taurus 956328000 Top Temp Connect Portable Air Conditioner User Manual
- June 12, 2024
- taurus
Table of Contents
- PORTABLE AIR CONDITIONER TOP TEMP CONNECT
- USE AND CARE
- INSTALLATION
- HOW TO USE
- IMPORTANT
- CLEANING
- ANOMALIES AND REPAIR
- INSTRUCTIONS FOR REPAIRING APPLIANCES CONTAINING R290
- COMPETENCE OF SERVICE PERSONNEL
- TRANSPORTATION, MARKING AND STORAGE FOR UNITS THAT EMPLOY FLAMMABLE
- CUSTOMER SUPPORT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
taurus 956328000 Top Temp Connect Portable Air Conditioner
PORTABLE AIR CONDITIONER TOP TEMP CONNECT
Please do not install or use your mobile air conditioner before you have carefully read this manual. Please keep this instructions manual for an eventual product warranty and for future reference.
- A On / Off
- B Temperature / Time +
- C Temperature / Time –
- D Cooling mode / dehumidifier / fan / heat
- E Fan speed
- F Timer
- G Display
- H Swing
- I Sleep mode
- J switching key
- K WIFI
- Top cover
- Control panel
- Air outlet louver
- Front housing
- Casters
- Rear housing
- Eva filter
- Continuous drainage hole
- Air vent
- Con filter
- Drainage hole
- Plug
- Exhaust pipe assembly
- Window sealing plate assembly
If the model of your appliance does not have the accessories described above, they can also be bought separately from the Technical Assistance Service.
USE AND CARE
- Before each use, completely unplug the power cable from the power supply.
- Use the handles to take or transport the appliance.
- Unplug the power supply from the mains when not in use and before performing any cleaning operations.
- Keep this appliance out of the reach of children and / or persons with reduced physical, sensory or mental abilities or who are unfamiliar with its use.
- Do not expose the appliance to extreme temperatures. Keep the device in a dry, dust-free place protected from direct sunlight. Never leave the appliance unattended. It will also save energy and prolong the life of the device.
INSTALLATION
- Respect the legal provisions regarding safety distances with other elements such as pipes, electric conductors, etc.
- Make sure the appliance is level with the floor
- Do not cover or obstruct any openings in the appliance.
- The plug must be easily accessible in order to disconnect it in case of emergency.
MOUNTING THE EXHAUST PIPE
- Stretch the tube, and screw its end to the air outlet connector. Follow figures 1,2,3,4.
- The length of the air outlet pipe conforms to the technical characteristics of the appliance. Do not use air outlet tubes of different sizes or materials, as they may cause faults.
HOW TO USE
USE:
- Unwind the cable completely before plugging in.
- Plug the appliance into the mains.
- Orient the appliance to direct the air flow to the desired direction.
- Switch the appliance on by pressing the On / Off button (A).
- Select the desired mode (D).
- Select desired speed (E).
WIFI CONNECTION & DOWNOADING THE APP:
- To be able to use the thermal transmitter Top Temp Connect from anywhere, the Taurus Connect App has to be downloaded.
SET UP:
- Download the Taurus Connect App form the App Store or Google Play.
- Sign up using your email address and password.
- Confirm the registration using the verification code that will be sent to your email account.
- Create your home, name it, establish the geographical location and select the room where you are going to place this smart appliance.
- Add Top Temp Connect by following the steps described in THE QUICK GUIDE.
IMPORTANT
- The device only supports 2.4GHz Wi-Fi network.
- If the connection fails again, check the following possible causes
- Top Temp Connect is too far away from the router.
- The Wi-Fi password is incorrect.
- The Wi-Fi network is not 2.4GHz
COLD MODE:
- Press mode to select cold mode, the cold mode indicator will light up.
- Press + or – to set the temperature in a range of 16~31°C.
- Pressing + or – once, the temperature will increase or decrease gradually.
- Press (E) to select high or low fan speed.
HEATING MODE:
- Press mode to select heating mode, the heating mode indicator will light up.
- Press + or – to set the temperature in a range of 16~31°C.
- Pressing + or – once, the temperature will increase or decrease gradually.
- Press (E) to select high or low fan speed.
FAN MODE:
- Press mode (D) to select the fan mode and the fan indicator will light up. Press (E) Speed to increase or decrease power speed.
DEHUMIDIFIER MODE:
- Press (D) to select the mode
- Dehumidification mode indicator, and the dehumidification mode indicator will light up.
TIMER FUNCTION:
SETTING THE TIMER ON:
- When the air conditioner is off, press the “F” button and select the desired power-on time through the temperature and time adjustment buttons.
- The on time can be set up to 24 hours.
- The programmed time or remaining time will appear in the display (G).
SETTING THE TIMER OFF:
- When the air conditioner is on, press the “F” button and select the desired sleep time through the temperature and time adjustment buttons.
- The shut-off time can be set up to 24 hours.
- The programmed time or remaining time will appear in the display (G).
COMPRESSOR PROTECTION:
- Three minutes after pressing on / restarting, the compressor will start to operate.
PROTECTION OF THE WATER TANK:
- When the water level in the lower water plate is below the warning level, the appliance will notify you automatically.
- Please pour the water in the machine according to the instructions in the chapter “water drainage”.
WATER DRAINAGE:
-
This machine has two drainage methods: manual drainage and continuous drainage (fig 5).
-
When the inside of the water tank is full, the indicator will light up on the display.
-
The device enters the standby mode.
-
Remove the plug to remove the water, turn the machine off and on again, the machine will operate normally.
-
This model has a self-evaporating function, in the cold mode, please do not make continuous drains to get a greater effect of cold.
ONCE THE APPLIANCE HAS BEEN USED:
- Stop the appliance by pressing button (A) on / off
- Unplug the appliance from the mains.
- Unplug the appliance from the mains and allow it to cool down before starting any cleaning operation.
- Clean the electrical assembly and the mains plug with a damp cloth and dry them afterwards. NEVER SUBMIT THEM IN WATER OR ANY OTHER LIQUID.
CLEANING
- Wipe the appliance with a damp cloth impregnated with a few drops of detergent. Do not use solvents or products with an acidic or basic pH factor such as bleach or abrasive products to clean the apparatus.
- Do not immerse the connector in water or other liquid or place it under the tap. If the appliance is not maintained in good condition.
CLEANING THE AIR FILTER:
-
Clean the air filters every 2 weeks. If the air filter is blocked with dust, its effectiveness will be reduced. Fig 6.
-
Washing the air filters by submerging them
-
Carefully in warm water with a neutral detergent, rinse them off and let them dry completely in a shady place.
-
Install the filters carefully after having them cleaned.
AFTER PERIODIC MAINTENANCE:
- Switch off the appliance and remove the plug.
- Separate the exhaust pipe from the air and store it carefully.
- Put the appliance in a dry place.
- Remove the batteries from the remote control and store them carefully.
ANOMALIES AND REPAIR
If any fault is detected, refer to the following table:
The appliance contains flammable refrigerant
Problems | Reasons | Solutions |
---|---|---|
The air conditioning does not work. | There is no electricity. | Turn it on |
after connecting it to a socket with electricity.
| The overflow indicator will light on/flash.| Discharge the water inside.
| The ambient temperature is too low or too high| Recommend to use the machine
in at the temperature of 7-35 °C (44-95 °F).
| In cooling mode, the room temperature is lower than the set temperature; in
heating mode, the room temperature is higher than the set temperature.| Change
the set temperature.
| In dehumidification mode, the ambient temperature is low.| The machine is
placed in a room with an ambient temperature of greater than 17 °C (62 °F).
The cooling effect is not good| There is direct sunlight.| Pull the Curtain.
Doors or windows are open; there are a lot of people; or in cooling mode,
there are other sources of heat.| Close doors and windows, and add new air
conditioning.
The filter screen is dirty.| Clean or replace the filter screen.
