ft)
(m)
10 (33ft) 20 (66ft) 25 (82ft) 30 (98,5ft) 5 (16ft) 8 (26ft) 10 (33ft) 10
(33ft) 8 (26ft) 10 (33ft) 15 (49ft)
–
1:
,
.
90°
.
.
, .
90 .
, . .
89
. .
2:
. .
. , .
PVC .
. .
3:
.
, PVC . . . , .
A (mm)
(mm)
.
.
Ø6,35 (Ø1/4″)
0,7 (0,0275″) 1,3 (0,05″)
Ø9,52 (Ø3/8″)
1,0 (0,04″) 1,6 (0,063″)
Ø12,7 (Ø1/2″)
1,0 (0,04″) 1,8 (0,07″)
Ø16 (Ø5/8″)
2,0 (0,078″) 2,2 (0,086″)
Ø19 (Ø3/4″)
2,0 (0,078″) 2,4 (0,094″)
A
.
.
, .
90
2
, . .
, 10cm.
10cm (4″)
1:
.
2:
. ,
.
, . .
()
(mm) Ø6,35 (Ø1/4″) Ø9,52 (Ø3/8″) Ø12,7 (Ø1/2″) Ø16 (Ø5/8″) Ø19 (Ø3/4″)
(N·m)
18~20 (180~200kgf.cm) 32~39 (320~390kgf.cm) 49~59 (490~590kgf.cm) 57~71
(570~710kgf.cm) 67~101 (670~1010kgf.cm)
(B) (mm)
8,4~8,7 (0,33~0.34″) 13,2~13,5 (0,52~0.53″) 16,2~16,5 (0,64~0.65″) 19,2~19,7
(0,76~0.78″) 23,2~23,7 (0,91~0.93″)
.
. .
91
3
.
%LJJHU
1:
.
2:
.
. , . .
.
3: ,
. . 1 3 .
92
:
, . , . .
. .
-76cmHg
1:
.
.
. .
.
15 -76cmHG (-10 Pa).
.
5 , , .
93
2: ,
. , ( ). ( ) 1/4. 5 . . . . , . ( , ) . .
, . .
. . , , 7,5 (25’). , 5 (16`). . :
(m)
N/A
: Ø6,35 (1/4″) R410A:
( – ) x 15g/m ( – ) x 0,16oZ/ft R32:
( – ) x 12g/m ( – ) x 0,13oZ/ft R22:
( – ) x 20g/ m
( – ) x 0,21oZ/ft
: Ø9,52 (3/8″) R410A:
( – ) x 30g/m ( – ) x 0,32oZ/
ft R32: ( – ) x 24g/m ( – ) x 0,26oZ/
ft R22: ( – ) x 40g/m ( – ) x 0,42oZ/
ft
.
94
–
.
:
( )
.
.
, . , . : .
.
, . .
, .
D
B
C
A
. . . . & :
, .
95
30 . . ON/OFF (/
) . MODE () , : COOL ()
HEAT ()
5 :
/
(2): (2):
COOL ()
HEAT ()
, . . . .
, : . ,
. b. , . 16°C (60°F) COOL () 16°C/62°F. , MANUAL CONTROL ( ) COOL (). . MANUAL
CONTROL ( ) . 2 COOL (). .
96
: |
---|
1. , , . |
2. . |
3. . 4. . 5. . 6. . 7. , |
. |
1. . 2. . 3. . 4. . |
---|
1. . 2. |
. 3. , , |
. 4. . 5. , . |
: |
1. . 2. . 3. , , |
. 4. . 5. , . |
: . |
97 |
. . .
. .
( – )
( )
( 3 . )
( 3 . )
, .
Wireless Control.
Air magic UV-C ( ) .
ECO . TIMER ON ( ) (
, ” ” TIMER ON ( ) ). UV-C, , , , TURBO .
TIMER OFF ( )
UV-C, , , , TURBO .
( ).
.
8°C (46°F).
98
, .
.
COOL ()
HEAT ()
.
16°C~32°C (60°F~90°F)
0°C~30°C (32°F~86°F)
.
0°C~50°C (32°F~122°F)
-15°C~50°C (5°F~122°F) ( )
-15°C~24°C (5°F~75°F)
-15°C~50°C (5°F~122°F)
-15°C~24°C (5°F~75°F)
DRY ()
10°C~32°C (50°F~90°F)
0°C~50°C (32°F~122°F)
0°C~52°C (32°F~126°F)
0°C (32°F), .
