DSE4510 MKII Manual And Auto Genset Controller User Manual
- June 1, 2024
- DSE
Table of Contents
DSE4510 MKII Manual And Auto Genset Controller
“`html
Product Specifications
- 101 Contrast: 0 (%)
- 102 Fast Loading Enabled: On (1)
- 103 All Warnings Latched: On (1)
- 104 Lamp Test at Startup: On (1)
- 105 Power Save Mode Enable: On (1)
- 106 Deep Sleep Mode Enable: On (1)
- 107 Protected Start Enable: On (1)
- 108 Event Log Display Format: 0 (Display Mode)
- 109 Power Up Mode: 0 (Power Up Mode)
- 110 DTC String Enable: On (1)
Product Usage Instructions
Enabling/Disabling Features
To enable or disable specific features, follow these steps:
-
Access the settings menu on the product.
-
Navigate to the desired feature using the provided codes (e.g.,
101 for Contrast). -
Toggle the feature by selecting On (1) or Off (0) as
needed.
Maintenance Reset
To perform a PIN protected maintenance reset:
- Enter the correct PIN code provided in the manual.
- Follow the on-screen instructions to complete the reset
process.
Display Settings
To adjust display settings such as voltage, frequency, and
current display:
- Access the display settings menu.
- Select the specific display setting you wish to modify.
- Toggle the display between On (1) and Off (0) as per your
preference.
Frequently Asked Questions (FAQ)
What should I do if my product does not start up
correctly?
If your product does not start up correctly, ensure that all
settings are properly configured. If issues persist, contact
customer support for further assistance.
How can I reset the maintenance PIN?
To reset the maintenance PIN, refer to the maintenance section
in the user manual for detailed instructions on how to proceed.
“`
Configuration Parameters Module (Page 1)
101 Contrast
0 (%)
102 Fast Loading Enabled
103 All Warnings Latched
104 Lamp Test at Startup
105 Power Save Mode Enable
106 Deep Sleep Mode Enable
107 Protected Start Enable
108 Event Log Display Format
109 Power Up Mode
110 DTC String Enable
111 RESERVED
112
PIN Protected Maintenance Reset
113 Stop Button Cooldown
114 Use Module Oil Pressure
115 Use Module Coolant Temp
116 Use Module Engine Hours
117 Use Module RPM
On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off
(0) On (1), Off (0) On (1), Off (0) 0 (Power Up Mode) On (1), Off (0)
On (1), Off (0)
On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off
(0)
118 Use Module Charge Alt
On (1), Off (0)
119 Disable CAN Speed Control On (1), Off (0)
120 CT Position
Gen (0), Load (1)
121
Disable Generator Voltage Display
On (1), Off (0)
122 Disable Mains Voltage Display On (1), Off (0)
123
Disable Generator Frequency Display
On (1), Off (0)
124
Disable Mains Frequency Display
125 Disable Current Display
126 Disable kW Display
127 Disable kvar Display
128 Disable kVA Display
129 Disable pf Display
130 Disable kWh Display
131 Disable kvarh Display
132 Disable kVAh Display
133 RESERVED
134 Show Load Switching Icons
On (1), Off (0)
On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off
(0) On (1), Off (0) On (1), Off (0) On (1), Off (0)
On (1), Off (0)
135 Backlight Inactivity Timer
On (1), Off (0)
136 ECU Periodic Wake Up
On (1), Off (0)
137 Coolant Temp Persistence On (1), Off (0)
138 Limit Audible Alarm Duration On (1), Off (0)
139 Transducer Power Supply
On (1), Off (0)
140 English Text Mode
On (1), Off (0)
141
Ignore Active Alarms in Backlight Power Save Mode
On (1), Off (0)
142
Display Mode for Oil Pressure
0 (Display Mode)
143
Display Mode for Coolant Temp
0 (Display Mode Temp)
144 Display Mode for Fuel Level
0 (Display Mode)
145
ECU Override During Protected Start
On (1), Off (0)
Configuration Parameters CAN Application (Page 2)
201 CAN Alternative Engine Speed On (1), Off (0) 203
202 CAN ECU Data Fail Arming
0 (Arming)
204
CAN ECU Data Fail Action CAN ECU Data Fail Delay
0 (Action) 0 s
Configuration Parameters Digital Inputs (Page 3) 301 Digital Input A Source 302 Digital Input A Polarity 303 Digital Input A Action (If Source = User Config) 304 Digital Input A Arming (If Source = User Config) 305 Digital Input A Activation Delay (If Source = User Config) 306 Digital Input B Source 307 Digital Input B Polarity 308 Digital Input B Action (If Source = User Config) 309 Digital Input B Arming (If Source = User Config) 310 Digital Input B Activation Delay (If Source = User Config) 311 Digital Input C Source 312 Digital Input C Polarity 313 Digital Input C Action (If Source = User Config) 314 Digital Input C Arming (If Source = User Config) 315 Digital Input C Activation Delay (If Source = User Config) 316 Digital Input D Source 317 Digital Input D Polarity 318 Digital Input D Action (If Source = User Config) 319 Digital Input D Arming (If Source = User Config) 320 Digital Input D Activation Delay (If Source = User Config)
0 (Input Source) 0 (Polarity) 0 (Action) 0 (Arming) 0 s 0 (Input Source) 0 (Polarity) 0 (Action) 0 (Arming) 0 s 0 (Input Source) 0 (Polarity) 0 (Action) 0 (Arming) 0 s 0 (Input Source) 0 (Polarity) 0 (Action) 0 (Arming) 0 s
Configuration Parameters Outputs (Page 4) 401 Digital Output A Source 0 (Output Source) 402 Digital Output A Polarity 0 (Output Polarity) 403 Digital Output B Source 0 (Output Source) 404 Digital Output B Polarity 0 (Output Polarity) 405 Digital Output C Source 0 (Output Source) 406 Digital Output C Polarity 0 (Output Polarity)
407 Digital Output D Source 408 Digital Output D Polarity 409 Digital Output E Source 410 Digital Output E Polarity 411 Digital Output F Source 412 Digital Output F Polarity
0 (Output Source) 0 (Output Polarity) 0 (Output Source) 0 (Output Polarity) 0 (Output Source) 0 (Output Polarity)
Configuration Parameters Timers (Page 5)
501 Mains Transient Delay
514 Failed to Stop Delay
502 Start Delay
515 Generator Transient Delay
503 Preheat Timer
516 Transfer Delay
504 Crank Time
517 Breaker Trip Pulse
505 Crank Rest Time
518 Breaker Close Pulse
506 Smoke Limiting
519 Delayed Load Output 1
507 Smoke Limiting Off
520 Delayed Load Output 2
508 DPF Ramp
521 Delayed Load Output 3
509 Safety On Delay
522 Delayed Load Output 4
510 Warm Up Time
523 Power Save Mode Delay
511 Return Delay
524 Deep Sleep Mode Delay
512 Cooling Time
525 Page Delay
513 ETS Solenoid Hold
526 Cooling Time at Idle
527 Backlight Power Save Delay 528 Audible Alarm Timer 529 Fuel Pull in Coil Duration 530 ECU Override Time 531 ECU Periodic Wakeup Period 532 Post-Heat Timer 533 Delay Crank Timer 534 Max Start Pause Timer 535 Engage Attempt Time 536 Engage Rest Time 537 Protected Start Timeout 538 Exhaust Temp Based Cool Time
Digital Input Polarity
Index Polarity
0
Close to Activate
1
Open to Activate
Output Polarity
Index Polarity
0
Energise
1
De-Energise
Alarm Action
Index Action
0
Electrical Trip
1
Shutdown
2
Warning
Display Mode Index 0 1
Action Numerical Value Bar Graph
Display Mode Temp
Index Action
0
Numerical Value
1
Bar Graph (80 to 175 °C)
2
Bar Graph (80 to 215 °C)
Configuration Parameters Generator (Page 6)
601 Alternator Fitted
On (1), Off (0)
602 Alternator Poles
603
Under Voltage Shutdown Enable
604 Under Voltage Trip Shutdown
605 Under Voltage Warning Enable
0
On (1), Off (0)
0 V On (1), Off (0)
606 Under Voltage Warning Trip
0 V
607 RESERVED
608 Loading Voltage
0 V
609 Over Voltage Warning Enable On (1), Off (0)
610 Over Voltage Warning Return 0 V
611 Over Voltage Warning Trip
0 V
612 Over Voltage Shutdown Trip 0 V
613
Under Frequency Shutdown Enable
On (1), Off (0)
614 Under Frequency Shutdown Trip 0.0 Hz
615
Under Frequency Warning Enable
On (1), Off (0)
616 Under Frequency Warning Trip 0.0 Hz
617 RESERVED
618 Loading Frequency
0.0 Hz
619 Nominal Frequency
0.0 Hz
620
Over Frequency Warning Enable
On (1), Off (0)
621 Over Frequency Warning Return 0.0 Hz
622 Over Frequency Warning Trip 0.0 Hz
623
Over Frequency Shutdown Enable
On (1), Off (0)
624 Over Frequency Shutdown Trip 0.0 Hz
625 Generator AC System 626 CT Primary
0 (AC System) 0 A
627 CT Secondary
1 A, 5 A
628 Full Load Rating
629 Immediate Over Current Enable
630
Delayed Over Current Alarm Enable
631
Delayed Over Current Alarm Action
632 Over Current Delay Time
633 Over Current Trip
634 kW Rating
635 Over kW Protection Enable
636 Over kW Protection Action
0 A On (1), Off (0)
On (1), Off (0)
0 (Action)
0 s 0 % 0 kW On (1), Off (0) 0 (Action)
637 Over kW Protection Trip
0 %
638 Over kW Protection Trip Delay 0 s
639 Enable CT Support
On (1), Off (0)
640 Over kW Protection Return
641 Nominal Voltage
642655
RESERVED
656 Load Unbalance Alarm
0 % 0 V
On (1), Off (0)
657 Load Unbalance Alarm Action 0 (Action)
658 Load Unbalance Trip
0 %
659 Load Unbalance Warning Return 0 %
660 Load Unbalance Delay Time
0 s
Configuration Parameters Mains (Page 7)
701 Mains AC System
0 (AC System)
702 Mains Failure Detection
On (1), Off (0)
703 Immediate Mains Dropout On (1), Off (0)
704 Under Voltage Enable
On (1), Off (0)
705 Under Voltage Level
0 V
706 Under Voltage Return
0 V
707 Over Voltage Enable
On (1), Off (0)
708 Over Voltage Return
0 V
709 Over Voltage Level Trip 710 Under Frequency Enable 711 Under Frequency Trip 712 Under Frequency Return 713 Over Frequency Enable 714 Over Frequency Return 715 Over Frequency Trip
0 V On (1), Off (0) 0.0 Hz 0.0 Hz On (1), Off (0) 0 Hz 0.0 Hz
Configuration Parameters Engine (Page 8)
801 Start Attempts
0
833 RESERVED
802 Over Speed Overshoot
0 %
834 RESERVED
803 Over Speed Delay
0 s
835 J1939-75 Instruments Enable On (1), Off (0)
804
Gas Choke Timer (Gas Engine Only)
0 s
836 J1939-75 Alarms Enable
On (1), Off (0)
805
Gas On Delay (Gas Engine Only)
0 s
837 Engine CAN Source Address 0
806
Gas Ignition Off Delay (Gas Engine Only)
0 s
838
Instrumentation CAN Source Address
0
807
Crank Disconnect On Oil Pressure Enable
On (1), Off (0) 839 RESERVED
808
Check Oil Pressure Prior to Starting
On (1), Off (0) 840 Tier 4 Home Screen Enable On (1), Off (0)
809 Crank Disconnect On Oil
0.00 Bar
841 Start Pause Time
0 s
810
Crank Disconnect On Frequency
0.0 Hz
842 Preheat Enable
On (1), Off (0)
811
Crank Disconnect On Engine Speed
0 RPM
843 Preheat Temperature
0 °C
812 Under Speed Enable
On (1), Off (0) 844 Post-heat Enabled
On (1), Off (0)
813 Under Speed Trip
0 RPM
845 Post-heat Temperature
0 °C
814 Over Speed Trip
0 RPM
846 Coolant Heater Enabled
On (1), Off (0)
815 Low Battery Voltage Enable On (1), Off (0) 847 Coolant Heater On Temp
0 °C
816 Low Battery Voltage Warning 0.0 V
848 Coolant Heater Off Temp
0 °C
817 Low Battery Voltage Return
0.0 V
849 Coolant Cooler Enabled
On (1), Off (0)
818 Low Battery Voltage Delay
0:00:00
850 Coolant Cooler On Temp
0 °C
819 High Battery Voltage Enable On (1), Off (0) 851 Coolant Cooler Off Temp
0 °C
820 High Battery Voltage Return 0.0 V
852 RESERVED
821 High Battery Voltage Warning 0.0 V
853 Tank Bund Level High Alarm 0 (Action)
822
High Battery Voltage Warning Delay
0 s
854 Fan Speed Low Arming
0 (Arming)
823 Charge Alt Shutdown Enable On (1), Off (0) 855 Fan Speed Low Action
0 (Action)
824 Charge Alt Shutdown Trip
0.0 V
856 Fan Speed Low Delay
0 s
825 Charge Alt Shutdown Delay
0 s
857 Fuel Low Switch Arming
0 (Arming)
826 Charge Alt Warning Enable
On (1), Off (0) 858 Fuel Low Switch Action
0 (Action)
827 Charge Alt Warning Trip
0.0 V
859
Fuel Low Switch Activation Delay
0 s
828 Charge Alt Warning Delay
0 s
860
Crank Disconnect on Charge Alt Enable
On (1), Off (0)
829 Start on Low Battery Enable
On (1), Off (0)
861
Crank Disconnect on Charge Alt Voltage
0.0 V
830 Start on Low Battery Threshold 0.0 V
862
Enable Multiple Engage Attempts
On (1), Off (0)
831 Start on Low Battery Start Delay 0 s
863 Engage Attempts
0
832
Start on Low Battery Engine Run Duration
0 s
864
Exhaust Temperature Based Cooling On Temperature
0 °C
Configuration Parameters Analogue Inputs (Page 9) 901-902 RESERVED 903 Low Oil Pressure Enable 904 Low Oil Pressure Trip 905 Oil Pressure Sensor Open Circuit 906-907 RESERVED 908 High Engine Temperature Trip 909 Temperature Sensor Open Circuit 910-929 RESERVED 930 Fuel Sensor C Low Alarm Action 931 Fuel Sensor C Low Shutdown Trip 932 Fuel Sensor C Low Shutdown Delay 933 Fuel Sensor C Low Pre-Alarm Enable 934 Fuel Sensor C Low Pre-Alarm Trip 935 Fuel Sensor C Low Pre-Alarm Return 936 Fuel Sensor C Low Pre-Alarm Delay 937 Fuel Sensor C High Pre-Alarm Enable 938 Fuel Sensor C High Pre-Alarm Return 939 Fuel Sensor C High Pre-Alarm Trip 940 Fuel Sensor C High Pre-Alarm Delay 941 RESERVED 942 Fuel Sensor C High Alarm Action 943 Fuel Sensor C High Alarm Trip 944 Fuel Sensor C High Alarm Delay 945-967 RESERVED 968 Fuel Usage Alarm (Run) Arming 969 Fuel Usage Alarm (Run) Action 970 Fuel Usage Alarm (Run) Trip 971 Fuel Usage Alarm (Run) Return 972 Fuel Usage Alarm (Stopped) Arming 973 Fuel Usage Alarm (Stopped) Action 974 Fuel Usage Alarm (Stopped) Trip 975 Fuel Usage Alarm (Stopped) Return 976 Low Coolant Level Arming 977 Low Coolant Level Action 978 Low Coolant Level Trip 979 Low Coolant Level Return 980 Low Coolant Level Delay 981 Low Coolant Level Open Circuit Arming 982 Low Coolant Level Switch Arming 983 Low Coolant Level Switch Action 984 Low Coolant Level Switch Delay 985 High Engine Temp Pre-Alarm Enable 986 High Engine Temp Pre- Alarm Return 987 High Engine Temp Pre-Alarm Trip
On (1), Off (0) 0 Bar On (1), Off (0)
0.00 °C On (1), Off (0)
Shutdown (2), Electrical Trip (1), Disabled (0) 0 % 0 s On (1), Off (0) 0 % 0
% 0 s On (1), Off (0) 0 % 0 % 0 s
Shutdown (2), Electrical Trip (1), Disabled (0) 0 % 0 s
On (1), Off (0) 0 (Action) 0 % 0 % 0 (Arming) 0 (Action) 0 % 0 % 0 (Arming) 0
(Action) 0 % 0 % 00:00:00 On (1), Off (0) 0 (Arming) 0 (Action) 00:00:00 On
(1), Off (0) 0.00 °C 0.00 °C
Configuration Parameters Scheduler (Page 10) 1001 1002 1003
1004, 1008, 1012, 1016, 1020, 1024, 1028, 1032 1005, 1009, 1013, 1017, 1021,
1025, 1029, 1033 1006, 1010, 1014, 1018, 1022, 1026, 1030, 1034 1007, 1011,
1015, 1019, 1023, 1027, 1031, 1035
Enable Scheduler Schedule Run On or Off Load Scheduler Period Start Time (Entry 1 to 8) Day (Entry 1 to 8) Week (Entry 1 to 8) Duration (Entry 1 to 8)
On (1), Off (0) On (1), Off (0) Weekly (0), Monthly (1) 0:00:00 0 (1=Monday) 1, 2, 3 or 4 0 s
Configuration Parameters Time (Page 11)
1101 Time of Day
0:00:00
1102 RESERVED
1103 RESERVED
1104 Day of Month 1105 Month of Year 1106 Year
1 to 31 1 to 12 0 to 99
Configuration Parameters Maintenance Alarms (Page 12) 1201 Oil Maintenance Alarm Enable On (1), Off (0) 1206
1202 1203 1204 1205
Oil Maintenance Alarm Action 0 (Action)
Oil Maintenance Alarm Engine Hours
0 h
Air Maintenance Alarm Enable On (1), Off (0)
Air Maintenance Alarm Action 0 (Action)
1207 1208 1209
Air Maintenance Alarm Engine Hours
Fuel Maintenance Alarm Enable
0 h On (1), Off (0)
Fuel Maintenance Alarm Action 0 (Action)
Fuel Maintenance Alarm Engine Hours
0 h
Configuration Parameters Alternate Configuration 1 (Page 20)
2001-2076
Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for configuration parameters.
Configuration Parameters Alternate Configuration 2 (Page 30)
3002-3076
Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for configuration parameters.
Configuration Parameters Alternate Configuration 3 (Page 40)
4002-4076
Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for configuration parameters.
AC System Index Type 0 2 Phase 3 Wire (L1 to L3) 1 2 Phase 3 Wire (L1 to L2) 2 3 Phase 3 Wire 3 3 Phase 4 Wire 4 3 Phase 4 Wire (Delta) 5 Single Phase 2 Wire
Digital Input Alarm Arming Index Arming
0 Always 1 From Safety On 2 From Starting 3 Never
Power Up Mode Index Mode 0 Stop 1 Manual 2 Auto
Functionality in DSE4510 MKII & DSE4520 MKII Functionality in DSE4520 MKII Auto Start and AMF Functionality in DSE4520 MKII AMF Only
Input Sources 0 User Configured 1 Remote Start on Load 2 RESERVED 3 Auto Start
Inhibit 4 Lamp Test 5 Alarm Mute 6 Alarm Reset 7 RESERVED 8 Simulate Start
Button 9 Simulate Stop Button 10 RESERVED
11 Simulate Auto Button
12 RESERVED 13 Close Generator Open Mains 14 Generator Load Inhibit 15
RESERVED 16 Close Mains Open Generator
17 18 19 20 21 22 23 24 25 26-30 31
Mains Load Inhibit RESERVED External Panel Lock Auxiliary Mains Fail Oil Pressure Switch Coolant Temperature Switch RESERVED Simulate Mains Available Remote Start Off Load RESERVED Auto Restore Inhibit
32 RESERVED
33 34 35-38 39 40
Low Fuel Level Switch Smoke Limiting RESERVED Main Configuration Alternative Configuration 1
41 Alternative Configuration 2
42 Alternative Configuration 3
43 Emergency Stop
44 RESERVED
45 Maintenance Reset Oil
46 Maintenance Reset Air
47 Maintenance Reset Fuel
48 RESERVED
49 RESERVED
50 DPF Auto Regen Inhibit
51 DPF Force Regeneration
52
DPF Regeneration Interlock
53 Water in Fuel
54 Fuel Bund Level High
55 Fan Speed Low
56 Low Coolant Level Switch
57 Wait To Start
Output Sources
0 Not Used
1 Air Flap Relay
2 Audible Alarm
3 Battery High Volts Warning
4 Battery Low Volts Warning
5 CAN ECU Data Fail
6 ECU (ECM) Warning
7 ECU (ECM) Shutdown
8 CAN ECU Power
9 CAN ECU Stop
10 Charge Alternator Shutdown
11 Charge Alternator Warning
12 Close Generator Output
13
Close Generator Output Pulse
14 Close Mains Output
15 Close Mains Output Pulse
16 Combined Mains Failure
17 Common Alarm
18 Common Electrical Trip
19 Common Shutdown 20 Common Warning 21 Cooling Down 22 Digital Input A 23 Digital Input B 24 Digital Input C 25 Digital Input D 26 RESERVED 27 RESERVED 28 RESERVED 29 Emergency Stop 30 Energise to Stop 31 Fail to Start 32 Fail to Stop 33 Fuel Relay 34 Gas Choke On 35 Gas Ignition
36 Generator Available
37
Generator High Voltage Alarm
38
Generator Low Voltage Alarm
39 kW Overload Alarm
40
Over Current Immediate Warning
41 Delayed Over Current Alarm
42
High Coolant Temp Shutdown
43 Low Oil Pressure Shutdown
44 Mains High Frequency
45 Mains High Voltage
46 Mains Low Frequency
47 Mains Low Voltage
48
Oil Pressure Sensor Open Circuit
49 Open Generator Output
50 Open Generator Output Pulse 51 Open Mains Output 52 Open Mains Output Pulse
53 Over Frequency Shutdown 54 Over Speed Shutdown 55 Preheat During Preheat
Timer 56 Preheat Until End of Crank 57 Preheat Until End of Safety Timer 58
Preheat Until End of Warming 59 Smoke Limiting 60 Start Relay 61 Temperature
Sensor Open Circuit 62 Under Frequency Shutdown
63 Under Speed Shutdown
64 Waiting for Manual Restore 65 Flexible Sensor C High Alarm 66 Flexible
Sensor C High Pre-Alarm
67 Flexible Sensor C Low Pre-Alarm
68 Flexible Sensor C Low Alarm
69 RESERVED 70 RESERVED 71 RESERVED 72 RESERVED 73 Fuel Sensor High Alarm 74
Fuel Sensor High Pre-Alarm 75 Fuel Sensor Low Pre-Alarm 76 Fuel Sensor Low
Alarm 77 Delayed Load Output 1 78 Delayed Load Output 2 79 Delayed Load Output
3 80 Delayed Load Output 4 81 Air Filter Maintenance 82 Oil Filter Maintenance
83 Fuel Filter Maintenance 84 System in Stop Mode 85 System in Auto Mode
86 System in Manual Mode
87 RESERVED
88 Analogue Input A (Digital)
89 Analogue Input B (Digital)
90 Analogue Input C (Digital)
91 RESERVED
92 RESERVED
93 RESERVED
94 RESERVED
95 Over Speed Overshoot Alarm
96 Over Frequency Overshoot Alarm
97 Display Heater Fitted and Active
98 RESERVED
99 SCR Inducement
100 DEF Level Low 101 DPF Auto Regeneration Inhibit 102 DPF Forced Regeneration 103 DPF None Mission State 104 DPF Regeneration in Progress 105 DPF Regen Interlock Active 106 DPTC Filter 107 HEST Active 108 Water in Fuel 109 Fuel Pull in Coil 110 Generator at Rest 111 Fuel Tank Bund Level High 112 ECU Preheat
113 Water Heater
114 Water Cooler
115 Closed to Gen
116 Closed to Mains
117
Generator Under Frequency Warning
118
Generator Over Frequency Warning
119 Generator Low Voltage Warning
120 Generator High Voltage Warning
121 Main Config Selected
122 Alt Config 1 Selected
123 Alt Config 2 Selected
124 Alt Config 3 Selected
125 Flexible Sensor A High Alarm
126 Flexible Sensor A High Pre-Alarm
127 Flexible Sensor A Low Alarm
128 Flexible Sensor A Low Pre-Alarm
129 Flexible Sensor A Open Circuit
130 Fan Speed Low
131 Fuel Usage Alarm
132 Low Coolant Level
133 Low Coolant Level Open Circuit
134 Waiting To Start
135 High Coolant Temp Pre-Alarm
136
Gen Over Frequency Delayed Alarm
137 Load Unbalance Alarm
138
Configurable CAN 1 Instrument Active
139
Configurable CAN 2 Instrument Active
140
Configurable CAN 3 Instrument Active
141
Configurable CAN 4 Instrument Active
142
Configurable CAN 5 Instrument Active
143
Configurable CAN 6 Instrument Active
144
Configurable CAN 7 Instrument Active
145
Configurable CAN 8 Instrument Active
146
Configurable CAN 9 Instrument Active
147
Configurable CAN 10 Instrument Active
Functionality in DSE4510 MKII & DSE4520 MKII Functionality in DSE4520 MKII Auto Start and AMF Functionality in DSE4520 MKII AMF Only
TYPICAL WIRING DIAGRAM
DSE4510 MKII & DSE4520 MKII
053-234 Issue 6
DEEP SEA ELECTRONICS
DSE4510 MKII & DSE4520 MKII Installation Instructions
Applicable to module version 3.0.0 and upwards.
EDITING A PARAMETER
· Press the Stop/Reset Mode to enter the editor mode.
( – ) and Auto Mode
() buttons together
· Press the Up
or Down
navigation buttons to cycle through the front
panel editor in increments of 100.
· Press the Manual/Start Mode ( + ) or Stop/Reset Mode
cycle through the front panel editor in increments of 1.
( – ) buttons to
· When viewing the parameter to be edited, press the Auto Mode and the value begins to flash.
() button
· Press the Manual/Start Mode ( + ) or Stop/Reset Mode
buttons to adjust the value to the required setting.
( – ) navigation
· Press the Auto Mode ceases flashing.
() button to save the current value, the value
· Press and hold the Auto Mode () button to save and exit the editor, the
configuration icon
is removed from the display.
NOTE: Pressing and holding the Manual/Start Mode
( + ) or
Stop/Reset Mode
( – ) buttons will give auto-repeat functionality.
DIMENSIONS
140 mm x 113 mm x 43 mm (5.5″ x 4.4″ x 1.7″)
PANEL CUTOUT
118 mm x 92 mm (4.6″ x 3.6″)
TERMINALS
Tightening Torque: 0.5 Nm (4.5 lb-in) Conductor Size: 0.5 mm² to 2.5 mm²
(AWG 20 to AWG 13)
NOTE: A larger version of the typical wiring diagram is included in
the product’s operator manual. Refer to DSE Publication: 057-260 DSE4510 MKII
& DSE4520 MKII Operator Manual
NOTE: Terminals 25, 26, 27 & 28 are not fitted to the DSE4510 MKII
NOTE: More comprehensive module configuration is possible via PC configuration software. For further details of module configuration, refer to DSE Publication: 057-258 DSE4510 MKII & DSE4520 MKII Configuration Suite PC Software Manual.
Deep Sea Electronics Ltd Tel: +44 (0)1723 890099
Email: sales@deepseaelectronics.com Web: www.deepseaelectronics.com
Deep Sea Electronics Inc Tel: +1
815-316-8706 Fax: +1
815-316-8708
Email: USAsales@deepseaelectronics.com Web: www.deepseaelectronics.com
REQUIREMENTS FOR UL CERTIFICATION
Specification Screw Terminal Tightening Torque Conductors
Current Inputs
Description · 4.5 lb-in (0.5 Nm)
· Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5
mm² to 2.5 mm²). · Conductor protection must be provided in accordance with
NFPA 70, Article 240 · Low voltage circuits (35 V or less) must be supplied
from the engine starting battery or an isolated secondary circuit. · The
communication, sensor, and/or battery derived circuit conductors shall be
separated and secured to maintain at least ¼” (6 mm) separation from the
generator and mains connected circuit
conductors unless all conductors are rated 600 V or greater.
· Must be connected through UL Listed or Recognized isolating current
transformers with the secondary rating of 5 A max.
Communication Circuits
· Must be connected to communication circuits of UL Listed equipment
DC Output Pilot Duty Mounting
Operating Temperature
· 0.5 A · Suitable for use in type 1 Enclosure Type rating with surrounding
air temperature -22 ºF to +158 ºF (-30 ºC to +70 ºC) · Suitable for pollution
degree 3 environments when voltage sensing inputs do not exceed 300 V. When
used to monitor voltages over 300 V device to be install in an unventilated or
filtered ventilation
enclosure to maintain a pollution degree 2 environment. · -22 ºF to +158 ºF
(-30 ºC to +70 ºC)
Storage Temperature
· -40 ºF to +176 ºF (-40 ºC to +80 ºC)
Read User Manual Online (PDF format)