The air inlet or outlet is blocked.| Clear obstructions.
Big Noise| The air conditioning is not placed on a flat surface.| Put the air
conditioning on a flat and hard place (to reduce noise).
compressor does not work.| Frost production starts.| Wait for 3 minutes until
the temperature is lowered, and then restart the machine.
Overheat protection starts.
The remote control does not work.| The distance between the machine and the
remote control is too far.|
Let the remote control get close to the air conditioning, and make sure that the remote control directly faces to the direction of the remote control receiver.
The remote control is not aligned with the direction of the remote control
receiver.
Batteries are dead.| Replace batteries.
Displays ‘E1’.| The room temperature sensor failure.| Check the room
temperature sensor and related circuitry.
Displays ‘E2’| The pipe temperature sensor failure.| Check the pipe
temperature sensor and related circuitry.
INSTRUCTIONS FOR REPAIRING APPLIANCES CONTAINING R290
GENERAL INSTRUCTIONS
CHECKS TO THE AREA
- Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to con-ducting work on the system.
WORK PROCEDURE
- Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.
GENERAL WORK AREA
- All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
CHECKING FOR PRESENCE OFREFRIGERANT
- The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak section equipment being used is suitable for use with flammable refrigerants, i.e. non sparking, adequately sealed or intrinsically safe.
PRESENCE OF FIRE EXTINGUISHER
- If any hot work is to be conducted on the refrigeration equipment or any associated parts, propriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO 2 fire extinguisher adjacent to the charging area.
NO IGNITION SOURCES
- No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
VENTILATED AREA
- Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
CHECKS TO THE REFRIGERATION EQUIPMENT
- Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: the charge size is in accordance with the room size within which the refrigerant containing parts are installed; the ventilation machinery and outlets are operating adequately and are not obstructed; if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected; refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
CHECKS TO ELECTRICAL DEVICES
- Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
- Initial safety checks shall include: that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; that there no live electrical components and wiring are exposed while charging, recovering or purging the system; that there is continuity of earth bonding.
REPAIRS TO SEALED COMPONENTS
- During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
- Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected.
- This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
- NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
REPAIR TO INTRINSICALLY SAFE COMPONENTS
- Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.
CABLING
- Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
DETECTION OF FLAMMABLE REFRIGERANTS
- Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
LEAK DETECTION METHODS
- The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
REMOVAL AND EVACUATION
- When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: remove refrigerant; purge the circuit with inert gas; evacuate; purge again with inert gas; open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipework are to take place.
- Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
CHARGING PROCEDURES
- In addition to conventional charging procedures, the following requirements shall be followed.
- Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.
- Cylinders shall be kept upright.
- Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to overfill the refrigeration system.
- Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
DECOMMISSIONING
- Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that: mechanical handling
equipment is available, if required, for handling refrigerant cylinders; all
personal protective equipment is available and being used correctly; the
recovery process is supervised at all times by a competent person; recovery
equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can
be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery
takes place.
g) Start the recovery machine and operate in accordance with
manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j) When the cylinders have been filled correctly and the process
completed, make sure that the cylinders and the equipment are removed from
site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration
system unless it has been cleaned and checked.
LABELLING
- Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed.
- Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
RECOVERY
- When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
- The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
- The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
COMPETENCE OF SERVICE PERSONNEL
GENERAL
- Special training additional to usual refrigerating equipment repair procedures is required when equipment with flammable refrigerants is affected.
- In many countries, this training is carried out by national training organizations that are accredited to teach the relevant national competency standards that may be set in legislation.
- The achieved competence should be documented by a certificate.
TRAINING
- The training should include the substance of the following:
- Information about the explosion potential of flammable refrigerants to show that flammables may be dangerous when handled without care.
- Information about potential ignition sources, especially those that are not obvious, such as lighters, light switches, vacuum cleaners, electric heaters.
- Information about the different safety concepts:
- Unventilated – (see Clause GG.2) Safety of the appliance does not depend on ventilation of
- the housing. Switching off the appliance or opening of the housing has no significant effect on the safety. Nevertheless, it is possible that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure is opened.
