EMKO 60W Power Supply Module Instructions

June 20, 2024
EMKO

EMKO 60W Power Supply Module

Product Information

Specifications:

  • Model : IPERTU-MPS060-00-00-00-00_1
  • Input Voltage Range: 100-240 VAC (-%15 + %10) 50/60 Hz
  • Efficiency : > 84%
  • Inrush Current: max 33A @ 230 VAC
  • Leakage Current: max 2.5mA
  • Rated Power: 60W 2.5A @ 24 VDC
  • Ripple : 300 mVpp max
  • Load Regulation: < %1.5
  • Line Regulation: < %1.5
  • Start-Up Time: 1200ms/230VAC
  • Hold Up Time: 100ms/230VAC
  • Protections:
    • Overload Protection: %140
    • Short Circuit Protection: Auto-recovery after the error disappears.
    • Thermal Protection
  • Operation Temp.
  • Protection Class: IP20
  • Pollution Degree: 2
  • Isolation:
    • 3000 VAC isolation between Input and Output
    • 1500 VAC isolation between Input and Earth
    • 500 VAC isolation between Output and Earth
  • Dimensions (WHD): 5010070 mm
  • Weight : 230 gr

Product Usage Instructions

Installation & Wiring:
Please check all wiring prior to energizing the device. To prevent electromagnetic interference, ensure correct grounding. Connect the ground terminal in the power input connector to the overall system ground. Avoid touching any terminals after energizing the device. If there is a need to touch any terminal, de-energize the device before making the connection.

Dimensions:
The product dimensions are 50mm (width) x 100mm (height) x 70mm (depth).

General Specifications

  • Universal Input Voltage 100-240 VAC (-15% .. +10%) 50/60 Hz
  • 24VDC (±%10) Adjustable Output Voltage
  • 2,5 A / 60 W @ 24 VDC
  • Active Output Led indicator
  • Can be connected to other IPERTU modules over IPERTU BUS without cable connection (must be connected to left of the modules connected to the IPERTU BUS)

Electrical Specifications

Input

Input Voltage Range| 100-240 VAC (-%15 + %10) 50/60 Hz
Efficiency| > 84%
Inrush Current| max 33A @ 230 VAC
Leakage Current| max 2.5mA
Output
Rated Power| 60W 2,5 A @ 24 VDC
Adj. Voltage Range| 24 VDC (±%10) Can be adjusted with Trimpot in the given range.
Ripple| 300 mVpp max
Load Regulation| < %1,5
Line Regulation| < %1,5
Start Up Time| 1200ms/230VAC
Hold Up Time| 100ms/230VAC
Protections
Overload Protection| % 140
Short Circuit Protect.| Auto-recovery after error disappears.
Thermal Protection| When the ambient temperature rises above 55 °C, the output voltage reduced depending on ambient temperature and load current.
Operation / Storage Environment
Operation Temp.| -20..+50 °C
Storage Temperature| -30..+75 °C
Protection Class| IP20
Pollution Degree| 2


İsolation

| *  3000 VAC isolation between Input and Output

*  1500 VAC isolation between Input and Earth

*  500 VAC isolation between Output and Earth

Dimensions (WHD)| 5010070 mm
Weight| 230 gr
Indıcators
Output| Output Led is ON when the output is in rated limits.

Installation & Wiring

Please check all wiring prior to energizing device. In order to prevent electromagnetic interference, be sure the grounding made corrected. Connect ground terminal in the power input connector to the overall system ground. Don’t touch any terminals after energizing the device, in case of need to touch any terminal, de-energize the device before connection.

Dimensions

FAQ

Q: What should I do if the output LED is not ON?
A: If the output LED is not ON, ensure that the output is within rated limits and check the wiring connections.

Q: How can I reset the device after a short circuit error?
A: The short circuit protection feature of the device allows for auto-recovery after the error disappears. Once the error is resolved, the device will resume normal operation.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals