DSE9460 Amp Enclosed Intelligent Battery Charger Instruction Manual

June 13, 2024
DSE

DEEP SEA ELECTRONICS
SE9460 & DSE9461
INSTALLATION INSTRUCTIONS

053-147
ISSUE 4

INSTALLATION

The battery chargers are wall mounted via four holes on the back of the enclosure. Dimension and mounting details are given overleaf.
The battery charger is fit-and-forget. It can be permanently connected to the supply and the load, with no requirement to disable the charger during times of heavy load (such as engine cranking) or when in parallel with a charging alternator.

BATTERY SUITABILITY

The battery charger is factory set by DSE to suit Lead Acid batteries but can be adjusted to suit other battery types using the Configuration Suite PC Software.
Care must be taken to ensure the batteries connected to the charger are of the correct ‘technology’ to suit the setting of the charger.
INDICATIONS
The Battery Charger features an LCD display and depending on the variant, additional voltage and current meters may be fitted.
BOOST MODE
Boost mode is operated automatically or by activation of the digital input (if configured to perform this function). This raises the battery charger voltage to the boost voltage setting.

ACCESSING THE FRONT PANEL EDITOR

  • The Front Panel Editor (FPE) is accessed by pressing and holding the ( ) button.
  • Press the (up) or (down) button to cycle through the Adjustable Parameters listed overleaf.
  • Press the ( ) button to edit a parameter when it is being viewed on the screen. The value flashes to show edit mode is in progress.
  • Press the (+) or (-) button to change the parameter to the required value.
  • Press the v( ) button to save the currently selected value. The value ceases flashing to show editing is complete.
  • Press and hold the ( ) button to exit the editor

ADJUSTABLE PARAMETERS

NOTE: On later versions of the DSE2541 display, only parameters 100 to 108 are available for configuration.

Index Parameter Value
100 Contrast 0%
101 Temperature Units ° C, ° F
102 Slave ID 1 to 255
103 Baud Rate 4800 to 115200
104 Enable Alarm Popup Scree Enable, Disable
105 Home Page Configuration 0 to 8 (Home Page List)
106 Home Page Timeout 0 s
107 Sleep Mode Timeout 0 s
108 Enable Engineering Page Enable, Disable

Parameter 105 – Home Page Configuration has the following possible selections:

Value Home Page List
0 Analogue Meters
1 Output Voltage And Current
2 Output Power And Battery Charger Temperature
3 Battery Sensed Voltage And Battery Temperature
4 Mains AC Voltage And Frequency
5 Battery Charger Model And Charger Software Version
7 Control Page
8 Alarms Page

DISPLAY LED INDICATIONS

DSE9460 Amp Enclosed Intelligent Battery Charger -
INDICATIONS

CHARGER STATUS

Condition LED State
Charger Off Off
Charger On On

FAULT STATUS

Condition LED State
No Fault Off
Warning Fault On
Shutdown Fault Flashing

BOOST MODE

Condition LED State
Charger Off Off
Charger On On

DIMENSIONS AND MOUNTING

DSE9460 Amp Enclosed Intelligent Battery Charger -DIMENSIONS AND
MOUNTING

Parameter Comment
Cabinet Type Custom cabinet for indoor use only
Overall Size 165 mm X 305 mm X 110 mm (6.5 ” X 12.0 ” X 4.3 ”)
Material Sheet steel enclosure of allround solid construction
Surface Finish Powder-coated black
Protection Category IP20, NEMA 1
Weight 2.3 kg  (5 lb 1 oz)
Mounting Type Wall mounted with terminals to bottom.
Mounting Holes Diameter 6 mm (0.2 ”) 63 mm X 284 mm (3.4 ” x 11.2 ”) centres
Operating Temperature (With Deratings -30 °C to +80 °C (-22 °F to +176 °F)

REQUIREMENTS FOR UL CERTIFICATION

Parameter Comment
Screw Terminal Tightening Torque 4.5 lb-in (0.5 Nm)
Conductors • Terminals suitable for connection of conductor size 12 AWG – 26

AWG (0.5 mm² to 2.0 mm²).
• Conductor protection must be provided in accordance with NFPA 70, Article 240
• Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to maintain at least ¼” (6 mm) separation from the generator and mains connected circuit conductors unless all conductors are rated 600 V or greater.
Communication Circuits| Must be connected to communication circuits of UL Listed equipment
Mounting| • Suitable for use in type 1 Enclosure Type rating with surrounding air temperature -22 ºF to +131 ºF (-30 ºC to +55 ºC)
• Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V device to be installed in an unventilated or filtered ventilation enclosure to maintain a pollution degree 2 environment.
Operating Temperature| -22 ºF to +131 ºF (-30 ºC to +55 ºC)
Storage Temperature| -40 ºF to +176 ºF (-40 ºC to +80 ºC)

TYPICAL WIRING DIAGRAM

DSE9460 Amp Enclosed Intelligent Battery Charger NOTE 1
A 120 OHM TERMINATION RESISTOR MUST 8E FITTED IF IT [S THE FIRST OR LAST DEVICE ON AN RS485 LINK
NOTE 2

AC INPUT ANTI-SURGE FUSE RATING
110v 6.3A
230V 3.5A

FUSE APPROPRIATELY WHEN CURRENT LIMIT IS CONFIGURED BELOW 10A AND AS CLOSE TO THE BATTER CHARGER AS POSSIBLE TO PROTECT THE CABLES
NOTE 3
FACTORY FITTED WTH 6.3A ANTI-SURGE FUSE, FUSE APPROPRIATELY
NOTE 4
FUSE APPROPRIATELY AND AS CLOSE TO THE BATTERY AS POSSIBLE TO PROTECT THE CABLES AND BATTERY

DANGER OF DEATH: LIVE PARTS exist within the enclosure. The enclosure cover must not be removed when connected to an AC supply

Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
Email: [email protected]
Web: www.deepseaplc.com
Deep Sea Electronics Inc.
Tel: +1 (815) 316 8706
Fax: +1 (815) 316 8708
Email: [email protected]
Web: www.deepseausa.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

DSE User Manuals

Related Manuals