KOSTAL 12170142 Surge Protection Module
Switch off inverter – battery
Open inverter
Remove the DC overvoltage protection cover
Install DC overvoltage protection
Close inverter
Switch on inverter
Optional: Check the DC overvoltage module activation
- After installation in the inverter, the internal overvoltage protection module is automatically detected and the usage is displayed in the web menu of the inverter under the following menu item.
Replace DC overvoltage module
The overvoltage protection module has tripped and must be replaced if the inverter reports event 1037. This is not a reason for a complaint or a warranty case.
01/2024 – MA 12189981-00001 – DOC03248044-0001 – Contact: KOSTAL Solar Electric GmbH, Hanferstr. 6, 79108 Freiburg i. Br., Germany, Tel. +49 761 477 44 – 100, Fax +49 761 477 44 – 111, www.kostal-solar-electric.com Subject to technical changes, errors excepted. You can find current information at www .kostal-solar-electric.com.