DSE4510 MKII Manual And Auto Genset Controller User Manual

June 1, 2024
DSE

DSE4510 MKII Manual And Auto Genset Controller

“`html

Product Specifications

  • 101 Contrast: 0 (%)
  • 102 Fast Loading Enabled: On (1)
  • 103 All Warnings Latched: On (1)
  • 104 Lamp Test at Startup: On (1)
  • 105 Power Save Mode Enable: On (1)
  • 106 Deep Sleep Mode Enable: On (1)
  • 107 Protected Start Enable: On (1)
  • 108 Event Log Display Format: 0 (Display Mode)
  • 109 Power Up Mode: 0 (Power Up Mode)
  • 110 DTC String Enable: On (1)

Product Usage Instructions

Enabling/Disabling Features

To enable or disable specific features, follow these steps:

  1. Access the settings menu on the product.

  2. Navigate to the desired feature using the provided codes (e.g.,
    101 for Contrast).

  3. Toggle the feature by selecting On (1) or Off (0) as
    needed.

Maintenance Reset

To perform a PIN protected maintenance reset:

  1. Enter the correct PIN code provided in the manual.
  2. Follow the on-screen instructions to complete the reset
    process.

Display Settings

To adjust display settings such as voltage, frequency, and
current display:

  1. Access the display settings menu.
  2. Select the specific display setting you wish to modify.
  3. Toggle the display between On (1) and Off (0) as per your
    preference.

Frequently Asked Questions (FAQ)

What should I do if my product does not start up

correctly?

If your product does not start up correctly, ensure that all
settings are properly configured. If issues persist, contact
customer support for further assistance.

How can I reset the maintenance PIN?

To reset the maintenance PIN, refer to the maintenance section
in the user manual for detailed instructions on how to proceed.

“`

Configuration Parameters ­ Module (Page 1)

101 Contrast

0 (%)

102 Fast Loading Enabled

103 All Warnings Latched

104 Lamp Test at Startup

105 Power Save Mode Enable

106 Deep Sleep Mode Enable

107 Protected Start Enable

108 Event Log Display Format

109 Power Up Mode

110 DTC String Enable

111 RESERVED

112

PIN Protected Maintenance Reset

113 Stop Button Cooldown

114 Use Module Oil Pressure

115 Use Module Coolant Temp

116 Use Module Engine Hours

117 Use Module RPM

On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) 0 (Power Up Mode) On (1), Off (0)
On (1), Off (0)
On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0)

118 Use Module Charge Alt

On (1), Off (0)

119 Disable CAN Speed Control On (1), Off (0)

120 CT Position

Gen (0), Load (1)

121

Disable Generator Voltage Display

On (1), Off (0)

122 Disable Mains Voltage Display On (1), Off (0)

123

Disable Generator Frequency Display

On (1), Off (0)

124

Disable Mains Frequency Display

125 Disable Current Display

126 Disable kW Display

127 Disable kvar Display

128 Disable kVA Display

129 Disable pf Display

130 Disable kWh Display

131 Disable kvarh Display

132 Disable kVAh Display

133 RESERVED

134 Show Load Switching Icons

On (1), Off (0)
On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0) On (1), Off (0)
On (1), Off (0)

135 Backlight Inactivity Timer

On (1), Off (0)

136 ECU Periodic Wake Up

On (1), Off (0)

137 Coolant Temp Persistence On (1), Off (0)

138 Limit Audible Alarm Duration On (1), Off (0)

139 Transducer Power Supply

On (1), Off (0)

140 English Text Mode

On (1), Off (0)

141

Ignore Active Alarms in Backlight Power Save Mode

On (1), Off (0)

142

Display Mode for Oil Pressure

0 (Display Mode)

143

Display Mode for Coolant Temp

0 (Display Mode Temp)

144 Display Mode for Fuel Level

0 (Display Mode)

145

ECU Override During Protected Start

On (1), Off (0)

Configuration Parameters ­ CAN Application (Page 2)

201 CAN Alternative Engine Speed On (1), Off (0) 203

202 CAN ECU Data Fail Arming

0 (Arming)