COOL ()
HEAT ()
DRY ()
.
16°C~32°C (60°F~90°F)
0°C~30°C (32°F~86°F)
10°C~32°C (50°F~90°F)
.
18°C~43°C (64°F~109°F)
-7°C~43°C (19°F~109°F)
-7°C~24°C (19°F~75°F)
11°C~43°C (52°F~109°F) 18°C~43°C (64°F~109°F)
18°C~52°C (64°F~126°F)
-15°C~24°C (5°F~75°F)
18°C~52°C (64°F~126°F)
: 80%, . ( ) .
99
, |
---|
. TIMER ON ( |
) TIMER OFF ( ). |
. . |
, .
( ) COOL (), AUTO (COOL) ( ()), DRY (), .
( ) . USB, .
( )
— . “-“. . , , .
— , “CL ” 20 130 , Active Clean ( ).
— , . . .
, .
Air Magic+ ( ) . sochwave .
. .
, .
“EL0C” .
UV-C ( ) UV, UV UV-C .
–
, . . – , . – .
100
. , . . 1-4.
. 1
. 2
. 3
. 4
: , , .
SLEEP () ( ). SLEEP () COOL (). 1°C (2°F) . 1°C (2°F) . . HEAT (), SLEEP () 1°C (2°F) . 1°C (2°F) . . . , SLEEP () , .
Cool () (+1°C/2°F) 2
.
1hr
1hr
.
Heat () ( -1°C/2°F) 2 .
: ()
, SWING () (/ ) . .
COOL () DRY (). , .
COOL () HEAT (), .
101
, .
. . , , , . .
. .
( ) |
---|
manual . . , . . |
:
.
MANUAL CONTROL ( ) .
MANUAL CONTROL ( ) FORCED AUTO ( ).
MANUAL CONTROL ( ) FORCED AUTO ( ).
MANUAL CONTROL ( ) .
.
102
1
2 MODE ()
TEMPERATURE 3 ()
POWER () 6
AUTO COOL DRY HEAT FAN
5
FAN SPEED 4 ( )
AU-100%
.
. ,
, .
103
( ). . 1.
. 2. , (+) (-) , . 3. .
:
.
, 2 .
. .
8 .
.
, .
.
. ,
CAN ICES-3(B)/NMB-3(B). , 15 FCC. : (1)
(2)
, 15 FCC. . , , , . , . , , : . . . / . .
104
2
1
3
4
6
5
7
8 10
9
LED
11
13
12
Cool/Heat Swing Air
Flash 3s
magic
14
15 : RG10N72HS/BGEF
No.1 No.2 No.3
No.4
No.5 No.6 No.7 No.8
No.9
No.10 No.11 No.12
No.13 No.14
ON/OFF (/) . MODE () > > > > : HEAT () . BREEZE () > > >
TEMP () 0,5°C (1°F). . 30°C (86°F). & 3
, °C °F.
SET () > > > AP > . TIMER () TEMP () 0,5°C (1°F). 16°C (60°F) FAN SPEED ( ) AU
20% > 40% > 60% > 80% > 100% TEMP ()
/ 1%. LED LED ECO/GEAR ECO > GEAR (75%) > GEAR (50%) > > ECO….. / ( ) ( ) . SWING () . 3 ( ). Air magic+ / Air magic UV-C ( ).
No.15
LOCK () 5 . 2 .
105
No.1
No.2
1
4
5
8
9
LED
12
Cool/Heat Swing Swing Flash
No.3
2 3 No.4
6 7
No.5 10 11
No.6 13 14
No.7
No.8 15
No.9 : RG10N8(2HS)/BGEF
No.10
No.11
No.12
No.13 No.14
ON/OFF (/) . MODE () > > > > : HEAT () . BREEZE () > > >
TEMP () 0,5°C (1°F). . 30°C (86°F). & 3 , °C °F.
SET () > > > AP > []: . TIMER () TEMP () 0,5°C (1°F). 16°C (60°F) FAN SPEED
( ) AU > 20% > 40% > 60% > 80% > 100% TEMP () / 1%. LED LED ECO/GEAR ECO >
GEAR (75%) > GEAR (50%) > > ECO….. / ( ) ( ) . SWING () ( ) . 2 ( ). SWING ()
( ) .
No.15
LOCK () 5 . 2 .
