USER MANUAL
SUPRA 505/705/905
INTERACTIVE UPS
120V NEMA
-
Technical information on this manual is property of XMART by INTEGRA
This manual Information cannot be copied or distributed totally or partially without written approval of XMART. -
XMART can introduce modifications in their products or manuals without further notice.
-
XMART is not responsible of mistakes or missing information in this manual.
-
XMART is not responsible for wrong use a third part can do of this information.
-
Trademarks and logos in this manual are property of their owners.
SAFETY INSTRUCTIONS
SYMBOLS
| WARNING
---|---
| ELECTRICAL SHOCK RISK
WARNING: It is required to read and understand this manual. Follow all
instructions given in this manual for starting up and operating this product.
Only qualified technician must start-up, operate and maintain this product.
Keep manuals as a guide for future consults.
WARNING: This product operates with dangerous voltages. It must be
installed, operated, and maintained ONLY by qualified technicians trained for
this kind of products. Service personnel MUST know and understand very well
all electric risks related to this product. UPS manufacturer or distributor
will never be responsible for any accident produced by lack of knowledge or
negligent practices at the moment of install, starting up, or maintain this
product. UPS manufacturer or distributor is not liable for any damage that
might rise from misusing this unit or defective installation.
WARNING: If you are not qualified technician do not try to repair this
product.
WARNING: Internal area of this product is locked by screws. Do not try to
access inside the UPS unless you are a qualified technician. UPS must be
checked, repaired, and maintained by qualified personnel only.
ELECTRICAL SHOCK RISK
CAUTION: There are dangerous voltages in the UPS power outlets although the
equipment is not plugged into power line.
CAUTION: Inside this equipment, due to internal batteries, there are
ALWAYS dangerous voltages, even UPS is OFF and unplugged of power line.
WARNING EQUIPMENT DISPOSAL
OUT OF SERVICE UNITS: It is strongly recommended to dispose this piece
of equipment according to valid directives in your country. At the moment of
disposing all pieces need to be managed appropriately to avoid possible
environmental damage or for some materials to be recycled.
BATTERIES: Do not throw it to fire (risk of explosion). Do not open the
batteries, there are dangerous liquids inside.
SAFETY & QUALITY STANDARDS
SAFETY – LOW VOLTAGE DIRECTIVE (2014/35/EU)
UPS Part 1-1: General & Safety UPS in accessible areas| IEC/EN 62040-1
ELECTROMAGNETIC COMPATIBILITY – EMC DIRECTIVE (2014/30/EU)
UPS, Part 2, Electromagnetic Compatibility:| IEC/EN 62040-2
Low Freq. Conducted Disturbances & Signals:| IEC/EN 61000-2-2
Electrostatic discharge immunity Test:| IEC/EN 61000-4-2 (Air: Level 3.
Contact: Level 2)
Radiated radio Frequency immunity:| IEC/EN 61000-4-3 (Level 3)
Electrical Fast Transient / burst immunity:| IEC/EN 61000-4-4 (Level 3)
Surge immunity:| IEC/EN 61000-4-5 (L-L: Level 2. L-G: Level 3)
UPS Part 3: Methods of operation. specifications, and test requirement| IEC/EN
62040-3
IT Equipment. SAFETY. Part 1: General Requirements| IEC/EN 60950-1
For 220V MODELS:| CE compliant
For 120V MODELS (505-UL/705-UL/905-UL):| UL1778 (Certified by cTUVus)
IP PROTECTION| IP20 (static)
QUALITY MANAGEMENT: ISO 9001 : 2000| Manufactured under: ISO 9001
ENVIRONMENTAL MANAGEMENT: ISO 14001 : 2004| Manufactured under: ISO 14001
Changes or modifications not expressly approved by the party responsible for
compliance could void the user´s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Any modification made by user or operator may affect compliance of the safety
and performance certifications listed above. UPS manufacturer is not
responsible of any modification made on the product or its accessories after
it is manufactured.
This product is designed to operate in domestic and commercial environment.
This is a C2 category product. In residential environment, this product may
cause radio interference, in this case the user may require taking additional
measures.
BATTERY MAINTENANCE
-
Batteries capacity, in general (of all kinds), decreases with time and use.
-
Our products contain high quality batteries only.
-
Batteries useful life in our UPS is between 3 and 5 years, considering environment temperature under 25ºC and optimal operational conditions. This time can be dramatically reduced by high temperature and other adverse operation condition.
-
Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as number and kind of equipment connected to UPS
-
Batteries should be periodically tested to check capacity and assure and appropriate back up.
