HYFIRE TAU-MC-01-BL Taurus Multi Sensor Detector Instruction Manual
- October 30, 2023
- Hyfire
Table of Contents
TAU-MC-01-BL Taurus Multi Sensor Detector
Instruction Manual
GENERAL DESCRIPTION
The TAU-MC-01-BL Taurus series detector samples the air and the environmental temperature in the protected area; when the environmental smoke quantity, the temperature level or the thermal variation rate exceeds a certain degree, a fire alarm message is sent to the control panel. TAU-MC-01-BL is battery powered and doesn’t need any system cabling installation.
All pictures are for product in black variant. Shown white for illustrative purpose only
- LED indicators
- Battery A
- Battery B
- Link program switch
- Tamper spring (internal)
- Tamper switch (external)
- Battery cover
- Battery cover latch
- Insulating tab
- Wall fixing openings
- Identification tag
- Identification tag lodgement
- Magnet test area
- Base/detector reference marks
- Safety screw
DEPLOYMENT PROCEDURE
-
Select a location for the detector. See LOCATION SELECTION.
-
Unbox the detector from its packaging.
-
Detach the detector from its base. See INSTALLING / REMOVING THE DETECTOR
-
Detach the battery cover from the detector. See BATTERY COVER.
-
- a) Link the detector to the system (insulating tab extraction).
See LINKING – WAKE-UP – WITH INSULATING TAB.
See LINKING – ONE-BY-ONE – WITH INSULATING TAB.
— or —
5. 2) a) Power up the detector.
See POWERING UP – FIRST TIME USE – WITHOUT INSULATING TAB.
See POWERING UP – RECOVERY.
b) Link the detector to the system (moving the link program switch).
See LINKING – WAKE-UP – WITHOUT INSULATING TAB.
See LINKING – ONE-BY-ONE – WITHOUT INSULATING TAB.
- a) Link the detector to the system (insulating tab extraction).
-
Reinstall the battery cover on the detector. See BATTERY COVER.
-
Detach the identification tag from the base adapter. See IDENTIFYING THE DETECTOR.
-
Install the base adapter. See FIXING THE ADAPTOR BASE.
-
Install the detector on the base adapter. See INSTALLING / REMOVING THE DETECTOR.
-
Install the identification tag to the base adapter, with all relevant information written / labelled on it. See IDENTIFYING THE DETECTOR.
-
Secure the detector to its base with its safety anti-tamper screw. See INSTALLING THE SAFETY SCREW.
-
Test the detector. See TESTING.
Dust covers DO NOT provide complete protection against contamination:
detectors should be removed before construction, major re-decoration or other
dust producing work is started.
Dust covers MUST be removed before the system can be made operational.
LOCATION SELECTION
Select a location for the detector that conforms to your local applicable
safety standards and that is in a good position for sending / receiving
wireless signals to / from the father TAU-TRM-01, TAU-CEM-01 or TAU-EXM-01
network device.
Mount the detector as far as possible from metal objects, metal doors, metal
window openings, etc. as well as cable conductors, cables (especially from
computers), otherwise the operating distance may greatly drop.
The TAU-MC-01-BL must NOT be installed near electronic devices and computer
equipment that can interfere with its wireless communication quality.
It is advisable to use the TAU-STK-01 survey kit to locate a good wireless
installation location.
BATTERY COVER
Detach the battery cover by pulling and lifting the closing latch.
To reinstall the battery cover, insert its two hooks into their corresponding
detector’s recesses; then block it by pressing down the opposite side, until
you hear the click of the closing latch.
Always install the battery cover, since it is a vital part of the tamper
detection feature. Make sure the battery cover is safely fixed, blocked and
closed. Make sure that the internal tamper spring fits completely into its
battery cover’s lodgement. Check, more than once, that the cover’s external
tamper switch clicks when pressed.
INSTALLING / REMOVING THE DETECTOR **
**
Rotate the detector clockwise on its adaptor base to install it. Rotate the
detector anti-clockwise from its adaptor base to remove it.
Check the alignment of the raised reference marks on the detector and on the
base.
IDENTIFYING THE DETECTOR
The detector can be visually identified by the detachable tag imprinted
with the adaptor base.
- Detach the tag from the base.
- Write / label the relevant identification information on the tag.
- Insert the tag into its lodgement on the side of the adaptor base.
FIXING THE ADAPTOR BASE
Fix the base to the wall with suitable screws.
Always install the safety blocking screw.
INSTALLING THE SAFETY SCREW
Always install the safety blocking screw.
Please mind that LED Signalling burns out battery power, therefore reducing
batteries lifespan.
LED INDICATORS STATUS MESSAGES
The two LED indicators communicate to the final user the status of the TAU-
MC-01-BL.
Table 1
Device status | LEDs indication |
---|---|
Power up (DIP on “ON”) | Blinks red 4 times |
Power up (DIP opposite “ON”) | Blinks green 4 times |
Entering wake-up mode | Blinks alternatively green / red 4 times |
Link success (one-by-one) | Blinks green 4 times, then the same pattern again |
Link failure (one-by-one) | Enters wake-up mode and signals “Entering wake-up |
mode” following this failure
Link success (wake-up)| Blinks green 4 times, then same pattern again
Link failure (wake-up)| Blinks green 4 times, then blinks red on once, then
blinks alternatively green / red 4 times
Normal condition| LED off (can be programmed so as to blink green every
wireless communication)
Alarm activation| Blinks red every 2 seconds
Battery fault| LED off (can be programmed so as to blink amber every 5
seconds)
Tamper fault| LED off
Replaced| Blinks amber 2 times
Test mode active| Blinks green
POWERING UP AND LINKING – PRELIMINARY NOTES
TAU-MC-01-BL needs to be powered up with the supplied batteries.
Linking is the operation through which TAU-MC-01-BL is “wirelessly connected”
to a TAU-TRM-01, TAU-CEM-01 or TAU-EXM-01 Taurus network device.
LINKING – WAKE-UP – WITH INSULATING TAB
“Wake-up” linking consists in associating one or more child devices to the
Taurus system altogether in a single operation.
Wake-up is performed either through the TauREX software or the TAU-TRM-01 /
TAU-CEM-01 keyboard-screen interface; it CANNOT be done through TAU-EXM-01
devices.
- Create the “virtual model” of the TAU-MC-01-BL either on TauREX or on the TAU-TRM-01 / TAU-CEM-01.
- Pull out the insulating tab.
- Trigger the wake-up procedure either from TauREX or from the TAU-TRM-01 / TAU-CEM-01.
- Wait the end of the “wake-up” linking procedure.
- Check on TauREX or from TAU-TRM-01 / TAU-CEM-01 for linking success. Consult their user manual.
LINKING – ONE-BY-ONE – WITH INSULATING TAB
“One-by-one” linking consists in associating one child device at a time to
the Taurus system.
This operation is performed either through the TauREX software or the TAU-
TRM-01 / TAU-CEM-01 keyboard-screen interface; it CANNOT be done through TAU-
EXM-01 devices.
- Create the “virtual model” of the TAU-MC-01-BL either on TauREX or on the TAU-TRM-01 / TAU-CEM-01.
- Trigger the linking procedure either from TauREX or from the TAU-TRM-01 / TAU-CEM-01.
- Pull out the insulating tab.
- Wait the end of the “one-by-one” linking procedure.
- Check on TauREX or from TAU-TRM-01 / TAU-CEM-01 for linking success. Consult their user manual.
When extracting the insulating tab, keep both batteries into their
lodgements with your thumb, since they can be accidentally pulled out too.
POWERING UP – FIRST TIME USE – WITHOUT INSULATING TAB
Use this procedure the first time you power up a TAU-MC-01-BL; the detector
has not been supplied with the insulating tab.
- Make sure the Link / program switch is set on “ON”.
- Insert the two supplied batteries into their device’s lodgments.
POWERING UP – DEVICE LINKED TO THE SYSTEM
Use this procedure when a TAU-MC-01-BL is successfully linked to its Taurus
system and you have to extract one or both batteries (batteries substitution).
- Reinsert the battery or both batteries into their lodgments.
If performing a batteries substitution, use two brand new batteries and
substitute both of them. Do not touch the Link/program switch.
POWERING UP – RECOVERY
Use this procedure when you fail to link successfully a TAU-MC-01-BL or you
want to link it again.
- Move alternatively the Link / program switch 5 times.
- Set the Link / program switch on “ON”.
- Insert the two supplied batteries into their device’s lodgments.
Always ensure that the batteries are installed properly, with their
polarities matching the indications on the device.
LINKING – WAKE-UP – WITHOUT INSULATING TAB
“Wake-up” linking consists in associating one or more child devices to the
Taurus system altogether in a single operation.
Wake-up is performed either through the TauREX software or the TAU-TRM-01 /
TAU-CEM-01 keyboard-screen interface; it CANNOT be done through TAU-EXM-01
devices.
- Create the “virtual model” of the TAU-MC-01-BL either on TauREX or on the TAU-TRM-01 / TAU-CEM-01.
- Power-up the detector (either “first time use” or “recovery”).
- Set the Link / program switch OPPOSITE to “ON”.
- Trigger the wake-up procedure either from TauREX or from the TAU-TRM-01 / TAU-CEM-01.
- Wait the end of the “wake-up” linking procedure.
- Check on TauREX or from TAU-TRM-01 / TAU-CEM-01 for linking success. Consult their user manual.
LINKING – ONE-BY-ONE – WITHOUT INSULATING TAB
“One-by-one” linking consists in associating one child device at a time to
the Taurus system.
This operation is performed either through the TauREX software or the TAU-
TRM-01 / TAU-CEM-01 keyboard-screen interface; it CANNOT be done through TAU-
EXM-01 devices.
- Create the “virtual model” of the child device either on TauREX or on the TAU-TRM-01 / TAU-CEM-01.
- Trigger the linking procedure either from TauREX or from the TAU-TRM-01 / TAU-CEM-01.
- Power-up the child device (either “first time use” or “recovery”).
- Set the child device’s Link / program switch OPPOSITE to “ON”.
- Wait the end of the “one-by-one” linking procedure.
- Check on TauREX or from TAU-TRM-01 / TAU-CEM-01 for linking success. Consult their user manual.
TESTING
Magnet test
- Activate test mode.
- Apply again the magnet in correspondence of the “magnet test activation area”.
- LED indicators signal “Alarm activation”.
Local safety standards may require you to test these devices on a regular
basis.
Use only suitable aerosol testers / heat test devices supplied by approved
manufacturers. Follow their specific use instructions.
Aerosol test
- Activate test mode.
- Apply the aerosol test device to the detector.
- Wait a few seconds.
- LED indicators signal “Alarm activation”.
Before testing every TAU-MC-01-BL, always activate test mode. This is done by holding a suitable magnet in the “magnet test activation area”. When activated, LED indicators signal “Test mode active”.
Heat test
- Activate test mode.
- Apply the heat test device to the detector.
- Wait a few seconds.
- LED indicators signal “Alarm activation”.
BATTERY FAULTS AND BATTERY SUBSTITUTION PROCEDURE
When one or both batteries are low in charge, a specific fault message is
routed to the control panel. If such event occurs:
-
Remove the safety screw.
-
Remove the detector from its base.
-
Remove the batteries cover.
-
Extract both batteries.
-
Insert both new batteries into their holders, oriented as per polarity marks.
See POWERING UP – DEVICE LINKED TO THE SYSTEM. -
Reinstall the batteries cover.
-
Reinstall the detector.
-
Reinstall the safety screw.
When a low battery condition is indicated, both batteries must be changed
altogether.
Batteries must be brand new.
Do not touch the Link / program switch.
Ensure that the batteries are installed properly, with their polarities
matching the indications on the device.
MAINTENANCE – CLEANING
- Remove the safety screw.
- Remove the detector from its base.
- Smoke entry areas and thermistor area: use a small, soft bristle brush to dislodge any obvious contaminants such as insects, spider webs, hairs, etc.
- Smoke entry areas and thermistor area: use a small vacuum tube or dry, clean, compressed air to suck up or blow any remaining small particles away.
- Wipe the exterior housing of the detector with a clean, damp, lint-free cloth to remove any surface film that can later attract airborne contaminants.
- Install the detector onto its base again.
- Test the detector.
- Reinstall the safety screw.
TECHNICAL SPECIFICATIONS *
Table 2
Specification | Value |
---|
Communication range with TAU-TRM-01 , TAU-CEM-01 or TAU-EXM-01
network devices| 200 m (in open space)
Wireless frequency band| 868 MHz
Number of wireless channels| 66
Radiated power| 14 dBm (25 mW)
Temperature alarm threshold (static)| 58 °C
Operating temperature range| -10 °C to 55 °C
Maximum humidity (non condensing)| 95% RH
IP rating| 40
- See TDS-TWDMX technical specification document for further technical data.
BATTERIES SPECIFICATIONS
Table 3
Specification | Value |
---|---|
Batteries type | CR123A (3 V, 1.25 Ah) |
Batteries lifespan * | 10 years |
Low battery threshold value (nominal) | 2.850 V |
- Batteries lifespan depends by environmental conditions, default monitor settings and link quality.
SMOKE SENSITIVITY SPECIFICATIONS
Table 4
**Detector’s sensitivity setting *| Obscuration threshold value for
alarm activation**
---|---
High sensitivity| 0.12 dB/m
Medium sensitivity (default setting)| 0.15 dB/m
Low sensitivity| 0.18 dB/m
- Detector’s smoke sensitivity can be set through TauREX.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace the devices in order to minimize the risk of reduced performance caused by external factors. Ensure that this device is only used with compatible control panels. Detection systems must be checked, serviced and maintained on a regular basis to confirm correct operation. Smoke detectors may respond differently to various kinds of smoke particles, thus application advice should be sought for special risks. Detectors cannot respond correctly if barriers exist between them and the fire location and may be affected by special environmental conditions. Refer to and follow national codes of practice and other internationally recognized fire engineering standards. Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically. Use only in Taurus fire detection and alarm systems.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or manufacturing defects, effective from the production date indicated on each product. This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling or usage. Product must be returned via your authorized supplier for repair or replacement together with full information on any problem identified. Full details on our warranty and product’s returns policy canbe obtained upon request.
0051
22
HF-20-014CPR
Hyfire Wireless Fire Solutions Ltd – Unit B12a, Holly Farm Business Park,
Honiley, Warwick shire, CV8 1NP – United Kingdom
TAU-MC-01-BL
EN 54-25:2008
EN 54-7:2018
EN 54-5:2017+A1:2018
Class A1R
Hyfire Wireless Fire Solutions Ltd – Unit B12a,
Holly Farm Business Park, Honiley,
Warwickshire, CV8 1NP – United Kingdom
www.hyfirewireless.com
info@hyfirewireless.co.uk
L20-TWDM1B-1400 (vA.1)