106
No.1
No.2
1
4
5
8
9
LED
12
Cool/Heat Swing
Flash
3s
Fresh
No.3
2 3 No.4
6 7
No.5 10 11 No.6 13 14
No.7
No.8 15
No.9 : RG10N9(2HS)/BGEF
No.10
No.11
No.12
No.13 No.14
ON/OFF (/) . MODE () > > > > : HEAT () . BREEZE () > > >
TEMP () 0,5°C (1°F). . 30°C (86°F). & 3 , °C °F.
SET () > > > AP > []: . TIMER () TEMP () 0,5°C (1°F). 16°C (60°F) FAN SPEED
( ) AU > 20% > 40% > 60% > 80% > 100% TEMP () / 1%. LED LED ECO/GEAR ECO >
GEAR (75%) > GEAR (50%) > > ECO….. / ( ) ( ) . SWING () . 3 ( ). FRESH ()
UV-C.
No.15
LOCK () 5 . 2 .
107
.
( )
.
Sleep()
*:
Air magic+ *
MODE ()
AUTO COOL DRY
HEAT
FAN
ECO
GEAR
TIMER ON ( )
Timer OFF ( )
Temperature/Timer/Fan speed (/ / ) TIMER ON/OFF ( /).
FAN SPEED ( )
AUTO
SLIENCE
() ()
LOW
MED
() ()
HIGH ()
1% 2-20% 21-40% 41-60% 61-80% 81-100% : AUTO () DRY ().
/
1. .
, .
108
, .
AUTO () AUTO ()
: 1. AUTO (), COOL (),
FAN () HEAT () .
2. AUTO (), .
COOL () HEAT ()
COOL/HEAT (/ )
DRY () DRY ()
: DRY (), .
FAN ()
FAN ()
: FAN (), . , .
109
TIMER ()
TIMER ON/OFF ( /)- / .
TIMER ON ( )
TIMER () ON ().
ON () . 1 .
TIMER OFF ( )
TIMER () OFF ().
. 1 .
: 1. TIMER ON ( ) TIMER OFF
( ), 30 , 10 . 10 24, 1 . ( , 5 2,5 10 5 ). 0,0 24. 2. 0,0h.
TIMER ON & OFF ( & ) () .
xn
xn
1 sec
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMER OF
ON
()
OFF (-
)
1
2:00PM 3:00PM
3:30PM
4PM
5PM
6PM
2,5 5
ON/OFF
MODE FAN
SLEEP
TEMP
SCHUOTRT TIMER ON
TIMER OF
: 1:00 .., , 2,5 (3:30 ..) 6:00 ..
110
Swing () Swing ()
Swing ().
SWING (), . . .
3 . ( )
Swing ()
Swing ().
SWING (), . . .
, .
LED
5 ( )
.
5 , . 5 .
111
/
COOL (), . , . HEAT (), . .
ECO/GEAR
: ECO GEAR (75%) GEAR (50%) ECO…… : COOL ().
ECO: , 24°C/75°F Auto . , .
: ECO 24°C/75°F ECO. ECO, 24°C/75°F. . ECO .
GEAR ECO/GEAR GEAR : 75% ( 75% ) 50% ( 50% ) . GEAR, .
FP
2
Fan () 2 / Silence (). , . ON/OFF (/ ), Mode, Sleep, Boost Clean .
HEAT () 16°C/60°F FP. ( ) 8°C/46°F.
112
SET ()
SET
SET
OK
SET () , SET () TEMP TEMP . , OK .
, . SET () :
( ) ( ) ( ) AP* ( )
. Active Clean , . , “CL”. 20 130 , .
( ): SLEEP () ( ). : SLEEP () FAN () DRY ().
AP ( )( ) : SET () AP ( ) . , AP LED 7 10 .
( ): FOLLOW ME ( ) 3 . AUTO (), COOL () HEAT (), ( ) .
: / 7 / .
, 3 “ON ()”.
, “OFF ()” 3 .
, ON/OFF (/ ), .
113
: iOS, Android
. Android iOS .
.
Smart Kit WPA-PSK/WPA2-PSK . WPA-PSK / WPA2-PSK.
:
. , .
5 megapixel QR.
, .
.
. .
: APP: EU-SK110, US-SK110 : PCB : 2400-2483,5MHz :0°C~45°C/32°F~113°F :
10%~85% : DC 5V/500mA TX: <20dBm
. Internet . .
1. .
2. QR MSmartHome Google Play Store Apple App Store.
MSmartHome
&
114
:
, «» , . .
, .
: 8
, .
: .
.
. 2,4 GHz
. 2,4 GHz, . . , .. . . . , . , . WLAN+ (Android) WLAN Assistant (iOS) .
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>