Danfoss FCP-106 Wall Mount Plate Drive Motor Instruction Manual
- June 1, 2024
- Danfoss
Table of Contents
Installation Instructions
Wall Mount Plate
VLT® DriveMotor FCP 106
These installation instructions provide information on how to mount the VLT® DriveMotor FCP 106 on a wall.
Only Danfoss authorized, qualified personnel is allowed to install this equipment. The personnel must be familiar with the instructions and safety measures described in the VLT® DriveMotor FCP 106 & FCM 106 Service Guide.
Items Supplied
- Wall mount plate
- Accessory bag
– Motor plug
– Gasket
– Wall mount plug housing
– Wall mount plug housing gasket
– Wall mount cover for plug housing
– Screws
– Crimp terminals
– 134B0497 (1-2.5 mm²) [AWG 17-14], MH1
– 134B0498 (2.5-4 mm²) [AWG 14-12], MH2 and MH3
Enclosure size | Ordering number |
---|---|
MH1 | 134B0341 |
MH2 | 134B0391 |
MH3 | 134B0441 |
Table 1.1 Ordering Numbers, Wall Mount Plate
Additional Items Required
- FCP 106 frequency converter.
- Motor cable, suitable for Type 4X.
- Cable gland, suitable for Type 4X.
- Grabber tool, TE ordering number 1-1579007-6.
– Gripper for all crimp contacts: TE ordering number 539635-1.
– Crimp die for MH1, 600 V, 3.7 A, 16 AWG: TE ordering number 539733-2.
– Crimp die for MH2, 600 V, 9 A, 14 AWG: TE ordering number 539734-2.
– Crimp die for MH3, 600 V, 15.5 A, 12 AWG: TE ordering number 539734-2
Safety Instructions
For important information about safety precautions for installation, refer to VLT® DriveMotor FCP 106/FCM 106 Operating Instructions.
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain
charged even when the frequency converter is not powered. High voltage can be
present even when the warning LED indicator lights are off. Failure to wait
the specified time after power has been removed before performing service or
repair work can result in death or serious injury.
- Stop the motor.
- Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
- Disconnect or lock PM motor.
- Wait for the capacitors to discharge fully. The minimum duration of waiting time is specified in Table 1.2.
- Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Voltage
[V]| Power Range 1)
[kW (hp)]| Minimum waiting time
(minutes)
---|---|---
3×400| 0.55–7.5 (0.75–10)| 4
Table 1.2 Discharge Time
- Power ratings relate to normal overload, see VLT® DriveMotor FCP 106/FCM 106 Operating Instructions.
Preparing for Wall Mounting
Improper mounting can result in overheating and reduced performance.
Cooling
To ensure sufficient air flow for the frequency converter, observe the minimum
clearances listed in Table 1.3.
When air flow is obstructed close to the frequency converter, ensure adequate
inlet of cool air and exhaust of hot air from the unit.
Enclosure
| Power 1)
[kW (hp)]| Clearance at ends
[mm (in)]
---|---|---
Enclosure size| Protection rating| 3×380-480 V| Terminal
end|
Cooling fan end
FCP 106 with wall mount plate
MH1| IP66/Type 4X2)| 0.55-1.5 (0.75-2.0)| 30 (1.2)|
100 (4.0)
MH2
| IP66/Type 4X2)| 2.2-4.0 (3.0-5.0)| 40 (1.6)| 100 (4.0)
MH3| IP66/Type 4X2)| 5.5-7.5 (7.5-10)| 50 (2.0)|
100 (4.0)
Table 1.3 Minimum Clearance for Cooling
- Power ratings relate to NO, see chapter Electrical Data in the VLT® DriveMotor FCP 106/FCM 106 Design Guide.
- The stated IP and Type rating only apply when the FCP 106 is mounted on a wall mount plate. When mounted on a wall mount plate, the standalone frequency converter has enclosure rating IP00 and Open type.
Lifting
- To determine a safe lifting method, check the weight of the unit, see chapter Specifications in the VLT® DriveMotor FCP 106/FCM 106 Design Guide.
- Ensure that the lifting device is suitable for the task.
- If necessary, plan for a hoist, crane, or forklift with the appropriate rating to move the unit.
- For lifting, use the hoist rings on the unit, when provided.
Mounting
- Ensure that the strength of the mounting location supports the unit weight. The frequency converter allows side-by-side installation.
- Locate the unit as near to the motor as possible. Keep the motor cables as short as possible.
- Use the slotted mounting holes on the unit for wall mounting, when provided.
- Crimp wires according to Illustration 1.1 to Illustration 1.4.
1 | Conductor present |
---|---|
2 | Insulation present |
3 | Bellmouth must always be present |
4 | Bellmouth allowed |
5 | Locking lances and terminal body not deformed |
6 | Cut-off tabs present |
Illustration 1.1 Correct Selection of Wire, Terminal, and Applicator
1 | Crimp barrel closed – legs support each other |
---|---|
2 | Sufficient gap between legs and bottom of crimp |
Illustration 1.2 Correct Wire Crimp
Illustration 1.3 F-crimp – Insulation Securely Held, Crimp Barrel Closed
Illustration 1.4 Overlap Crimp – Insulation Securely Held, Legs overlap
1 | Wall mount plate | 8 | Motor connector |
---|---|---|---|
2 | Cover screws | 9 | Motor wires and crimp terminals |
3 | Plug housing cover | 10 | Motor thermistor wires |
4 | Plug cover gasket | 11 | PE wire |
5 | Plug housing | 12 | Motor cable |
6 | Plug housing screws | 13 | Cable gland |
7 | Motor connector gasket | 14 | Wall mount plate screws |
Illustration 1.5 Exploded View
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
130R0561 MI03P102 02/2016