DSE9460 Amp Enclosed Intelligent Battery Charger Instruction Manual
- June 13, 2024
- DSE
Table of Contents
DEEP SEA ELECTRONICS
SE9460 & DSE9461
INSTALLATION INSTRUCTIONS
053-147
ISSUE 4
INSTALLATION
The battery chargers are wall mounted via four holes on the back of the
enclosure. Dimension and mounting details are given overleaf.
The battery charger is fit-and-forget. It can be permanently connected to the
supply and the load, with no requirement to disable the charger during times
of heavy load (such as engine cranking) or when in parallel with a charging
alternator.
BATTERY SUITABILITY
The battery charger is factory set by DSE to suit Lead Acid batteries but can
be adjusted to suit other battery types using the Configuration Suite PC
Software.
Care must be taken to ensure the batteries connected to the charger are of the
correct ‘technology’ to suit the setting of the charger.
INDICATIONS
The Battery Charger features an LCD display and depending on the variant,
additional voltage and current meters may be fitted.
BOOST MODE
Boost mode is operated automatically or by activation of the digital input (if
configured to perform this function). This raises the battery charger voltage
to the boost voltage setting.
ACCESSING THE FRONT PANEL EDITOR
- The Front Panel Editor (FPE) is accessed by pressing and holding the ( ) button.
- Press the (up) or (down) button to cycle through the Adjustable Parameters listed overleaf.
- Press the ( ) button to edit a parameter when it is being viewed on the screen. The value flashes to show edit mode is in progress.
- Press the (+) or (-) button to change the parameter to the required value.
- Press the v( ) button to save the currently selected value. The value ceases flashing to show editing is complete.
- Press and hold the ( ) button to exit the editor
ADJUSTABLE PARAMETERS
NOTE: On later versions of the DSE2541 display, only parameters 100 to 108 are available for configuration.
Index | Parameter | Value |
---|---|---|
100 | Contrast | 0% |
101 | Temperature Units | ° C, ° F |
102 | Slave ID | 1 to 255 |
103 | Baud Rate | 4800 to 115200 |
104 | Enable Alarm Popup Scree | Enable, Disable |
105 | Home Page Configuration | 0 to 8 (Home Page List) |
106 | Home Page Timeout | 0 s |
107 | Sleep Mode Timeout | 0 s |
108 | Enable Engineering Page | Enable, Disable |
Parameter 105 – Home Page Configuration has the following possible selections:
Value | Home Page List |
---|---|
0 | Analogue Meters |
1 | Output Voltage And Current |
2 | Output Power And Battery Charger Temperature |
3 | Battery Sensed Voltage And Battery Temperature |
4 | Mains AC Voltage And Frequency |
5 | Battery Charger Model And Charger Software Version |
7 | Control Page |
8 | Alarms Page |
DISPLAY LED INDICATIONS
CHARGER STATUS
Condition | LED State |
---|---|
Charger Off | Off |
Charger On | On |
FAULT STATUS
Condition | LED State |
---|---|
No Fault | Off |
Warning Fault | On |
Shutdown Fault | Flashing |
BOOST MODE
Condition | LED State |
---|---|
Charger Off | Off |
Charger On | On |
DIMENSIONS AND MOUNTING
Parameter | Comment |
---|---|
Cabinet Type | Custom cabinet for indoor use only |
Overall Size | 165 mm X 305 mm X 110 mm (6.5 ” X 12.0 ” X 4.3 ”) |
Material | Sheet steel enclosure of allround solid construction |
Surface Finish | Powder-coated black |
Protection Category | IP20, NEMA 1 |
Weight | 2.3 kg (5 lb 1 oz) |
Mounting Type | Wall mounted with terminals to bottom. |
Mounting Holes | Diameter 6 mm (0.2 ”) 63 mm X 284 mm (3.4 ” x 11.2 ”) centres |
Operating Temperature (With Deratings | -30 °C to +80 °C (-22 °F to +176 °F) |
REQUIREMENTS FOR UL CERTIFICATION
Parameter | Comment |
---|---|
Screw Terminal Tightening Torque | 4.5 lb-in (0.5 Nm) |
Conductors | • Terminals suitable for connection of conductor size 12 AWG – 26 |
AWG (0.5 mm² to 2.0 mm²).
• Conductor protection must be provided in accordance with NFPA 70, Article
240
• Low voltage circuits (35 V or less) must be supplied from the engine
starting battery or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit conductors shall
be separated and secured to maintain at least ¼” (6 mm) separation from the
generator and mains connected circuit conductors unless all conductors are
rated 600 V or greater.
Communication Circuits| Must be connected to communication circuits of UL
Listed equipment
Mounting| • Suitable for use in type 1 Enclosure Type rating with surrounding
air temperature -22 ºF to +131 ºF (-30 ºC to +55 ºC)
• Suitable for pollution degree 3 environments when voltage sensing inputs do
not exceed 300 V. When used to monitor voltages over 300 V device to be
installed in an unventilated or filtered ventilation enclosure to maintain a
pollution degree 2 environment.
Operating Temperature| -22 ºF to +131 ºF (-30 ºC to +55 ºC)
Storage Temperature| -40 ºF to +176 ºF (-40 ºC to +80 ºC)
TYPICAL WIRING DIAGRAM
NOTE 1
A 120 OHM TERMINATION RESISTOR MUST 8E FITTED IF IT [S THE FIRST OR LAST
DEVICE ON AN RS485 LINK
NOTE 2
AC INPUT | ANTI-SURGE FUSE RATING |
---|---|
110v | 6.3A |
230V | 3.5A |
FUSE APPROPRIATELY WHEN CURRENT LIMIT IS CONFIGURED BELOW 10A AND AS CLOSE TO
THE BATTER CHARGER AS POSSIBLE TO PROTECT THE CABLES
NOTE 3
FACTORY FITTED WTH 6.3A ANTI-SURGE FUSE, FUSE APPROPRIATELY
NOTE 4
FUSE APPROPRIATELY AND AS CLOSE TO THE BATTERY AS POSSIBLE TO PROTECT THE
CABLES AND BATTERY
DANGER OF DEATH: LIVE PARTS exist within the enclosure. The enclosure cover must not be removed when connected to an AC supply
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
Email: support@deepseaplc.com
Web: www.deepseaplc.com
Deep Sea Electronics Inc.
Tel: +1 (815) 316 8706
Fax: +1 (815) 316 8708
Email: support@deepseausa.com
Web: www.deepseausa.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>