THERMOLEC THERMO-AIR and THERMO ZONE Units Instruction Manual

June 17, 2024
THERMOLEC

THERMOLEC logo Instruction Manual

Installation Instructions for THERMO-AIR and THERMO-ZONE units.
Please read instructions carefully before starting.

Mechanical Installation.

  1. The air direction may be either vertical or horizontal, but when the unit is installed horizontally, the cut-out cover must be on top.THERMOLEC THERMO AIR and THERMO ZONE Units - Installation

  2. Do not install elbows closer than 12 inches to either the inlet or outlet of the unit.

  3. The electronic controller shuts down the heater when there is no air fl ow.
    The minimum amount of air required (in cubic feet per minute) to operate the unit is given in the CFM column of the table (30 CFM per kilowatt).
    If CFM is lower than specifi ed, the airfl ow sensor will limit the total capacity according to the airfl ow available.

  4. Attach the unit to a suitable support.
    The 6” model is small enough to be located between standard 16” spaced fl oor joists.
    Always allow a minimum 1/2” clearance above the heater.THERMOLEC THERMO AIR
and THERMO ZONE Units - Installation 2

  5. Electrical Installation.
    Please conform to all local and national electrical codes for wiring. The heater should be supplied by a separate cable, of appropriate gauge and with appropriate protection.
    Use wires suited for 75ºC. Please refer to the following table Fig. 1.THERMOLEC THERMO AIR and THERMO ZONE Units - Installation
3THERMOLEC THERMO AIR and THERMO ZONE
Units - Installation 5DIMENSIONS IN INCHES

SIZE  X   Y   Z
A 11.5 8 11.5
B 11.5 10 13.5
C 15.5 12 15.5
  1. Special Instructions for each type of unit.
    THERMO-AIR (TER models in Fig. 1)
    When the unit is installed and connected, set the potentiometer on the controller to the desired temperature.
    Please check the air direction carefully. The temperature sensor must be located on the air outlet side. The sensor is factory installed on the left side, so the air moves from the right to the left. It has to be moved to the right if the air outlet is on the right side. A pre-punched rectangular hole is provided on the right side to accommodate this change. In the lower part of the table (Fig. 1) starting at SIZE C, the unit becomes bigger and the heater is split in two halves, preheat and reheat, each one supplied by its own controller and equipped with safety limits.
    Following the air direction, the fi rst half thus becomes the preheat section and the second half becomes the reheat section. The position of the sensors is very important. Please check the air direction through the heater carefully. In this model, there are three rectangular holes to allow the change of heat sensor position. Set the preheat controller to the desired output temperature and the reheat controller to 2 ºC (4 ºF) lower. During milder temperatures the preheat controller will be able to handle the full load without engaging the reheat controller. Please refer to the following diagrams.THERMOLEC THERMO
AIR and THERMO ZONE Units - Instructions 1The Thermo-Zone unit uses a different controller which works with a 0-10VDC Thermostat. Connect the thermostat wires as indicated in the wiring diagram.
    If you don’t fi nd the exact model you need in the table, please order a standard Thermolec heater equipped with SCR control.
    Remember : In case of trouble or for technical assistance, please use our free Help Line:

1-800-336-9130THERMOLEC