Safety Instructions

These instructions describe the replacement and the software update for the control card in VLT® HVAC Basic Drive FC 101.

Only Danfoss-authorised, qualified personnel is allowed to repair this equipment. The personnel must be familiar with the instructions and safety measures described in the VLT® HVAC Basic Drive FC 101 Service Manual.
Symbol

DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. Failure to wait the specified time after power has been removed before performing service or repair work, can result in death or serious injury.

  • Stop motor.
  • Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DClink connections to other frequency converters.
  • Disconnect or lock PM motor.
  • Wait for the capacitors to discharge fully, before performing any service or repair work. The duration of waiting time is specified in Table 1.1.
    Table 1.1 Discharge Time Voltage [V]| Power Range [kW]| Minimum waiting time (min)
    ---|---|---
    3×200| 0.25–3.7| 4
    3×200| 5.5–11| 15
    3×400| 0.37–7.5| 4
    3×400| 11–90| 15
    3×600| 2.2–7.5| 4
    3×600| 11–90| 15
    High voltage can be present even when the warning LED indicator lights are off.

Item Supplied

The following item is supplied:

  • Control Card

Additional Items Required

  • FC 101 frequency converter
  • MCT 10 Set-up Software. The software must be activated to support the Drive Software Upgrader feature. For information about activating the software, contact the Danfoss sales office.
  • USB to RS-232 Converter
  • The OSE file containing the appropriate control card software.

Obtaining the OSE file
Download the appropriate OSE file from the Danfoss Intranet site or get it from a Danfoss sales office. When contacting the Danfoss sales office, provide the frequency converter order number, listed as “P/N” on the frequency converter nameplate.

To download the OSE file from the Danfoss Intranet site:

  1. On the Danfoss Intranet home page, select Danfoss Power Electronics > Marketing & Segments > Product Management > VLT® HVAC Basic Drive FC 101.
  2. In the Software updates section, select the appropriate file:
    2a P618 platform: select the ZIP file with the following name: FC- 101_vX_XX_OSE_P618. X_XX stands for the latest software version number. In the ZIP file, select the OSE file that matches the order number of the frequency converter, listed as ”P/N” on the frequency converter nameplate.
    2b P619 platform: select the FC-101_P619_vX_XX_OSE.ose file.

Replacing the Control Card

Follow the instructions in the VLT® HVAC Basic Drive FC 101 Service Manual to disassemble the frequency converter and replace the control card.

Upload the Software

To upload the new software to the control card:

  1. Connect the frequency converter to the computer where the MCT 10 Set-up Software is installed. For wiring instructions, see MCT 10 Set-up Software Operating Instructions, chapter Set-up of Communication.

  2. Power up the frequency converter with the new control card installed. The LCP may show the alarm AL 038 Internal Fault. This is normal operation.

  3. Start MCT 10 Set-up Software.

  4. Configure the bus. In the Network group, right-click Serial and select Configure Bus.
    Upload the Software
    The Serial fieldbus configuration dialog box opens.
    Upload the Software

  5. Scan the bus for active drives. In the Network group, right-click Serial and select Scan Bus for Active Drives.
    Upload the Software

  6. The MCT 10 Set-up Software shows the Scanning for Drives dialog box.

  7. When the scanning is complete, the frequency converter appears under Serial item.
    Upload the Software

  8. Right-click Serial and select Drive Software Upgrader.
    Upload the Software

  9. In the Drive Software Upgrader dialog box, click Browse. In the prompt dialog box, select the appropriate OSE file and click OK.
    Upload the Software
    When an OSE file is selected in the Firmware file field, the Drive Software Upgrader dialog box shows the Start upgrade button.

  10. Click Start upgrade. The Drive Software Upgrader dialog box shows the Upgrading Software step.
    Upload the Software

  11. When the software upgrade process is finished, the following message appears:
    Upload the Software

  12. To confirm successful software upgrade, open parameter 15-43 Software Version and check that the software version in the frequency converter is the same as the version in the OSE file.
    Upload the Software

Now the control card contains the appropriate software and the frequency converter is ready for operation.

Customer Support

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without sub sequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S Ulsnaes 1 DK-6300 Graasten
www.danfoss.com/drives
Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Danfoss User Manuals

Related Manuals