User Guide
Slim CPU (PLC) Module with Digital Input & Transistor Output
SPL3P1-02-00-03-00_1
SPP3P1-30-00-51-00_1
General Specifications
-
Program Memory Area : 196K
Volatile Memory Area: 27K -
9 pieces Digital Input ( NPN / PNP)
-
6 pieces Digital Output (Active High)
-
Ethernet 10/100 Mbit
Easy access via the Internet with WEB QUICK CONNECT
Module access via Web Browser with IPERTU SCADA -
Modbus RTU communication protocol with RS232
-
Modbus RTU communication protocol with RS485
-
USB – Device (For device configuration)
-
Modular connection (up to 16 extension modules can be connected)
-
Led indicators:
– RUN, USB, RS-485
– Active Input led indicators
– Active Output led indicators
Technical Specifications
Volatile Memory Area Map
Volatile Memory Area Modbus Slave Addresses
Specific Bit Memory Area Definitions
Specific Data Memory Area Definitions
Installation & Wiring
* Do not connect AC Power to any I/O terminal, otherwise serious damage may occur in module. Please check all wiring prior to energizing device. In order to prevent electromagnetic interference, be sure the grounding made corrected. Connect ground terminal in the power input connector to the overall system ground. Don’t touch any terminals after energizing the device, in case of need to touch any terminal, de-energize the device before connection.
* For digital input connections; In case of using encoder, as fast counter, use the encoders original cables. Keep the cables away from power cables in order to prevent electrical interference. Ground the encoders screen cables to device ground.
* For Fast Digital Input counter (encoder) connections; For HSCO I0 = A, I1 = B; For HSC1 I3 = A, I4 = B and For HSC2 I6 = A, I7 = B
* For RS232 communication connection; Use shielded communication cable and ground the shield conncection to power input earth terminal.
* For RS485 communication connection; Connect the termination resistor (120R) between A & B terminal of the CPU (PLC) module, connected left of the extension module group. In case of more than one module group, connect it between the A & B terminals of the CPU (PLC) module, connected left of the extension module group, at the end of the communication line. Use shielded and twisted-pair communication cable. Ground the shield connection of the cable to power input earth terminal.