- Ventilated enclosure – (see Clause GG.4) Safety of the appliance depends on ventilation of
- the housing. Switching off the appliance or opening of the enclosure has a significant effect
- on the safety. Care should be taken to ensure a sufficient ventilation before.
- Ventilated room – (see Clause GG.5) Safety of the appliance depends on the ventilation of
- the room. Switching off the appliance or opening of the housing has no significant effect on
- the safety. The ventilation of the room shall not be switched off during repair procedures.
- Information about the concept of sealed components and sealed enclosures according to IEC 60079-15:2010.
- Information about the correct working procedures:
COMMISSIONING
- Ensure that the floor area is sufficient for the refrigerant charge or that the ventilation duct is assembled in a correct manner.
- Connect the pipes and carry out a leak test before charging with refrigerant.
- Check safety equipment before putting into service.
MAINTENANCE
- Portable equipment shall be repaired outside or in a workshop specially equipped for servicing units with flammable refrigerants.
- Ensure sufficient ventilation at the repair place.
- Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrigerant leak is possible.
- Discharge capacitors in a way that won’t cause any spark. The standard procedure to short circuit the capacitor terminals usually creates sparks.
- Reassemble sealed enclosures accurately. If seals are worn, replace them.
- Check safety equipment before putting into service.
REPAIR
- Portable equipment shall be repaired outside or in a workshop specially equipped for servicing units with flammable refrigerants.
- Ensure sufficient ventilation at the repair place.
- Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrigerant leak is possible.
- Discharge capacitors in a way that won’t cause any spark.
- When brazing is required, the following procedures shall be carried out in the right order:
- Remove the refrigerant. If the recovery is not required by national regulations, drain
- the refrigerant to the outside. Take care that the drained refrigerant will not cause any danger. In doubt, one person should guard the outlet. Take special care that drained refrigerant will not float back into the building.
- Evacuate the refrigerant circuit.
- Purge the refrigerant circuit with nitrogen for 5 min.
- Evacuate again.
- Remove parts to be replaced by cutting, not by flame.
- Purge the braze point with nitrogen during the brazing procedure.
- Carry out a leak test before charging with refrigerant.
- Reassemble sealed enclosures accurately. If seals are worn, replace them.
- Check safety equipment before putting into service.
DECOMMISSIONING
- If the safety is affected when the equipment is putted out of service, the refrigerant charge shall be removed before decommissioning.
- Ensure sufficient ventilation at the equipment location.
- Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrigerant leak is possible.
- Discharge capacitors in a way that won’t cause any spark.
- Remove the refrigerant. If the recovery is not required by national regulations, drain the refrigerant to the outside. Take care that the drained refrigerant will not cause any danger. In doubt, one person should guard the outlet. Take special care that drained refrigerant will not float back into the building.
- Evacuate the refrigerant circuit.
- Purge the refrigerant circuit with nitrogen for 5 min.
- Evacuate again.
- Fill with nitrogen up to atmospheric pressure.
- Put a label on the equipment that the refrigerant is removed.
DISPOSAL
- Ensure sufficient ventilation at the working place.
- Remove the refrigerant. If the recovery is not required by national regulations, drain the refrigerant to the outside. Take care that the drained refrigerant will not cause any danger. In doubt, one person should guard the outlet. Take special care that drained refrigerant will not float back into the building.
- Evacuate the refrigerant circuit.
- Purge the refrigerant circuit with nitrogen for 5 min.
- Evacuate again.
- Cut out the compressor and drain the oil.
TRANSPORTATION, MARKING AND STORAGE FOR UNITS THAT EMPLOY FLAMMABLE
REFRIGERANTS
TRANSPORT OF EQUIPMENT CONTAINING FLAMMABLE REFRIGERANTS
- Attention is drawn to the fact that additional transportation regulations may exist with respect to equipment containing flammable gas. The maximum number of pieces of equipment or the configuration of the equipment, permitted to be transported together will be determined by the applicable transport regulations.
MARKING OF EQUIPMENT USING SIGNS
- Signs for similar appliances used in a work area generally are addressed by local regulations and give the minimum requirements for the provision of safety and/or health signs for a work location.
- All required signs are to be maintained and employers should ensure that employees receive suitable and sufficient instruction and training on the meaning of appropriate safety signs and the actions that need to be taken in connection with these signs.
- The effectiveness of signs should not be diminished by too many signs being placed together.
- Any pictograms used should be as simple as possible and contain only essential details.
DISPOSAL OF EQUIPMENT USING FLAMMABLE REFRIGERANTS
- See national regulations.
STORAGE OF EQUIPMENT/APPLIANCES
- The storage of equipment should be in accordance with the manufacturer’s instructions.
- Storage of packed (unsold) equipment
- Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge.
- The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
CUSTOMER SUPPORT
COUNTRY | ADDRESS | PHONE |
---|---|---|
Algeria | Zone d’Activite, Nº 62, Constantine | 213770777756 |
Argentina | Av. del Libertador 1298,(B1638BEY), Vicente López (Pcia. | |
Buenos Aires) | 541153685223 | |
Belgium | Mariëndonkstraat 5, 5154 EG, Elshout | 31620401500 |
Benin | 359 Av. Steinmetz, 1930, Cotonou | 0299-21313798 |
Bulgaria | 265,Okolovrasten Pat, Mladost 4, 1766, Sofia | 35929211120 / |
35929211193
Burkina Faso| Avenue Bassawarga, 01 BP915, Ouagadougou| 226 25301038
Congo (Republic of)| 98 Blvd General Charles de Gaulle, Pointe Noire|
242066776656
Cyprus| 20, Bethlehem Str. / P.O.Box 20430, 2033, Strovolos| 35722711300
Czech Republic| Milady Horakove 357/4, 568 02, Svitavy| 420 461 540 130
Democratic Republic
of the Congo
| AV. Pont Canale Nº 3440, Kinshasa| 00243-991223232
Equatorial Guinea| SN Av Patricio Lumumba y C/ Jesus B, Bata| 00240 333
082958 / 00240 333 082453
Equatorial Guinea| Calle de las Naciones Unidas, PO box 762, Malabo|
240333082958 / 240333082453
España| Avda Barcelona, S/N, 25790 Oliana (Lleida)
atencioncliente@taurus.es| 902 118 050
Ethiopia| Lideta Sub City Kebele 10 H.NO 124, Addis Ababa| +251 11
5518300
France| Za les bas musats 18, 89100, Malay-le-Grand| 03 86 83 90 90
Gabon| BP 574, Port-Gentil Centre-ville| 24101552689 / 24101560698
Ghana| Ederick Place, Accra-Ghana| 302682448 / 302682404
Gibraltar| 11 Horse Barrack Lane, 54000, Gibraltar| 00350 200 75397 /
00350 200
41023
Greece| Sapfous 7-9, 10553, Athens| +30 21 0373 7000
Guinea| BP 206, GN, Conakry| (224) 622204545
Hong Kong| Unit H,13/F., World Tech Centre, Hong kong| (852) 2448 0116 /
9197 3519
Hungary| Késmárk utca 11-13, 1158, Budapest| +36 1 370 4519
India| C-175, Sector-63, Noida, Gautam Budh Nagar – 201301, Delhi| (+91)
120 4016200
Ivory Coast| 01 Rue Des Carrossiers-Zone 3, B.P 3747, Abidjan 01 (RCI)|
22521251820 / 225 21 353494
Jordan| 28 Basman St Down town, Amman| +962 6 46 222 68
Kuwait| P.O. BOX 3379 hawally, 32034, Hawally| +965 2200 1010
Lebanon| Damascus Highway; Sciale Building, Jamhour| 9615922963
Luxembourg| Mariëndonkstraat 5, 5154 EG, Elshout| 31620401500
Mali| BP E2900, Dravela Bolibana| 223227216 / 223227259
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>