17xxxx Duco Box Silent Box sensor Installation Guide
- June 14, 2024
- Duco
Table of Contents
DucoBox Silent
Product version 17xxxx and above
Installation guide
17xxxx Duco Box Silent Box sensor
Video instructions www.duco.tv
Translation of the original instructions
See www.duco.eu for information regarding warranty,
maintenance, technical data, etc.
Installation, connection, maintenance and repairs are to be carried out by an
accredited installer. The electronic components of this product may be live.
Avoid contact with water.
Introduction
Congratulations on your DucoBox Silent, the quietest box in Europe! The
DucoBox Silent performs two functions in a Duco Demand-Controlled Natural
Ventilation System:
On the one hand it is the extractor fan that exhausts stale air with excessive
CO2 content or humidity.
On the other it is the system ‘master’ or brain of the system. It receives and
interprets signals from slave components (measurements from sensors or manual
input), on the basis of which it controls the ventilation system.
It is inadvisable to connect the DucoBox (via a duct or directly) to an
extractor hood, regardless of type. This usually causes excessive fouling in
the DucoBox, which affects its operation or has a more direct effect on
output.
Product sheet
PRODUCT FICHE – Ref Delegated regulation (EU) n° 1253/2014
DucoBox Silent
Trade mark | Duco |
---|---|
Model reference | DucoBox Silent |
0000-4215 / 0000-4225 / 0000-4229 / 0000-4232 / 0000-4233 / 0000-4237 /
0000-4238 / 0000-4304 / 0000-4305 / 0000-4438 / 0000-4490 / 0000-4501 /
0000-4607
| Manual control (no DCV)| Clock control (no DCV)|
**Central demand control**
(+ 1 sensor)
| **Local demand control**
(+ min 2 sensors)
---|---|---|---|---
Specific energy consumption (SEC) in (kWh/(m².an))| cold| -30,5| –| -40,7|
-54,1
average| -14,1| –| -19,8| -27,0
warm| -4,8| –| -7,7| -11,5
SEC class
| cold| B| –| A| A+
average| E| –| E| B
warm| F| –| F| E
| | | |
Typology| Unidirectional| –| Unidirectional| Unidirectional
Type of motor| Variable speed| –| Variable speed| Variable speed
Type of heat recovery| None| –| None| None
Thermal efficiency of heat recovery in (%)| Not applicable| –| Not applicable|
Not applicable
Maximum flow rate in (m³/h)| 400| –| 400| 400
Electric fanpower input at maximum flow rate in (W)| 72,42| –| 72,42| 72,42
Sound power level Lwa at reference flow rate in dB(A))| 45| –| 45| 45
Reference flow rate in (m³/s)| 0,08| –| 0,08| 0,08
Reference pressure difference in (Pa)| 50| –| 50| 50
SPI en (W/m³/h)| 0,10| –| 0,10| 0,10
Control factor and control typology| 1
Manual control| –
–| 0,85
Central demand control| 0,65
Local demand control
Declared maximum internal leakage rates in (%)| Not applicable| –| Not
applicable| Not applicable
Declared maximum external leakage rates in (%)| 2,23%| –| 2,23%| 2,23%
Mixing rate in (%)| Not applicable| –| Not applicable| Not applicable
Position and description of visual filter warning| Not applicable| –| Not
applicable| Not applicable
Instructions to install regulated supply/exhaust grilles| Instructions
according to legislative regulations area of application
Pre-/dis-assembly instructions| www.duco.eu
Airflow sensitivity to pressure variations at + 20 Pa / -20Pa| Not applicable|
–| Not applicable| Not applicable
Indoor/outdoor air tightness in (m³/h)| Not applicable| –| Not applicable| Not
applicable
| | | |
Annual electricity consumption (AEC) in (kWh electricity/a)| 120,2| –| 86,8|
50,8
Annual heating saved (AHS) in (kWh primary energy/a)| cold| 3355| –| 4290|
5536
average| 1715| –| 2193| 2830
warm| 776| –| 992| 1280
PRODUCT FICHE – Ref Delegated regulation (EU) n° 1253/2014
DucoBox Silent 325
Trade mark | Duco |
---|---|
Model reference | DucoBox Silent 325 |
0000-5127
| Manual control (no DCV)| Clock control (no DCV)| Central
demand control
(+ 1 sensor)| **Local demand control**
(+ min 2 sensors)
---|---|---|---|---
Specific energy consumption (SEC) in (kWh/(m².an))| cold| -31,0| –| -41,1|
-54,3
average| -14,6| –| -20,1| -27,2
warm| -5,2| –| -8,1| -11,7
SEC class
| cold| B| –| A| A+
average| E| –| D| B
warm| F| –| F| E
| | | |
Typology| Unidirectional| –| Unidirectional| Unidirectional
Type of motor| Variable speed| –| Variable speed| Variable speed
Type of heat recovery| None| –| None| None
Thermal efficiency of heat recovery in (%)| Not applicable| –| Not applicable|
Not applicable
Maximum flow rate in (m³/h)| 325| –| 325| 325
Electric fanpower input at maximum flow rate in (W)| 45,73| –| 45,73| 45,73
Sound power level Lwa at reference flow rate in dB(A))| 41| –| 41| 41
Reference flow rate in (m³/s)| 0,06| –| 0,06| 0,06
Reference pressure difference in (Pa)| 50| –| 50| 50
SPI en (W/m³/h)| 0,08| –| 0,08| 0,08
**** Control factor and control typology| 1
Manual control| –
–| 0,85
Central demand control| 0,65
Local demand control
Declared maximum internal leakage rates in (%)| Not applicable| –| Not
applicable| Not applicable
Declared maximum external leakage rates in (%)| 2,74%| –| 2,74%| 2,74%
Mixing rate in (%)| Not applicable| –| Not applicable| Not applicable
Position and description of visual filter warning| Not applicable| –| Not
applicable| Not applicable
Instructions to install regulated supply/exhaust grilles| Instructions
according to legislative regulations area of application
Pre-/dis-assembly instructions| www.duco.eu
Airflow sensitivity to pressure variations at + 20 Pa / -20Pa| Not applicable|
–| Not applicable| Not applicable
Indoor/outdoor air tightness in (m³/h)| Not applicable| –| Not applicable| Not
applicable
| | | |
Annual electricity consumption (AEC) in (kWh electricity/a)| 100,9| –| 72,9|
42,6
Annual heating saved (AHS) in (kWh primary energy/a)| cold| 3355| –| 4290|
5536
average| 1715| –| 2193| 2830
warm| 776| –| 992| 1280
PRODUCT FICHE – Ref Delegated regulation (EU) n° 1253/2014
DucoBox Silent 225
Trade mark | Duco |
---|---|
Model reference | DucoBox Silent 225 |
0000-5126
| Manual control (no DCV)| Clock control (no DCV)| Central
demand control
(+ 1 sensor)| Local demand control
(+ min 2 sensors)
---|---|---|---|---
Specific energy consumption (SEC) in (kWh/(m².an))| cold| -31,3| –| -41,3|
-54,4
average| -14,9| –| -20,3| -27,4
warm| -5,5| –| -8,3| -11,9
SEC class
| cold| B| –| A| A+
average| E| –| D| B
warm| F| –| F| E
| | | |
Typology| Unidirectional| –| Unidirectional| Unidirectional
Type of motor| Variable speed| –| Variable speed| Variable speed
Type of heat recovery| None| –| None| None
Thermal efficiency of heat recovery in (%)| Not applicable| –| Not applicable|
Not applicable
Maximum flow rate in (m³/h)| 225| –| 225| 225
Electric fanpower input at maximum flow rate in (W)| 24,43| –| 24,43| 24,43
Sound power level Lwa at reference flow rate in dB(A))| 37| –| 37| 37
Reference flow rate in (m³/s)| 0,04| –| 0,04| 0,04
Reference pressure difference in (Pa)| 50| –| 50| 50
SPI en (W/m³/h)| 0,07| –| 0,07| 0,07
Control factor and control typology| 1
Manual control| –
–| 0,85
Central demand control| 0,65
Local demand control
Declared maximum internal leakage rates in (%)| Not applicable| –| Not
applicable| Not applicable
Declared maximum external leakage rates in (%)| 3,96%| –| 3,96%| 3,96%
Mixing rate in (%)| Not applicable| –| Not applicable| Not applicable
Position and description of visual filter warning| Not applicable| –| Not
applicable| Not applicable
Instructions to install regulated supply/exhaust grilles| Instructions
according to legislative regulations area of application
Pre-/dis-assembly instructions| www.duco.eu
Airflow sensitivity to pressure variations at + 20 Pa / -20Pa| Not applicable|
–| Not applicable| Not applicable
Indoor/outdoor air tightness in (m³/h)| Not applicable| –| Not applicable| Not
applicable
| | | |
Annual electricity consumption (AEC) in (kWh electricity/a)| 89,6| –| 64,7|
37,8
Annual heating saved (AHS) in (kWh primary energy/a)| cold| 3355| –| 4290|
5536
average| 1715| –| 2193| 2830
warm| 776| –| 992| 1280
Fitting
03.A Position
03.B Fixing
03.C Air duct connections
Keep down restriction.A non-return flap is required when discharging into a
manifold.
Be sure to take note of the ‘10 unmissable tips’ as well when fitting the
DucoBox. Avoiding excessive use of bends, especially angles greater than 90°
and adhering to the diameter guidelines for the ductwork will ensure that the
ventilation box is able to do its job satisfactorily. Failure to take account
of this recommendation may result in a highly energy and maintenance-intensive
system that gives rise to frequent excessive noise levels.
10 UNMISSABLE TIPS
The smooth running of your Duco ventilation system is totally dependent on the choice and the quality of implementation of the duct system!
Wiring
04.A Connector & buttons
CONNECTORS
1| Power 230 VAC
2| Perilex
3| Humidity Boxsensor
4| CO2
5| Boxsensor
6| Duco Network Tool
7| Fan
BUTTONS
A| UP
B| ENTER
C| DOWN
D| HIGH
E| LOW
F| INST
Illustrations and connections may vary depending on product configuration. Incorrect connection or failure to follow the instructions may result in damage to the connected devices.
Strain relief
It is mandatory to place the power supply cable in the slot provided, as shown
in the drawing, before powering up the DucoBox.
04.B Cabling diagram
The DucoBox Silent communicates with slave components through a wireless (RF) connection.RF components have a maximum free-field range of 350 metres.This distance will be much less in a building because of obstacles. Therefor you will need to allow for features such as walls, concrete and metal. All slave components (except those which are battery powered) also act as repeaters. Signals from components that are unable to make a (strong) connection with the master component are forwarded automatically via no more than one other component (= hop point). Please refer to information sheet RF communication (L8000018) at www.duco.eu for further information.
DUCO RF
Power supply| 230 VAC
Wiring| 1,5 mm²
Frequency| 868 Mhz
Maximum distance| 350 m, free field (less through obstacles)
Maximum number of components| Up to 25 wireless components in a
single system
Additional control options
*05.A 3-position switch via Perilex connector**
The last operation on any User controller takes primacy in all cases. The
ventilation position on the 3-position switch can therefore be overruled by
another User controller, such that an incorrect ventilation position will be
visible on the 3-position switch.
Please refer to the manual with the Duco Perilex plug for more information.
- The 3-position switch is not a DUCO component.
05.B Boxsensors
Boxsensors can be built into a DucoBox Silent and provide CO2 and/ or humidity
measurement in an air duct. A DucoBox Silent can contain a maximum of one CO2
and one Humidity Boxsensor. If the living room (CO2 measurement) and bathroom
(humidity measurement) are connected to the same duct/zone, the two Boxsensors
can be clipped together.
Fitting + connecting Boxsensor
- Twist the Boxsensor(s) into the desired duct in the box until the Boxsensor clicks home.
- Connect the Boxsensors to one of the two connectors provided on the DucoBox Silent PCB.
Electronical installation
06.A Change settings
Most of the factory settings for the network and components will be satisfactory as they are, however, depending on the situation, it may be desirable to change some parameters, such as the CO2 setpoint. This can be done using the Duco Network Tool This user-friendly software also enables problems in the system to be pinpointed. The Duco Network Tool is issued to every installer after attending a free training course at the Duco Academy Please refer to our website or your Duco dealer for further information.
- Only in Belgium and the Netherlands
06.B Installer / User mode
To add components to the network, remove or replace, the system should be put
in ‘Installer mode’. The LED on each component indicates the active mode of
the component (see table in next section). ‘Installer mode’ can be activated
by pressing the DucoBox Silent ‘INST’ button (see drawing in section “04. A
Connections & buttons” on page 8.) Once the LED on the master unit starts
flashing, it means that
‘Installer mode’ is active. Press ‘INST’ again to return to ‘User mode’ (LED
fully on or off). The system reverts automatically to ‘User mode’ after 15
minutes of inactivity.
06.C LED indications
| RED (blinking slowly) Not in network| RED (blinking rapidly) Logging in
---|---|---
| GREEN (blinking slowly) In network| GREEN (blinking rapidly) In network,
waiting for associated components
| YELLOW (clignotement rapide) Transitional phase (please wait)| YELLOW
(on) Initialising (system configuration in progress)
| WHITE or OFF
Normal
| BLUE
Component is displayed if changes are being put through via the master.
| ORANGE
The system is not working correctly because the DucoBox has not been
calibrated. Restart the DucoBox. Follow the guidelines in ‘10 essential tips’
if the problem recurs continually.
06.D Setting type of home
Setting the type of home and number of occupants correctly will provide the
ventilation system with a better basis to adjust the mid-position.There are
two types of home: low-rise (e.g. a house) and high-rise (e.g. a flat).
Configuration of this component is obligatory in the Netherlands. The standard
setting for a DucoBox is as a low-rise home for 4 (or more) occupants.
Setting type of home
- Ensure that ‘Installer Mode’ has been activated (via the ‘INST’ button).
- Press ‘LOW’ for a low-rise or ‘HIGH’ for a high-rise home
- The yellow LED (see illustration) will flash in a pattern that indicates the number of occupants: Once, twice (applies for 3 occupants as well) or 4 times (applies for 4 occupants or more). Press ‘LOW’ or ‘HIGH’ respectively again until the LED pattern matches the correct number of occupants.
- Press the ‘INST’ button to exit ‘Installer mode’
06.E Pairing components
Never pair more than one system with RF components at the same time. If you do
so, a component in the wrong network could be paired, e.g. in the neighbours’
DucoBox.
Pairing components on the DucoBox Silent
-
Activate ‘Installer mode’ by tapping ‘INST’ on the DucoBox. The LEDwill flash green rapidly.
Add control components by tapping once on the component to be paired. The LED will flash red briefly and then start to flash green rapidly. Repeat this step until all remaining components in the current zone have been paired. -
With RF components: start with the component closest to the master.If the first pairing is unsuccessful, another component may be tried first, which can then act as a hop point for components which are unable to make an RF connection with the DucoBox.
-
Once all components have been paired, ‘Installer mode’ can be deactivated by tapping ‘INST’ on the DucoBox Silent. LEDs on all components will stop flashing.
Please refer to the manual with the components for more detailed information.
Example of a pairing sequence
indicates the order in which a button of the component must be pressed controls component
06.F Removing / replacing components
Removing paired components from the network or replacing is only possible
within 30 minutes after the component is paired in or is restarted. Restarting
can be done by disconnecting the power for a moment. After a time-span of 30
minutes, remove and
replace operations are ignored. This is valid for all components from date of
manufacture 170323.
Removing a component
- Activate ‘Installer mode’ by long-pressing 2 diagonal buttons on a paired control. The LED will flash green rapidly.
- Press once and hold a button on the component to be removed in order to remove it from the network.
- Deactivate ‘Installer mode’ by pressing the 4 buttons on a paired control simultaneously (or using the palm of your hand on a control featuring touch buttons). The LED will turn white.
Replacing a component
- Activate ‘Installer mode’ by long-pressing 2 diagonal buttons on a paired control. The LED will flash green rapidly.
- Press briefly twice on the button of the component to be replaced.
- Tap once on the button for the new component. The latter will take on all settings / connections in the network.
- Deactivate ‘Installer mode’ by pressing the 4 buttons on a paired control simultaneously (or using the palm of your hand on a control featuring touch buttons). The LED will turn white.
06.H Tips
- Removing all components from the network (e.g. in the event of problems): Activate ‘Installer mode’ and long-press ‘INST’ until the LED starts flashing red. The DucoBox will reboot (around 15 seconds) and the LED will stop flashing.
- Restore factory settings for the DucoBox and all paired components (AS FROM DucoBox version 18xxxx): Long-press ‘INST’ and ‘ENTER’ if not in ‘Installer mode’. The network remains in place.
- Use the Duco Network Tool to read out information from components.
Air calibration
The system needs to be configured for it to work correctly. This will ensure
its operation is as quiet as possible and energy-efficient.
See under the Tools heading at www.duco.eu for
information about determining ventilation flow rates.
07.A Air calibration procedure for DucoBox Silent
The air calibration procedure must be carried out on a calm day (no more than wind force 2: leaves rustling, feeling the wind in one’s face).
Air calibrating the DucoBox Silent
- Set all exhaust vents so they match the desired flow rate in accordance with the table below. Proper pre-setting makes for rapid and correct configuration.
Flow rate| DucoVent Design| DucoVent Basic and other vents
---|---|---
75m3/h| | 100% open
50m3/h| | 50% open
25m3/h| | 25% open
When using DucoVent Design exhaust vents always leave the outer ring in place for acoustic effect.
-
Before activating air calibration mode:
• Close all windows and doors.
• Ensure that all duct openings in the DucoBox are fully closed and that the DucoBox cover is closed!
• Avoid air leaks in the ventilation ducts.
• Set all window ventilators to the open position Press ‘HIGH’ or ‘LOW’ to activate the configuration mode for 30 minutes. Then close the cover firmly. -
Which configuration mode should I choose?****
Button| Air calibration using ‘HIGH’
This method is standard and has the lowest consumption. Recommended in the majority of homes.
| Air calibration using ‘LOW’
This method offers a boost mode but may give rise to more noise and higher consumption.
---|---|---
| Low mode (10%)| Low mode (14-33%)
| Medium mode (50%)| High mode (100%)
| High mode (100%)| Boost mode (143-333%)
The percentages in the table indicate what percentage of the flow rate
configured will be extracted.
The configuration mode chosen does not affect the operation of the AUTO mode.
-
In the ‘LOW’ configuration, the percentage in low mode and boost mode is dependent on the type of home (see section “06.D Setting type of home” on page 10) and limited to the maximum achievable ventilation system flow rate.
-
Close the DucoBox cover.
Ensure it forms an airtight seal with the DucoBox. -
Select the duct with the highest flow rate and restriction.
-
Measure at the vent and adjust the DucoBox rpm until the desired flow rate is obtained. This can be done in two ways:
Using the (lower) and (higher) buttons on a paired User controller or CO2 / Humidity Sensor*.
Using the ‘DOWN’ and ‘UP’ buttons on the DucoBox. This requires the cover to be removed temporarily. Always close the cover after every measurement.Pressing the buttons once is equal to 1% (= approximately 2 to 3 m3/h per press of the button depending on the restriction in the ducts). -
Now measure the other vents. The flow rate from these other vents must only be adjusted at the vents themselves.
-
Repeat steps 6 and 7 until the desired flow rate has been obtained at each vent.
-
Exit configuration mode. This can be done in two ways:
• Long-press ‘AUTO’ on a paired User controller or CO2 /Humidity sensor until the 4 LEDs light up white briefly and then turn yellow again.
• Press ‘ENTER’ in the DucoBox and then immediately close the cover on the DucoBox. If the cover was not closed, you can pull the plug out of the power socket for a few seconds after closing the cover in order to reboot the DucoBox.
The DucoBox will now perform a calibration by speeding up high. This may take up to 1.5 min. Calibration will be complete once the DucoBox slows down the ‘AUTO’ button LEDs on the User controllers / CO2 /Humidity sensors will turn white, as will the LED on the DucoBox.
-
-
Depending on the software version of the User controller / CO2 /Humidity sensor.
07.B Checking
The steps set out below can be used to check whether flow rates have been set
correctly.
Checking configured flow rate
-
The configured flow rate is dependent on whether the ‘HIGH’ or ‘LOW’ configuration mode has been chosen.
Press for ‘HIGH’ configuration (= standard) or for ‘LOW’ configuration on a random control to have the system run for 15 minutes at 100% of the requested flow rate. -
Measure the flow rate at the exhaust vents.
-
After the check, the system can be reset to the desired ventilation mode. If you do not do so, the system will revert automatically to the AUTO mode after 15 minutes.
Maintenance & service
Please refer to the maintenance instructions at www.duco.eu and view the videos on duco.tv for more information.
For service problems as a user:
Please contact your installer. Keep the serial number of your product to hand.
For service problems as an installer:
Please contact your Duco products seller. Keep the serial number of your
product to hand.
Warranty
All warranty conditions concerning the DucoBox and Duco’s ventilation systems
can be found on the Duco website.
All complaints are to be reported to Duco by the Duco distributor with a clear
description and the order/invoice number under which the products were
delivered. In order to register the complaint, please use the complaint
registration form found on the Duco website and the product’s serial number in
your message to service@duco.eu.
Installed by:
L2000651 Document last modified on 15.11.2023 (revision O)
Vero Duco – Handelsstraat 19 – 8630 Veurne – Belgium
tel +32 58 33 00 33
fax +32 58 33 00 44
info@duco.eu
www.duco.eu
L2000651 Installation guide for DucoBox Silent (Revision O | 15.11.2023)
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>