PHILIPS LEDtube EM-Mains T8 Tubular LED Lamp Installation Guide

June 1, 2024
Philips

PHILIPS LEDtube EM-Mains T8 Tubular LED Lamp

Specifications:

  • Product Name: Philips LEDtube EM/Mains T8
  • Number of LEDtubes in Packing List: 10 pcs
  • Compatibility: Electro-magnetic ballast and direct mains
  • Dimmable: No

Product Usage Instructions

Installation Guide

To install the Philips LEDtube EM/Mains T8, follow the steps below:

Installation on Electro-magnetic Ballast:

  1. Turn off the power supply.
  2. Replace the starter with the provided EMP (Electronic Replacement Starter).
  3. Follow the wiring diagram provided in the installation guide to connect the LED tube to the ballast.
  4. Apply the warning sticker on the luminaire after installation.

Installation on Direct Mains:

  1. Turn off the power supply.
  2. Remove the ballast from the circuit (if present).
  3. Connect the LED tube directly to the mains following the wiring diagram in the installation guide.
  4. Apply the warning sticker on the luminaire after installation.

FAQ:

  • Q: Can I use the Philips LEDtube T8 on direct mains without removing the ballast?
    A: No, for direct mains installation, it is recommended to remove the ballast from the circuit to ensure proper functionality.

  • Q: Is the Philips LEDtube T8 dimmable?
    A: No, the LED tube is not dimmable and should not be used with dimming systems.

  • Q: What is the warranty period for the Philips LEDtube EM/Mains T8?
    A: The warranty period is typically mentioned in the product packaging or can be obtained from Philips customer support.

Packing list

  • Philips LEDtube: 10 pcs
  • EMP (to replace starter): available as an accessory
  • Installation Guide
  • Warning Sticker

SYMBOLS

PHILIPS-LEDtube-EM-Mains-T8-Tubular-LED-Lamp-FIG-
\(1\)

INSTRUCTION

  • This lamp is not suitable to be used in emergency luminaires designed for double-capped fluorescent lamp(s).
  • Operating ambient temperature -20℃ to +45℃
  • This lamp may not be suitable for use in all applications where a traditional fluorescent lamp has been used. The temperature range of this lamp is more restricted. In cases of doubt regarding the suitability of the application, the manufacturer of this lamp should be consulted.
  • This lamp is designed for general lighting service (excluding e.g. explosive atmospheres).
  • Always switch off the power supply before commencing work!

Installation of Electro-magnetic ballast

PHILIPS-LEDtube-EM-Mains-T8-Tubular-LED-Lamp-FIG-
\(2\)

  • No modifications of the luminaire are to be made in this application.
  • It is recommended to remove the compensation capacitor to improve the power factor.
  • LEDtube 600mm is not suitable for series operation

Installation on direct mains

PHILIPS-LEDtube-EM-Mains-T8-Tubular-LED-
Lamp-FIG- \(3\)

  • This application shall be used in case there is a series compensation capacitor installed.
  • The fluorescent starter, if installed in the luminaire, shall be removed or bypassed (an LED replacement starter can be used for this purpose).
  • The installation shall be performed by qualified professionals by the relevant local code.
  • The fixture has been modified and can no longer operate the originally specified fluorescent lamp. Stick the Warning Sticker on the luminaire after the modification has been made.

Please inform yourself about the local waste disposal, separation and collection system for electrical and electronic products and packaging. Please act according to your local rules and do not dispose of your old product and packaging with your normal household waste. The correct disposal of the packaging, your product and/or batteries will help prevent potential negative consequences for the environment and human health. Batteries should be disposed of separately from the municipal waste stream via designated collection facilities. When disposing of a product that contains non-user- replaceable batteries, the non-user-replaceable batteries shall be removed by a professional.

© 2024 Signify Holding Signify
All rights reserved. Reproduction in whole or in part is prohibited without the prior written consent of the copyright owner.
The information presented in this document does not form part of any quotation or contract, is believed to be accurate and reliable and may be changed without notice. No liability will be accepted by the publisher for any consequence of its use.
Publication thereof does not convey nor imply any license under patent or other industrial or intellectual property rights.
Philips and the Philips Shield Emblem are registered trademarks of Koninklike Philips N.V. and are used under license 02/2024
www.philips.com/lightingPHILIPS-LEDtube-
EM-Mains-T8-Tubular-LED-Lamp-FIG- \(4\)
3241 661 744|1

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals