DCC-10
Electric Vehicle Energy
Management System (EVEMS)
INSTALLATION MANUAL
MODELS
DCC-10-30A, DCC-10-40A, DCC-10-50A, DCC-10-60A
DCC-10-30A-3R, DCC-10-40A-3R, DCC-10-50A-3R, DCC-10-60A-3R
LTEE DCC 10 Electric Vehicle Energy
MAIN POWER SUPPLY
120/240-208V, Single Phase
60A – 70A – 80A – 90A
100A – 125A – 150A – 200A
APPROVED MARKET
North America
Read and save these instructions
Manufactured by
Designed by
V11
ABOUT THIS MANUAL
ERRORS AND INACURACIES
For any inaccuracy or omission, or to forward any general comments or
suggestions concerning the quality of this manual, please send an email to
info@dccelectric.com.
COPYRIGHTS AND TRADE NAMES
All information’s in this manual are subject to copyright protection and other
intellectual property protection of THERMOLEC LTÉE. / RECHARGE VÉHICULE
ÉLECTRIQUE and its licensors. This installation manual cannot be modified,
reproduced or copied without a prior written authorisation from THERMOLEC
LTÉE. / RECHARGE VÉHICULE ÉLECTRIQUE and its licensors. Additional
information’s are available on request. The following logos are trade names or
trademarks of THERMOLEC LTÉE. / RECHARGE VÉHICULE ÉLECTRIQUE in the United
States and in Canada.
All other trade names mentioned in this document are the property of their
respective owners and their uses in this manual does not means a sponsorship
or approval of the product. The use of any trade name shown in this document
is strictly forbidden.
In this document, the terms DCC – EVEMS and DCC are equivalent.
SAFETY INFORMATION
This document describes important safety instructions which must be followed during installation, maintenance and application of the DCC – Electric Vehicle Energy Management System (EVEMS).
Warning
Read all instructions prior using this product.
Always disconnect the DCC – EVEMS power supply before any works.
Use only the DCC – EVEMS by following the technical specifications indicated
in this installation manual.
Do not install the DCC – EVEMS nearby inflammable materials, explosives or
fuels, chemical products and vapors.
Never spray the DCC – EVEMS with water or any other liquids.
Stop using the DCC – EVEMS immediately if defective, cracked, broken or
damaged.
Never try to modify, repair or dismantle the DCC – EVEMS. Please contact the
manufacturer for any malfunction.
Never insert a sharp object inside the DCC – EVEMS at the risk of causing
damages to the components.
Any improper use of the DCC – EVEMS could result in serious injuries which may
cause death.
For a vertical installation on a wall, refer to the information’s on the
enclosure for the choice of mounting position.
Precautions
Any improper use of the DCC – EVEMS can cause damages and premature wear of
the components, which voids the warranty.
Never use the DCC – EVEMS above or below the temperature range of -22 °F to
113 °F (-30 °C to 45 °C).
Only store the DCC – EVEMS above or below the temperature range of -4 °F to
158 °F (-20 °C to 70 °C).
The installation of the DCC – EVEMS must be done in accordance with the latest
electrical code requirements.
Notes
It is recommended to schedule the charging of the vehicle during hours of low
electrical consumption to minimize interruptions to the electric charging
station.
Always check that the DCC – EVEMS is adequately fixed to the wall or ceiling
or in a location to avoid any damages.
Even if this product is advertised for EV chargers, it can be installed with
other types of load.
It is the installer’s responsibility to make sure that the electric power
source is adequate for the use of the DCC – EVEMS.
Do not use any cleaning solvents to clean the DCC – EVEMS.
Limited warranty
-
THERMOLEC LTÉE. warrants the integrated controls against any defects for a period of one year from the shipping date. The warranty is limited to the equipment and components supplier by THERMOLEC LTÉE.
-
In case of incorrect installation, inappropriate use or repairs done by unauthorized personnel by THERMOLEC LTÉE., the warranty will be automatically void.
-
THERMOLEC LTÉE. undertakes to repair or replace, at site or at the manufacturing location, at his option, the defective material only after an evaluation made by its representative.
-
THERMOLEC LTÉE. will not be held liable for damages or delays and will not be required to pay transport cost of the EVEMS said to be defective.
-
THERMOLEC LTÉE. shall not be liable for any indirect damages or delays caused by faulty workmanship or materials.
No indemnity will be paid for repairs, replacements or modifications without a prior written consent supplied by THERMOLEC LTÉE. -
Any control device or accessory supplied with the DCC – EVEMS to be installed or connected remotely from the EVEMS will be guaranteed by the manufacturer only under the special conditions mentioned in paragraph 5.
-
The components supplied for repairs are guaranteed for the remaining of the warranty on the original product or 90 days. The longest period will prevail.
-
All repairs made at the THERMOLEC LTÉE. plant are guaranteed for 30 days from the date of repairs.
SPECIFICATIONS
The DCC – Electric Vehicle Energy Management System (EVEMS) is a safety device with programmable controller that can protect an electrical distribution circuit in relation with its main breaker. It will prevent overloading the electrical distribution circuit by turning off momentarily the power to the charging station when the demand exceeds 80% of the main breaker rating.
CHARACTERISTICS
CONDITIONS FOR APPLICATION
The DCC-10 is an Energy Management System specially designed to allow the
connection of an EV Charger, in a house or dwelling, to an electrical panel
that is at full capacity and would otherwise need to have an expensive service
upgrade.
MAIN POWER SUPPLY (CB)
The DCC – Electric Vehicle Energy Management System (EVEMS) can be powered by
a 240/208V AC single phase source.
The following options are offered by each DCC model:
Models | Breaker | Main power supply |
---|---|---|
EV charger | 60A | 70A |
DCC-10-30A | 30A | |
DCC-10-40A | 40A | |
DCC-10-50A | 50A | |
DCC-10-60A | 60A |
SECONDARY LOAD SUPPLY (EVC)
The DCC – EVEMS will provide power to a charging station through a 30A, 40A,
50A or 60A 240/208V AC circuit breaker, L1, L2 and ground.
The DCC is equipped with a Square D circuit breaker (QU0230, QU0240, QU0250 or
QU0260).
TRIP PERCENTAGE (TP)
The DCC – EVEMS is factory set to turn off the charging station if the total
consumption of a service exceeds 80%. For other configurations, please contact
the factory.
POWER OUTAGE
In the event of a power outage, the DCC – EVEMS automatically restore the
power supply to the vehicle charging station when power returns.
RECOVERY TIME (RT)
Following a power cut to the electric vehicle supply equipment (EVSE), a 15
minutes delay is initiated to monitor the total consumption of the electrical
power system. Power to the vehicle will then be restored if the total load
consumption is lower than 80% of the main circuit breaker rating during a
period exceeding the 15 minutes’ recovery time.
TYPICAL INSTALLATION
NOTES
For outdoor installation, use our NEMA 3R enclosure
(DCC-10-XXA-3R).
DCC INSTALLATION
STEP 1: CHECK THE PACKAGE CONTENTS
INSTALLATION VIDEO
To access our installation video,
visit our website www.dccelectric.com
STEP 2: PREPARATIONS FOR INSTALLATION
-
Disconnect the main power
-
Select the DCC intended location. Select an intended location preferably less than 25 feet away from the electric panel (power source). The current transformers supplied have a wiring of 25 feet in length, but can be extended (see the section Step 4: Conductor connexons for the extension details).
The DCC can be mounted:
– on a ceiling
– on a wall
NOTE: The DCC controller must be mounted so that the nameplate remains visible at all times.
Do not install the DCC:
– Outdoor, unless the DCC is ordered with our NEMA 3R enclosure.
– In a location with high level of risk.
– Nearby inflammable materials, explosives or fuels, chemical products and vapors. -
Before installation, check the DCC mounting position.
Wall installation| Ceiling installation
---|---
Refer to the information on the enclosure to insure proper installation.| The installation may be done
in any direction.
WARNING
Warranty automatically void if the DCC is installed incorrectly.
STEP 3: INSTALLATION
Ceiling installation
- Remove the 4 cover screws.
- Fix the ceiling mounting support on the DCC.
- Lift the DCC using the ceiling mounting support.
- Position the DCC at the intended location.
- Fix the DCC with the anchors for the type of surface.
- Check that the DCC is adequately fixed to the wall or ceiling.
- Remove the ceiling mounting support.
Wall installation
- Remove the 4 cover screws.
- Position the DCC at the intended location.
- Ensure that the mounting is according with the information’s on the enclosure.
- Fix the DCC with the anchors provided for the type of surface.
- Check that the DCC is adequately fixed to the wall or ceiling.
STEP 4: CONDUCTOR CONNEXIONS
Consult the diagram on the next page for all details on the cable connections
configuration. This diagram is also found under the DCC cover.
Current transformers (CT) installation and connections
- Open the CT.
- Install the CT around the main power cable of the panel.
- Check the correct polarity on the CTs.
- Connect the CT cables to the terminal block, provided for that purpose, inside the DCC.
EXTENSION OF CURRENT TRANSFORMERS’S WIRE
The DCC comes with 25 feet of wire. It is possible to extend the wiring
supplied with the current transformers.
Additional wire must be 300V rated, minimum 18 AWG (1mm), 4 conductors
shielded twisted (ex: FT4 SHIELD. 4C FAS #18 or equivalent).
LEGEND
R | POWER RELAY |
---|---|
dcc | ELECTRONIC CONTROLLER |
cb | CIRCUIT BREAKER |
c | TRANSFORMER |
ct | CURRENT TRANSFORMER |
IMPORTANT
Wire in accordance with local and National Electrical codes.
Read instructions carefully before wiring and operating.
CONFIGURATION DIAGRAMS Main Circuit Breaker (Amps)
Main power supply
Models | 60A | 70A | 80A | 90A | 100A | 125A | 150A | 200A |
---|---|---|---|---|---|---|---|---|
DCC-10-30A | ||||||||
DCC-10-40A | ||||||||
DCC-10-50A | **** | |||||||
DCC-10-60A | ||||||||
Trip Percentage (%)
Reintegration Time (Minutes) EV Charger (Breaker)
Trip Delay : 15 seconds (Default)
TO INSTALL AROUND THE POWER SUPPLY CABLE
TITLE
DCC-10 CONTROLLER GEN 3
BOITIER DE CONTROLE DCC-10 GEN 3
DRAWING NO. DCC-10 CONTROLLER
DATE
09-23-2021| PER| THERMOLEC V.7
DCC V.13
STEP 5:
DIP SWITCH PROGRAMMING FOR MAIN POWER SUPPLY
- Identify the set-up section on the DCC.
- Set up the section as per the layout corresponding to the main power supply :
Models | 60A | 70A | 80A | 90A | 100A | 125A | 150A | 200A |
---|---|---|---|---|---|---|---|---|
DCC-10-30A | ||||||||
DCC-10-40A | ||||||||
DCC-10-50A | ||||||||
DCC-10-60A | ||||||||
STEP 6: START-UP
DCC power supply
- Supply electrical power to the DCC.
- Wait ten (10) seconds.
- Check if the relay is switched on.
- Check the pilot light:
GREEN at all time: compliant installation, go to the next step.
RED: refer to the Lights code section.
Charging station power supply
- Put the circuit breaker in the ON position.
- Check if the electric vehicle supply equipment (EVSE) is powered:
EVSE powered: go to the next step.
EVSE not energized: check the charging station connections.
STEP 7: SECURE AND RE-ENERGIZE
Secure
- Turn off the power on the DCC.
- Put the cover back.
Re-energize
- Supply electrical power to the DCC.
STEP 8: IDENTIFICATION
- Identify the branch circuit breaker.
- Register all configuration settings of the charging station in the space provided on the cover.
APPLICATION
Electric vehicle recovery time
Following a power cut to the electric vehicle supply equipment (EVSE), a 15
minutes delay is initiated to monitor the total consumption of the electrical
system. Power to the vehicle will then be restored if the total load
consumption is lower than 80% of the main circuit breaker rating.
Electric vehicle charging time
It is recommended to schedule the charging vehicle program during hours of low
electrical consumption to minimize interruptions to the electric charging
station.
MAINTENANCE
Do not use any cleaning solvents to clean the DCC.
LIGHTS CODE
The charging station is energized.
The charging station is energized. The total load exceeds 80%. If the loads
exceed 80% for a predetermined period, the charging station will be de-
energized.
The charging station is not energized. The total loads exceed 80%. The
resumption time will start when the total load is lower than 80%.
The charging station is not energized. The total load is lower than 80% and
the recovery time is in progress. Each flash mean two (2) minutes before the
resumption of power to the charging station. (ex: 3 flashes = 6 minutes before
power
to the charging station). During that period, if the total load exceeds 80%,
the recovery time will restart from the beginning.
Malfunction:
- Check all connections and voltage.
- Check the DIP switch configuration settings.
- Check if the current transformers (CT) are properly connected and interlocked.
- Check if the connection for the current transformers are properly connected to the PCB electronics.
- If the problem persists, send pictures of the installation at support@dccelectric.com and then call 1 833-717-1355.