204

CAN ECU Data Fail Action CAN ECU Data Fail Delay

0 (Action) 0 s

Configuration Parameters ­ Digital Inputs (Page 3) 301 Digital Input A Source 302 Digital Input A Polarity 303 Digital Input A Action (If Source = User Config) 304 Digital Input A Arming (If Source = User Config) 305 Digital Input A Activation Delay (If Source = User Config) 306 Digital Input B Source 307 Digital Input B Polarity 308 Digital Input B Action (If Source = User Config) 309 Digital Input B Arming (If Source = User Config) 310 Digital Input B Activation Delay (If Source = User Config) 311 Digital Input C Source 312 Digital Input C Polarity 313 Digital Input C Action (If Source = User Config) 314 Digital Input C Arming (If Source = User Config) 315 Digital Input C Activation Delay (If Source = User Config) 316 Digital Input D Source 317 Digital Input D Polarity 318 Digital Input D Action (If Source = User Config) 319 Digital Input D Arming (If Source = User Config) 320 Digital Input D Activation Delay (If Source = User Config)

0 (Input Source) 0 (Polarity) 0 (Action) 0 (Arming) 0 s 0 (Input Source) 0 (Polarity) 0 (Action) 0 (Arming) 0 s 0 (Input Source) 0 (Polarity) 0 (Action) 0 (Arming) 0 s 0 (Input Source) 0 (Polarity) 0 (Action) 0 (Arming) 0 s

Configuration Parameters ­ Outputs (Page 4) 401 Digital Output A Source 0 (Output Source) 402 Digital Output A Polarity 0 (Output Polarity) 403 Digital Output B Source 0 (Output Source) 404 Digital Output B Polarity 0 (Output Polarity) 405 Digital Output C Source 0 (Output Source) 406 Digital Output C Polarity 0 (Output Polarity)

407 Digital Output D Source 408 Digital Output D Polarity 409 Digital Output E Source 410 Digital Output E Polarity 411 Digital Output F Source 412 Digital Output F Polarity

0 (Output Source) 0 (Output Polarity) 0 (Output Source) 0 (Output Polarity) 0 (Output Source) 0 (Output Polarity)

Configuration Parameters ­ Timers (Page 5)

501 Mains Transient Delay

514 Failed to Stop Delay

502 Start Delay

515 Generator Transient Delay

503 Preheat Timer

516 Transfer Delay

504 Crank Time

517 Breaker Trip Pulse

505 Crank Rest Time

518 Breaker Close Pulse

506 Smoke Limiting

519 Delayed Load Output 1

507 Smoke Limiting Off

520 Delayed Load Output 2

508 DPF Ramp

521 Delayed Load Output 3

509 Safety On Delay

522 Delayed Load Output 4

510 Warm Up Time

523 Power Save Mode Delay

511 Return Delay

524 Deep Sleep Mode Delay

512 Cooling Time

525 Page Delay

513 ETS Solenoid Hold

526 Cooling Time at Idle

527 Backlight Power Save Delay 528 Audible Alarm Timer 529 Fuel Pull in Coil Duration 530 ECU Override Time 531 ECU Periodic Wakeup Period 532 Post-Heat Timer 533 Delay Crank Timer 534 Max Start Pause Timer 535 Engage Attempt Time 536 Engage Rest Time 537 Protected Start Timeout 538 Exhaust Temp Based Cool Time

Digital Input Polarity

Index Polarity

0

Close to Activate

1

Open to Activate

Output Polarity

Index Polarity

0

Energise

1

De-Energise

Alarm Action

Index Action

0

Electrical Trip

1

Shutdown

2

Warning

Display Mode Index 0 1

Action Numerical Value Bar Graph

Display Mode Temp

Index Action

0

Numerical Value

1

Bar Graph (80 to 175 °C)

2

Bar Graph (80 to 215 °C)

Configuration Parameters ­ Generator (Page 6)

601 Alternator Fitted

On (1), Off (0)

602 Alternator Poles

603

Under Voltage Shutdown Enable

604 Under Voltage Trip Shutdown

605 Under Voltage Warning Enable

0
On (1), Off (0)
0 V On (1), Off (0)

606 Under Voltage Warning Trip

0 V

607 RESERVED

608 Loading Voltage

0 V

609 Over Voltage Warning Enable On (1), Off (0)

610 Over Voltage Warning Return 0 V

611 Over Voltage Warning Trip

0 V

612 Over Voltage Shutdown Trip 0 V

613

Under Frequency Shutdown Enable

On (1), Off (0)

614 Under Frequency Shutdown Trip 0.0 Hz

615

Under Frequency Warning Enable

On (1), Off (0)

616 Under Frequency Warning Trip 0.0 Hz

617 RESERVED

618 Loading Frequency

0.0 Hz

619 Nominal Frequency

0.0 Hz

620

Over Frequency Warning Enable

On (1), Off (0)

621 Over Frequency Warning Return 0.0 Hz

622 Over Frequency Warning Trip 0.0 Hz

623

Over Frequency Shutdown Enable

On (1), Off (0)

624 Over Frequency Shutdown Trip 0.0 Hz

625 Generator AC System 626 CT Primary

0 (AC System) 0 A

627 CT Secondary

1 A, 5 A

628 Full Load Rating

629 Immediate Over Current Enable

630

Delayed Over Current Alarm Enable

631

Delayed Over Current Alarm Action

632 Over Current Delay Time

633 Over Current Trip

634 kW Rating

635 Over kW Protection Enable

636 Over kW Protection Action

0 A On (1), Off (0)
On (1), Off (0)
0 (Action)
0 s 0 % 0 kW On (1), Off (0) 0 (Action)

637 Over kW Protection Trip

0 %

638 Over kW Protection Trip Delay 0 s

639 Enable CT Support

On (1), Off (0)

640 Over kW Protection Return

641 Nominal Voltage

642655

RESERVED

656 Load Unbalance Alarm

0 % 0 V
On (1), Off (0)

657 Load Unbalance Alarm Action 0 (Action)

658 Load Unbalance Trip

0 %

659 Load Unbalance Warning Return 0 %

660 Load Unbalance Delay Time

0 s

Configuration Parameters ­ Mains (Page 7)

701 Mains AC System

0 (AC System)

702 Mains Failure Detection

On (1), Off (0)

703 Immediate Mains Dropout On (1), Off (0)

704 Under Voltage Enable

On (1), Off (0)

705 Under Voltage Level

0 V

706 Under Voltage Return

0 V

707 Over Voltage Enable

On (1), Off (0)

708 Over Voltage Return

0 V

709 Over Voltage Level Trip 710 Under Frequency Enable 711 Under Frequency Trip 712 Under Frequency Return 713 Over Frequency Enable 714 Over Frequency Return 715 Over Frequency Trip

0 V On (1), Off (0) 0.0 Hz 0.0 Hz On (1), Off (0) 0 Hz 0.0 Hz

Configuration Parameters ­ Engine (Page 8)

801 Start Attempts

0

833 RESERVED

802 Over Speed Overshoot

0 %

834 RESERVED

803 Over Speed Delay

0 s

835 J1939-75 Instruments Enable On (1), Off (0)

804

Gas Choke Timer (Gas Engine Only)

0 s

836 J1939-75 Alarms Enable

On (1), Off (0)

805

Gas On Delay (Gas Engine Only)

0 s

837 Engine CAN Source Address 0

806

Gas Ignition Off Delay (Gas Engine Only)

0 s

838

Instrumentation CAN Source Address

0

807

Crank Disconnect On Oil Pressure Enable

On (1), Off (0) 839 RESERVED

808

Check Oil Pressure Prior to Starting

On (1), Off (0) 840 Tier 4 Home Screen Enable On (1), Off (0)

809 Crank Disconnect On Oil

0.00 Bar

841 Start Pause Time

0 s

810

Crank Disconnect On Frequency

0.0 Hz

842 Preheat Enable

On (1), Off (0)

811

Crank Disconnect On Engine Speed

0 RPM

843 Preheat Temperature

0 °C

812 Under Speed Enable

On (1), Off (0) 844 Post-heat Enabled

On (1), Off (0)

813 Under Speed Trip

0 RPM

845 Post-heat Temperature

0 °C

814 Over Speed Trip

0 RPM

846 Coolant Heater Enabled

On (1), Off (0)

815 Low Battery Voltage Enable On (1), Off (0) 847 Coolant Heater On Temp

0 °C

816 Low Battery Voltage Warning 0.0 V

848 Coolant Heater Off Temp

0 °C

817 Low Battery Voltage Return

0.0 V

849 Coolant Cooler Enabled

On (1), Off (0)

818 Low Battery Voltage Delay

0:00:00

850 Coolant Cooler On Temp

0 °C

819 High Battery Voltage Enable On (1), Off (0) 851 Coolant Cooler Off Temp

0 °C

820 High Battery Voltage Return 0.0 V

852 RESERVED

821 High Battery Voltage Warning 0.0 V

853 Tank Bund Level High Alarm 0 (Action)

822

High Battery Voltage Warning Delay

0 s

854 Fan Speed Low Arming

0 (Arming)

823 Charge Alt Shutdown Enable On (1), Off (0) 855 Fan Speed Low Action

0 (Action)

824 Charge Alt Shutdown Trip

0.0 V

856 Fan Speed Low Delay

0 s

825 Charge Alt Shutdown Delay

0 s

857 Fuel Low Switch Arming

0 (Arming)

826 Charge Alt Warning Enable

On (1), Off (0) 858 Fuel Low Switch Action

0 (Action)

827 Charge Alt Warning Trip

0.0 V

859

Fuel Low Switch Activation Delay

0 s

828 Charge Alt Warning Delay

0 s

860

Crank Disconnect on Charge Alt Enable

On (1), Off (0)

829 Start on Low Battery Enable

On (1), Off (0)

861

Crank Disconnect on Charge Alt Voltage

0.0 V

830 Start on Low Battery Threshold 0.0 V

862

Enable Multiple Engage Attempts

On (1), Off (0)

831 Start on Low Battery Start Delay 0 s

863 Engage Attempts

0

832

Start on Low Battery Engine Run Duration

0 s

864

Exhaust Temperature Based Cooling On Temperature

0 °C

Configuration Parameters ­ Analogue Inputs (Page 9) 901-902 RESERVED 903 Low Oil Pressure Enable 904 Low Oil Pressure Trip 905 Oil Pressure Sensor Open Circuit 906-907 RESERVED 908 High Engine Temperature Trip 909 Temperature Sensor Open Circuit 910-929 RESERVED 930 Fuel Sensor C Low Alarm Action 931 Fuel Sensor C Low Shutdown Trip 932 Fuel Sensor C Low Shutdown Delay 933 Fuel Sensor C Low Pre-Alarm Enable 934 Fuel Sensor C Low Pre-Alarm Trip 935 Fuel Sensor C Low Pre-Alarm Return 936 Fuel Sensor C Low Pre-Alarm Delay 937 Fuel Sensor C High Pre-Alarm Enable 938 Fuel Sensor C High Pre-Alarm Return 939 Fuel Sensor C High Pre-Alarm Trip 940 Fuel Sensor C High Pre-Alarm Delay 941 RESERVED 942 Fuel Sensor C High Alarm Action 943 Fuel Sensor C High Alarm Trip 944 Fuel Sensor C High Alarm Delay 945-967 RESERVED 968 Fuel Usage Alarm (Run) Arming 969 Fuel Usage Alarm (Run) Action 970 Fuel Usage Alarm (Run) Trip 971 Fuel Usage Alarm (Run) Return 972 Fuel Usage Alarm (Stopped) Arming 973 Fuel Usage Alarm (Stopped) Action 974 Fuel Usage Alarm (Stopped) Trip 975 Fuel Usage Alarm (Stopped) Return 976 Low Coolant Level Arming 977 Low Coolant Level Action 978 Low Coolant Level Trip 979 Low Coolant Level Return 980 Low Coolant Level Delay 981 Low Coolant Level Open Circuit Arming 982 Low Coolant Level Switch Arming 983 Low Coolant Level Switch Action 984 Low Coolant Level Switch Delay 985 High Engine Temp Pre-Alarm Enable 986 High Engine Temp Pre- Alarm Return 987 High Engine Temp Pre-Alarm Trip

On (1), Off (0) 0 Bar On (1), Off (0)
0.00 °C On (1), Off (0)
Shutdown (2), Electrical Trip (1), Disabled (0) 0 % 0 s On (1), Off (0) 0 % 0 % 0 s On (1), Off (0) 0 % 0 % 0 s
Shutdown (2), Electrical Trip (1), Disabled (0) 0 % 0 s
On (1), Off (0) 0 (Action) 0 % 0 % 0 (Arming) 0 (Action) 0 % 0 % 0 (Arming) 0 (Action) 0 % 0 % 00:00:00 On (1), Off (0) 0 (Arming) 0 (Action) 00:00:00 On (1), Off (0) 0.00 °C 0.00 °C

Configuration Parameters ­ Scheduler (Page 10) 1001 1002 1003
1004, 1008, 1012, 1016, 1020, 1024, 1028, 1032 1005, 1009, 1013, 1017, 1021, 1025, 1029, 1033 1006, 1010, 1014, 1018, 1022, 1026, 1030, 1034 1007, 1011, 1015, 1019, 1023, 1027, 1031, 1035

Enable Scheduler Schedule Run On or Off Load Scheduler Period Start Time (Entry 1 to 8) Day (Entry 1 to 8) Week (Entry 1 to 8) Duration (Entry 1 to 8)

On (1), Off (0) On (1), Off (0) Weekly (0), Monthly (1) 0:00:00 0 (1=Monday) 1, 2, 3 or 4 0 s

Configuration Parameters ­ Time (Page 11)

1101 Time of Day

0:00:00

1102 RESERVED

1103 RESERVED

1104 Day of Month 1105 Month of Year 1106 Year

1 to 31 1 to 12 0 to 99

Configuration Parameters ­ Maintenance Alarms (Page 12) 1201 Oil Maintenance Alarm Enable On (1), Off (0) 1206

1202 1203 1204 1205

Oil Maintenance Alarm Action 0 (Action)

Oil Maintenance Alarm Engine Hours

0 h

Air Maintenance Alarm Enable On (1), Off (0)

Air Maintenance Alarm Action 0 (Action)

1207 1208 1209

Air Maintenance Alarm Engine Hours
Fuel Maintenance Alarm Enable

0 h On (1), Off (0)

Fuel Maintenance Alarm Action 0 (Action)

Fuel Maintenance Alarm Engine Hours

0 h

Configuration Parameters ­ Alternate Configuration 1 (Page 20)

2001-2076

Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for configuration parameters.

Configuration Parameters ­ Alternate Configuration 2 (Page 30)

3002-3076

Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for configuration parameters.

Configuration Parameters ­ Alternate Configuration 3 (Page 40)

4002-4076

Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for configuration parameters.

AC System Index Type 0 2 Phase 3 Wire (L1 to L3) 1 2 Phase 3 Wire (L1 to L2) 2 3 Phase 3 Wire 3 3 Phase 4 Wire 4 3 Phase 4 Wire (Delta) 5 Single Phase 2 Wire

Digital Input Alarm Arming Index Arming
0 Always 1 From Safety On 2 From Starting 3 Never

Power Up Mode Index Mode 0 Stop 1 Manual 2 Auto

Functionality in DSE4510 MKII & DSE4520 MKII Functionality in DSE4520 MKII Auto Start and AMF Functionality in DSE4520 MKII AMF Only

Input Sources 0 User Configured 1 Remote Start on Load 2 RESERVED 3 Auto Start Inhibit 4 Lamp Test 5 Alarm Mute 6 Alarm Reset 7 RESERVED 8 Simulate Start Button 9 Simulate Stop Button 10 RESERVED
11 Simulate Auto Button
12 RESERVED 13 Close Generator Open Mains 14 Generator Load Inhibit 15 RESERVED 16 Close Mains Open Generator

17 18 19 20 21 22 23 24 25 26-30 31

Mains Load Inhibit RESERVED External Panel Lock Auxiliary Mains Fail Oil Pressure Switch Coolant Temperature Switch RESERVED Simulate Mains Available Remote Start Off Load RESERVED Auto Restore Inhibit

32 RESERVED

33 34 35-38 39 40

Low Fuel Level Switch Smoke Limiting RESERVED Main Configuration Alternative Configuration 1

41 Alternative Configuration 2

42 Alternative Configuration 3

43 Emergency Stop

44 RESERVED

45 Maintenance Reset Oil

46 Maintenance Reset Air

47 Maintenance Reset Fuel

48 RESERVED

49 RESERVED

50 DPF Auto Regen Inhibit

51 DPF Force Regeneration

52

DPF Regeneration Interlock

53 Water in Fuel

54 Fuel Bund Level High

55 Fan Speed Low

56 Low Coolant Level Switch

57 Wait To Start

Output Sources

0 Not Used

1 Air Flap Relay

2 Audible Alarm

3 Battery High Volts Warning

4 Battery Low Volts Warning

5 CAN ECU Data Fail

6 ECU (ECM) Warning

7 ECU (ECM) Shutdown

8 CAN ECU Power

9 CAN ECU Stop

10 Charge Alternator Shutdown

11 Charge Alternator Warning

12 Close Generator Output

13

Close Generator Output Pulse

14 Close Mains Output

15 Close Mains Output Pulse

16 Combined Mains Failure

17 Common Alarm

18 Common Electrical Trip

19 Common Shutdown 20 Common Warning 21 Cooling Down 22 Digital Input A 23 Digital Input B 24 Digital Input C 25 Digital Input D 26 RESERVED 27 RESERVED 28 RESERVED 29 Emergency Stop 30 Energise to Stop 31 Fail to Start 32 Fail to Stop 33 Fuel Relay 34 Gas Choke On 35 Gas Ignition

36 Generator Available

37

Generator High Voltage Alarm

38

Generator Low Voltage Alarm

39 kW Overload Alarm

40

Over Current Immediate Warning

41 Delayed Over Current Alarm

42

High Coolant Temp Shutdown

43 Low Oil Pressure Shutdown

44 Mains High Frequency

45 Mains High Voltage

46 Mains Low Frequency

47 Mains Low Voltage

48

Oil Pressure Sensor Open Circuit

49 Open Generator Output

50 Open Generator Output Pulse 51 Open Mains Output 52 Open Mains Output Pulse 53 Over Frequency Shutdown 54 Over Speed Shutdown 55 Preheat During Preheat Timer 56 Preheat Until End of Crank 57 Preheat Until End of Safety Timer 58 Preheat Until End of Warming 59 Smoke Limiting 60 Start Relay 61 Temperature Sensor Open Circuit 62 Under Frequency Shutdown
63 Under Speed Shutdown
64 Waiting for Manual Restore 65 Flexible Sensor C High Alarm 66 Flexible Sensor C High Pre-Alarm
67 Flexible Sensor C Low Pre-Alarm
68 Flexible Sensor C Low Alarm
69 RESERVED 70 RESERVED 71 RESERVED 72 RESERVED 73 Fuel Sensor High Alarm 74 Fuel Sensor High Pre-Alarm 75 Fuel Sensor Low Pre-Alarm 76 Fuel Sensor Low Alarm 77 Delayed Load Output 1 78 Delayed Load Output 2 79 Delayed Load Output 3 80 Delayed Load Output 4 81 Air Filter Maintenance 82 Oil Filter Maintenance 83 Fuel Filter Maintenance 84 System in Stop Mode 85 System in Auto Mode
86 System in Manual Mode
87 RESERVED
88 Analogue Input A (Digital)
89 Analogue Input B (Digital)
90 Analogue Input C (Digital)
91 RESERVED
92 RESERVED
93 RESERVED
94 RESERVED
95 Over Speed Overshoot Alarm
96 Over Frequency Overshoot Alarm
97 Display Heater Fitted and Active
98 RESERVED
99 SCR Inducement

100 DEF Level Low 101 DPF Auto Regeneration Inhibit 102 DPF Forced Regeneration 103 DPF None Mission State 104 DPF Regeneration in Progress 105 DPF Regen Interlock Active 106 DPTC Filter 107 HEST Active 108 Water in Fuel 109 Fuel Pull in Coil 110 Generator at Rest 111 Fuel Tank Bund Level High 112 ECU Preheat

113 Water Heater

114 Water Cooler

115 Closed to Gen

116 Closed to Mains

117

Generator Under Frequency Warning

118

Generator Over Frequency Warning

119 Generator Low Voltage Warning

120 Generator High Voltage Warning

121 Main Config Selected

122 Alt Config 1 Selected

123 Alt Config 2 Selected

124 Alt Config 3 Selected

125 Flexible Sensor A High Alarm

126 Flexible Sensor A High Pre-Alarm

127 Flexible Sensor A Low Alarm

128 Flexible Sensor A Low Pre-Alarm

129 Flexible Sensor A Open Circuit

130 Fan Speed Low

131 Fuel Usage Alarm

132 Low Coolant Level

133 Low Coolant Level Open Circuit

134 Waiting To Start

135 High Coolant Temp Pre-Alarm

136

Gen Over Frequency Delayed Alarm

137 Load Unbalance Alarm

138

Configurable CAN 1 Instrument Active

139

Configurable CAN 2 Instrument Active

140

Configurable CAN 3 Instrument Active

141

Configurable CAN 4 Instrument Active

142

Configurable CAN 5 Instrument Active

143

Configurable CAN 6 Instrument Active

144

Configurable CAN 7 Instrument Active

145

Configurable CAN 8 Instrument Active

146

Configurable CAN 9 Instrument Active

147

Configurable CAN 10 Instrument Active

Functionality in DSE4510 MKII & DSE4520 MKII Functionality in DSE4520 MKII Auto Start and AMF Functionality in DSE4520 MKII AMF Only

TYPICAL WIRING DIAGRAM
DSE4510 MKII & DSE4520 MKII

053-234 Issue 6
DEEP SEA ELECTRONICS
DSE4510 MKII & DSE4520 MKII Installation Instructions
Applicable to module version 3.0.0 and upwards.
EDITING A PARAMETER

· Press the Stop/Reset Mode to enter the editor mode.

( – ) and Auto Mode

() buttons together

· Press the Up

or Down

navigation buttons to cycle through the front

panel editor in increments of 100.

· Press the Manual/Start Mode ( + ) or Stop/Reset Mode
cycle through the front panel editor in increments of 1.

( – ) buttons to

· When viewing the parameter to be edited, press the Auto Mode and the value begins to flash.

() button

· Press the Manual/Start Mode ( + ) or Stop/Reset Mode
buttons to adjust the value to the required setting.

( – ) navigation

· Press the Auto Mode ceases flashing.

() button to save the current value, the value

· Press and hold the Auto Mode () button to save and exit the editor, the

configuration icon

is removed from the display.

NOTE: Pressing and holding the Manual/Start Mode

( + ) or

Stop/Reset Mode

( – ) buttons will give auto-repeat functionality.

DIMENSIONS
140 mm x 113 mm x 43 mm (5.5″ x 4.4″ x 1.7″)

PANEL CUTOUT
118 mm x 92 mm (4.6″ x 3.6″)

TERMINALS
Tightening Torque: 0.5 Nm (4.5 lb-in) Conductor Size: 0.5 mm² to 2.5 mm²
(AWG 20 to AWG 13)

NOTE: A larger version of the typical wiring diagram is included in
the product’s operator manual. Refer to DSE Publication: 057-260 DSE4510 MKII & DSE4520 MKII Operator Manual

NOTE: Terminals 25, 26, 27 & 28 are not fitted to the DSE4510 MKII

NOTE: More comprehensive module configuration is possible via PC configuration software. For further details of module configuration, refer to DSE Publication: 057-258 DSE4510 MKII & DSE4520 MKII Configuration Suite PC Software Manual.

Deep Sea Electronics Ltd Tel: +44 (0)1723 890099
Email: sales@deepseaelectronics.com Web: www.deepseaelectronics.com

Deep Sea Electronics Inc Tel: +1 815-316-8706 Fax: +1 815-316-8708
Email: USAsales@deepseaelectronics.com Web: www.deepseaelectronics.com

REQUIREMENTS FOR UL CERTIFICATION

Specification Screw Terminal Tightening Torque Conductors
Current Inputs

Description · 4.5 lb-in (0.5 Nm)
· Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to 2.5 mm²). · Conductor protection must be provided in accordance with NFPA 70, Article 240 · Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit. · The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to maintain at least ¼” (6 mm) separation from the generator and mains connected circuit
conductors unless all conductors are rated 600 V or greater.
· Must be connected through UL Listed or Recognized isolating current transformers with the secondary rating of 5 A max.

Communication Circuits

· Must be connected to communication circuits of UL Listed equipment

DC Output Pilot Duty Mounting
Operating Temperature

· 0.5 A · Suitable for use in type 1 Enclosure Type rating with surrounding air temperature -22 ºF to +158 ºF (-30 ºC to +70 ºC) · Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V device to be install in an unventilated or filtered ventilation
enclosure to maintain a pollution degree 2 environment. · -22 ºF to +158 ºF (-30 ºC to +70 ºC)

Storage Temperature

· -40 ºF to +176 ºF (-40 ºC to +80 ºC)

Read User Manual Online (PDF format)