-
To enlarge batteries life expectancy, it is recommendable to fully discharge UPS once every 3 months
-
During long UPS storage recharge batteries according to following table:
STORAGE TEMPERATURE | FREQUENCY | RECHARGING TIME |
---|---|---|
-25°C a +30°C | Every 4 months | 4 h |
+30°C a +45°C | Every 2 months | 4 h |
UPS DESCRIPTION
This kind of equipment is known as UPS (Uninterruptible Power Supply). It has
2 main functions: give electrical protection against surges, spikes and some
other dangerous failures of electrical main system and also provides
electrical backup based on internal batteries. In that way products you
connect to your UPS will be protected and will receive electrical energy even
during failures of main electrical AC system.
This UPS is designed to satisfy all requirements of Personal Computers (PCs).
It includes internal voltage regulator to stabilize input AC variations
without using internal batteries. Only in presence of important input
failures UPS will use internal batteries to provide energy in outlet sockets.
In this way batteries life expectancy is longer.
It is an interactive UPS with step-wave output, including surge protection in
all AC outlets. RJ45 & RJ11 sockets also include surge protection for the
phone line of the router.
Parts Identification
1.- Output sockets | 4.- USB |
---|---|
2.- AC Input | 5.- RJ45/RJ11 surge protected sockets |
3.- AC Input breaker |
UPS will provide backup energy in its outlets when main AC input fails. Runtime will depend on some different factors:
- Battery charging level.
- Battery capacity according to the use given and lifetime.
- Load consumption connected to UPS outlets. Higher the output load shorter the runtime.
Under normal condition, when UPS is ON and connected to AC source, UPS will
keep batteries fully charged.
NOTE: For Self-protection, all models of this family have a Max. backup
time of 120 Minutes, limited by UPS electronic.
UPS INSTALLATION
SAVE THESE INSTRUCTIONS – This manual contains important instructions for
Models SUPRA 505/705/905 that should be followed during installation and
maintenance of the UPS and batteries.
Servicing of batteries should be performed or supervised by personnel
knowledgeable about batteries and the required precautions.
When replacing batteries, replace with the same type and number of batteries
or battery packs.
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
CAUTION: Do not open or mutilate batteries.
Released electrolyte is harmful to the skin and eyes.
It may be toxic.
CAUTION: A battery can present a risk of electrical shock and high short-
circuit current. Contact with any part of a grounded battery can result in
electrical shock. The following precautions should be observed hen working on
batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source and load prior to installing or maintaining the
battery.
f) Remove battery grounds during installation and aintenance to reduce
likelihood of shock. Remove the connection from ground if any part of the
battery is determined to be grounded.
CAUTION: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
The socket-outlet shall be installed near the equipment and shall be easily
accessible.
- This UPS must be installed indoor with controlled environment free of excessive dust, corrosive air, or conductive dust.
- Do not install in outdoor. Keep UPS working under operational conditions listed in specifications table of this manual. Keep out of direct sun light, water, and heat sources.
- Do not install UPS close to PC screen to avoid interference. UPS must be at least at 20cm from screen.
- Connect TEL or LAN line to RJ45/RJ11 port in this UPS identified as IN. Connect OUT to your Router (TEL input) or to your PC LAN port.
- Plug power cord of this UPS to AC source socket.
- Plug your equipment to UPS outlets.
- This unit MUST NOT be installed into closed boxes/cabinets that avoid fresh air access. During normal operation, this unit needs fresh air to flow through ventilation system (Vents) to cool power circuits.
Installing this unit in a closed box/cabinet makes inner air to be recycled without refreshing, increasing inside temperature, exceeding operation max. temperature, and causing permanent damage to the UPS.
IMPORTANT WARNINGS
-
Make sure UPS is plugged to AC source compatible with UPS electrical specifications.
Check UPS specs in UPS label. -
Make sure your products input voltage is compatible with UPS voltage output.
-
Check total load in Watts to be connected to UPS is not higher to maximum UPS capacity.
-
Do NOT plug neither laser printers nor copiers to this UPS. This equipment are high load products will overload your UPS.
OPERATION
-
Once UPS is installed and connected according to section 4 of this manual, please turn UPS on by
ON/OFF button in front panel. Front panel green LED must turn ON. -
Turn your products ON one by one.
-
After finishing your products will be fully protected by the UPS.
This UPS has COLD-START function that allows to turn UPS on even during a
failure in the main AC source.
Front panel LCD will let you know UPS status: OFF / ON / BATTERY MODE.
LCD
LCD shows valuable information about Utility and UPS data but also provides
alarm codes for easy troubleshooting. User can skip from screen to screen by
simple touching LCD.
Note: Below table shows screens for 220V model. In 120V models, input &
output values will be close to 120V.
CONTROL SOFTWARE
Most of the models of this UPS family come with USB port to communicate with
your PC. In that way UPS can be monitored and configured. Your PC can be
shutdown automatically when a input AC failure is detected saving your
information and providing a controlled shutdown. Event log and alarms can also
be monitored from your PC.
Control software can be downloaded from our website: www.xmart-ups.com. We
keep updated last updated version. User manual and installation manual is also
available in our web.
Our software is available in different versions for: Windows, Mac OSX, Linux,
and Unix.
TROUBLESHOOTING
# | PROBLEM | CAUSE | SOLUTION |
---|---|---|---|
UPS does not turn ON LED OFF | ON button has not been properly activated. |
Push ON button for 2-3 seconds
Very low battery level| Keep UPS plugged to main service to recharge batteries
Battery failure| Contact service center to replace batteries
2| UPS goes to battery mode even main source is OK Front LED flashing in green
color.
Intermittent BEEP alarm activated| Input cable or plug is not connected to
main source| Check and plug properly
Input breaker is activated (open)| Check and reset input breaker
3| Input breaker is activated frequently| Equipment connected to UPS outlets
overload UPS.| Check and unplug equipment until overload condition is solved
4| Continuous BEEP alarm.| UPS is overloaded| Check and unplug equipment until
overload condition is solved
5| UPS power off when AC main source fails
(runtime = Os)| Low battery level because recent discharge| Keep UPS plugged
to main service to recharge batteries
Battery failure| Contact service center to replace batteries
AFTER SALES SUPPORT & WARRANTY
Support: If a failure or problem is detected please check troubleshooting
section in user manual. If problem cannot be solved, please contact authorized
service center or authorized dealer.
Batteries: Rechargeable batteries can be charged and discharged hundreds of
times. However, they will eventually wear out.
This is not a defect or failure so that batteries wear out is not covered by
this warranty.
Battery lifetime will depend on operative conditions like working temperature,
type and frequency of discharging cycles. Higher the temperature shorter will
be the lifetime. Frequent and deep discharging cycles also will short
lifetime. For critical applications batteries should be revised and replaced
periodically. Long storage (longer than 6 months) without required recharging
will wear out batteries. This situation is not covered by this limited
warranty since this is not considered as a defect. Check recharging
instructions on user manual.
Conditions Limited Warranty “PLUS”
-
Subject to the conditions of this limited warranty, this product is warranted to be free from defects in materials and workmanship at the time of XMART supplies the product.
▪ In Europe, warranty time is 2 years on electronic parts and 2 years on internal batteries from XMART invoice date.
▪ In America, standard warranty times could vary depending on country/region or can be extended by purchasing warranty options. Please check warranty plans and extensions with your local distributor. -
If during the warranty period, this product fails to operate under normal use and service, due to defects in materials or workmanship, authorized distributor or service center will, at their option, either repair or replace the product in accordance with terms and conditions stipulated herein. Transportation expenses are not covered by this limited warranty.
-
Warranty is valid only if the original invoice issued by XMART, specifying date of purchase, serial number, and name of the dealer, is presented with the product to be revised. XMART and authorized partners reserve the right to refuse warranty service if any of this information has been removed, changed, or missing in original invoice document.
-
If product is repaired or replaced, repaired, or replaced product will be warranted for the remaining time of the original warranty or for 90 days on repaired part from date of repair, whichever is longer.
-
XMART or their distribution/service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty.
-
If product is out of warranty a reparation proposal will be sent to the user for his approval. If proposal is not accepted, service center will keep product available for the user during 60 continuous days. After this period product would be disposed and user will not be able to rise any claim.
-
Rechargeable batteries, like included in this product, will definitively wear out even under normal operation. This is not a defect or failure, so it is not covered by this warranty.
-
This warranty does not cover batteries wear out caused by improper or long storage (over 6 months without required recharging indicated in product manual). Even performing recharging procedure this product cannot be storage longer than 18 months. Problems on batteries caused by this kind of long storage are not covered by this warranty.
-
This warranty does not cover product failures caused by installations, modifications or repair performed by non-authorized person. If product is open by not authorized technician warranty will be considered void. This warranty does not cover failure caused by inadequate installation or maintenance, misuse, accidents, fire or floods.
-
This product can include protection devices like input fuse or input breaker. Activation of this kind of devices is not a failure it is caused by an improper product installation. Input fuse or breaker reset, or replacement is not covered by this warranty.
-
This warranty does not cover damages produced during transportation from user to technical service caused by improper packing of the product by user.
-
Warranty terms and conditions cannot be modified or extended by third parties without written approval of XMART.
Limited Warranty “PLUS”
- XMART does not warrant that the operation of this product will be uninterrupted or error-free during its lifetime. If product fails to work, the maximum liability of XMART under this limited warranty is expressly limited to the lesser of the price you have paid for the product or the cost of repairing or replacement of any hardware components that malfunction in conditions of normal use.
- In no event will XMART be liable for any damages caused by the product or the failure of the product to perform, including any lost profits or savings or special, incidental, or consequential damages. XMART is not liable for any claim made by a third party to XMART or to final user.
- XMART is not responsible for damage that occurs because of your failure to follow the instructions intended for this hardware product.
TECHNICAL SPECIFICATIONS
| 505 705
905
---|---
INTERACTIVE UPS
Capacity
Input
Nominal Voltage| 450VA/240W 650VA/360W
110 Vac -120 Vac (Default 120 Vac)| 850VA / 480W
-MI
Voltage Range| 89-145 Vac
Frequency| 60Hz! 50 Hz: Auto Sensing; AutodetecciOn
Power cord| 6 feet (1.83m) NEMAS-15P
Generator Compatible
Output
Voltage| Yes /Si
+/- 10% (1 Phase /1 Fase)
Frequency| 60Hz (+/- 1Hz) – 50Hz (+/- 1Hz)
Transfer Time| 2 – 6 ms typical /tipico
Waveform (Normal Mode)| Sinewave/ Sinusoidal
Waveform (Battery Mode)| Simulated Sinewave /Sinusoidal Sintelzada ..
Sealed Lead Acid – Maintenance Free (VRLA AGM) / Acido Plomo| ellada Sin Mtb.
(VR LA AGM)
Palterles
Type
Capacity| 4.5AH| 7AH| 9AH
Ouartity| 1| 1| 1
Back-up Time Typical| 10-12 min.| 17-20 min.| 22-25 min.
Recharge Time| 4-6 boas b 90% capacity /4-6 Haas hasta 90% de capacidad
Alarms-Indications LCD| Deep discharge and overcharge/ Descaga Profundas y
Sobre-Cagas
- Operation Mode 2) Input Volt. 3) Output Volt. 4) Load 5) Battery Level 6)
Overload
Acoustic Alan all models Protections
Input CircuR Breaker / “Breaker de Ertrada| Battery Mode/ Low Batery/ Overload/ Battery Replacement/ UPS Fault
With Manual Reset /11syuntor Rearmable
Surge/Spikes Protection (Line H-N) Protecdonconha Picos/ Rayos (Linea L-N)| Power Outlet Sockets with surge & spikes protection: L-N
Tomas de Salida Protegidas conha Picos/Rayos: L-N
Surge/Spikes Protection (RJ45) Protecdonconha Picos/ Rayos (RJ45)| Telinemet/Ethemet: RJ45
Total Surge Sibpression /Supresion Total| > 758J
Noise /Ruido Electdco
Features / Funcionalidades Poveer Outlets / Tomas de Salida| EMI inputfilbr
505-UL 1705-UL 1905-UL – NEMA 120V| 6 x NEMAS-15R
Communication /ComunicaciOn| USB Port/ Puerto IJSB (optiona /opcional)
Software / Software| Supports/Compatible: Windows, Mac OSX, Linux, Unix
Dimensions/ Dimensiones| 279x101x142 mm
Net Weight / Peso Neto Unitaio| 3.6 Kg 4.3 Kg 4.9 Kg
Operating / Conditions de Operaciiiit| < 95%RH / 0-40°C / s 40 dBig 1m
Operating Altitude / Altura Operativa Packing / Empaque
Carton Information / Int ormadon Catkin| 0-2000m (Over sea level /Sobre el rivet del mar)
4 Tits per carton/ 4 unidades porcarton (3511c600Q60 mm)
Half Pallet Information /InformaciOn Medio Pallet| 96pcs/ 364Kg
120(100(113cm| 96pcs /432Kg 120x100x113cm| 96pcs/ 489Kg
120x100x113an
Full Pallet Information /Informacion Medio Pallet NV & Sthndards| 192pcs /729Kg
120(100)213cm| 192pcs/ 864Kg
120x100x213cm
UL1778 (certified by cTUVus)| 192pcs/979Kg
120x100x213cm
American
Conduction & Radiation| FCC Part 15 Class A
Quality & Erwiroment| RoHS /1S09001 & IS014001