nVent HF Side Mount Filter Fans Instruction Manual
- June 1, 2024
- nVent
Table of Contents
nVent HF Side Mount Filter Fans
PARTS
CAUTION
Before cutting holes in the sides of the enclosure, verify all internal components are clear of the cutting tool to avoid damaging installed components.
INSTALLATION INSTRUCTIONS
-
Apply cutout template to the side of the enclosure located as desired. See Figure 1
-
Cutout hole in enclosure using the appropriate cutout size for the model you purchased.
-
Deburr the cutting edge.
-
Insert fan or grille and push into opening until all four corners are snapped and locked. See Figure 2.
-
Mounting fasteners are not required for panel or enclosure material thickness less than .10 (2.5 mm). For panel or enclosure material thickness between .10 (2.5 mm) and .14 (3.5 mm), mounting fasteners are recommended. For panel or enclosure material thickness greater than .14 (3.5 mm), mounting fasteners are required in order to maintain the IP / Type 12 rating.
-
In order to install the mounting fasteners, removal of the grille is required.
Remove the grille by pulling from the top of the grille to 45° maximum as shown in Figure 3 on page 4.
Then pull from the bottom as shown in Figure 4 on page 4.
NOTE: The orientation “Top” directs the louvers downward. This is for reference only; the assembly can be installed to orient louvers in any direction. -
It may be necessary to drill out the mounting holes in the filter housing. For model HF04, use a 1/8 (3 mm) drill bit. For models HF05, HF09, HF10 and HF13, use a 5/32 (4 mm) drill bit.
-
Torque fasteners to 20-25 in-lbs (2.3-2.8 Nm). See Figure 5 on page 4.
-
Install the grille as shown in Figure 2
-
Verify the location of the enclosure with installed filter fan has a minimum clearance of 7.00 (178 mm). See Figure 7 on page 4
-
Wire the filter fan following the Wire Diagrams on page 5 for the appropriate model being installed.
WIRE DIAGRAMS
-
WIRING DIRAMGRAM HF05, HF10 AC POWERED
-
WIRING DIAGRAM HF13 AC POWERED
-
WIRING DIRAGRAM HF04, HF05, HF09, HF10 DC POWERED
-
WIRING DIAGRAM HF13 – FULL SPEED DC POWERED
-
WIRING DIAGRAM HF 13 – VARIBLE SPEED DC POWERD
HOW TO READ MODEL NUMBERS
HF | 04 | 16 | 4 | 0 | 4 |
---|---|---|---|---|---|
1 | 2 | 3 | 4 | 5 | 6 |
-
Filter fan / Grille
-
Size
-
Voltage: 16 = AC 115/50/60/1
26= AC 230/50/60/1
24= DC 24V
48= DC 48V -
IP Rating: 4 = IP54
5 = IP55 -
Version
-
Color: 3 = RAL9011 Black
4 = RAL = RAL7035 Light Gray
FILTER CLEANING / REPLACEMENT
Replacement Filter Part Numbers
Replacement Filter Part Numbers
Fan/Grille Models| IP54 / Type 12 (≈ .50 [14 mm] thick)| IP55 / Type 12 (≈ .75
[20 mm] thick)
HF/HG04| 89134423R| —
HF/HG05| 89134424R| 89136408R
HF/HG09| 89134425R| 89136409R
HF/HG10| 89134426R| 89136410R
HF/HG13| 89134427R*| 89136411R
*Note: HF/HG13 replacement filters are not approved for IP54; only Type 12.
- Open louvered grille.
- Wash filter in warm water. Use mild detergent if necessary.
- For greasy matter, wash in warm water containing a grease solvent.
- Do not wring the filter.
REPLACEMENT PARTS
Model | RAL7035 Light Gray | RAL9011 Black |
---|---|---|
Grille | Housing | Grille |
HF04 | 89123894SP | 89133137SP |
HF05 | 89122973SP | 89133138SP |
HF09 | 89122907SP | 89133139SP |
HF10 | 89123456SP | 89133140SP |
HF13 | 89124454SP | HG1300404 |
HG04 | 89123894SP | HG0400404 |
HG05 | 89122973SP | HG0500404 |
HG09 | 89122907SP | HG0900404 |
HG10 | 89123456SP | HG1000404 |
HG13 | 89124454SP | HG1300404 |
WARRANTY
Please register your product and reference the Hoffman Cooling Product Warranty located here: https://hoffman.nvent.com/en/hoffman/warranty- information.
CUSTOMER SUPPORT
nVent 2100 Hoffman Way Anoka, MN 55303 USA
+1.763.422.2211
+1.763.576.3200
nVent.com
Read User Manual Online (PDF format)