Danfoss FC 280 VLT Midi Drive Installation Guide

June 1, 2024
Danfoss

Danfoss LOGO Installation Guide
Terminal Torque Instructions
VLT® Midi Drive FC 280

Installation Instructions

1.1 Description
These instructions give information on the torque values for the terminal blocks used in the VLT® Midi Drive FC 280.
1.2 Part Numbers
Table 1: Accessory Bag Numbers (Cannot be Ordered as Spare Parts)

Drive Description Part number
VLT® Midi Drive FC 280 Terminals for enclosure sizes K1–K3.
Plug item: 1, 2, 3, 4, 5, 6, 7. 132B0420

Terminals for enclosure sizes K4–K5.
Plug item: 1, 2, 3, 4.| 132B0798
VLT® Midi Drive FC 280 with Ethernet Safety Functions| Accessory bag, plugs K1–K3.
Plug item: 1, 4, 5, 6, 7, 10, 11.| 132B0421
Accessory bag, plugs K4–K5.
Plug item: 1, 4, 10, 11.| 132B0799

Table 2: Spare Part Numbers

Description Ordering number

Terminals for enclosure sizes K1–K5.
Plug item: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11.| 132B0350

1.3 Safety Precautions
Only Danfoss qualified personnel is allowed to install this equipment.
For important information about safety precautions for installation, refer to the drive’s Operating Guide.
1.4 Tools Required

  • SZS 0.6×3.5 mm slot screwdriver.

1.5 Torque Instructions

NOTICE
DESTRUCTION OF TERMINALS OR LOOSE CABLES
Applying too much torque can destroy the terminal blocks. Applying too low torque can result in loose cables.

  • Only use a screwdriver as specified in 1.4 Tools Required.
  • Apply the needed tightening torque as specified in Table 3.
  • Do not apply more torque than the maximum torque as specified in Table 3.

Danfoss FC 280 VLT Midi Drive - Terminals

Table 3: Tightening Torque for Terminals

Item| Designation| Tightening torque [Nm (in-lb)]| Maximum torque [Nm (in-lb)]
---|---|---|---
1| Plug connector, relay 1| 0.5 (4.4)| 0.6 (5.3)
2| I/O terminal plug, 10-pole| 0.35 (3.1)| 0.4 (3.5)
3| I/O terminal plug, 5-pole
4| I/O terminal plug, 3-pole
5| Motor plug, 3-pole 7.62| ≤4 mm2/AWG 12: 0.5 (4.4),

4 mm2/AWG 12: 0.7 (6.2)

| ≤4 mm2/AWG 12: 0.6 (5.3),

4 mm2/AWG 12: 0.8 (7.1)
6| BR DC plug, 3-pole 7.62
7| Mains plug, 3-pole 7.62
8| CANopen plug, 5-pole| 0.5 (4.4)| 0.6 (5.3)
9| PROFIBUS plug, 5-pole
10| IO plug, 5-pole, 5 mm| 0.35 (3.1)| 0.4 (3.5)
11| IO plug, 8-pole, 5 mm

Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com

Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice.
This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S © 2021.12
AN375526175644en-000101 / 132R0174

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals