DELTA-THERM BTR Series Floor Heating Cable Instruction Manual
- June 1, 2024
- DELTA-THERM
Table of Contents
- DELTA-THERM BTR Series Floor Heating Cable
- Product Information
- Product Usage Instructions
- Warranty
- Warnings and cautions
- Product specifications and details
- Critical information
- Selection of floor covering material
- Thermal insulation
- Installation instructions
- Electrical connection
- Operation of the floor heating system
- Control device
- Locating fault
- Control card
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DELTA-THERM BTR Series Floor Heating Cable
Product Information
Specifications
- Product Name: Floor Heating Cable
- Model: CBL and MCBL Series
- Compatible Series: BTR, BWF-R, CAG, CAR, CAR-P, DTR, DWF-R, OTR, OWF-R, DTM, FHM, MAG, MAT, OTM
- Warranty: 25 years from the date of purchase against manufacturing defects or malfunctions
Product Usage Instructions
-
Warnings and Cautions
Follow all safety precautions mentioned in the user manual. Ensure the power is switched off before installation. -
Product Specifications and Details
Refer to the specifications provided in the manual for detailed information on the product features and compatibility. -
Selection of Floor Heating System
Choose the appropriate heating cable series based on your requirements and floor type. Refer to the product specifications for guidance. -
Critical Information
Understand the warranty terms and conditions provided by the manufacturer. Keep the original purchase invoice for warranty claims. -
Selection of Floor Covering Material
Select suitable floor covering materials that are compatible with the floor heating system to ensure optimal performance. -
Thermal Insulation
Ensure proper thermal insulation to enhance the efficiency of the floor heating system. Follow recommended guidelines for insulation materials. -
Installation Instructions
Follow the step-by-step installation guide provided in the manual for installing the floor heating cable correctly. -
Installation Instruction for Floor Heating Cable with Strapping
Refer to section 8 of the manual for detailed instructions on installing the floor heating cable with strapping. -
Installation Instructions for Floor Heating Cable on Mat
Follow the instructions outlined in section 10 of the manual for installing the floor heating cable on a mat. -
Identification of Components
Identify all components provided with the floor heating cable mat system before installation. -
Floor Marking
Mark the floor area accurately where the floor heating cable mat will be placed for efficient heating distribution. -
Installation of the Floor Heating System
Proceed with the installation process as per the detailed instructions provided in section 10 of the manual.
FAQ (Frequently Asked Questions)
-
Q: How long is the warranty period for the CBL and MCBL series heating cables?
A: The warranty period is 25 years from the date of purchase against any manufacturing defect or malfunction. -
Q: What should I do in case of a malfunction covered by the warranty?
A: Report promptly in writing to the manufacturer and provide the original purchase invoice for warranty claim processing.
Floor heating cable for membrane and strapping
- BTR Series CBL Series
- BWF-R Series DTR Series
- CAG Series DWF-R Series
- CAR Series OTR Series
- CAR-P Series OWF-R Series
The floor heating cable on the mat
- DTM Series MAT Series
- FHM Series MCBL Series
- MAG Series OTM Series
Warranty
Subject to provisions stipulated in the Consumer Protection Act’s legal requirements respecting the quality and durability of goods: the manufacturer guarantees its CBL and MCBL series heating cables for 25 years from the date of purchase against any manufacturing defect or malfunction.
Limitations and exclusions
The above-mentioned guarantees are limited to the reimbursement of the
original purchase cost or replacement of the heating cables (hereinafter
called “equipment”) excluding any other part and also excluding any cost or
any expense relating to connection, removal or installation of aforesaid
equipment, including all workmanship costs. The buyer may choose between the
reimbursement of the original purchase cost and the replacement of defec-tive
equipment, subject to the aforementioned restrictions. This warranty is
provided to the original buyer
of the equipment as well as subsequent owners of the building where the
equipment was installed.
Warranty terms
The above-mentioned warranties are subject to the following conditions:
- The buyer must provide the original purchase invoice for the defective equipment, to the manufacturer or one of their authorized dealer.
- The buyer must report promptly in writing to the manufacturer any malfunction of equipment covered by the present warranties, in a reasonable time frame, from the time the malfunction occurred or the malfunction was brought to their knowledge thereby enabling the manufacturer representatives enough time to verify the defective equipment, if need be.
- Equipment covered under the present warranties must be installed in compliance with the manufacturer’s instructions.
- Equipment covered under the present warranties must be used under normal conditions of use and be maintained regularly on the date of purchase.
Address of the person providing the present warranties:
- 180, 3e Avenue, L’Islet (Québec) G0R 2C0 CANADA
- Telephone: 1 800 463-7043 or 418 247-3947
CAUTION!
Please read through these instructions carefully before you begin installing &
check that you are aware of all the components required.
Warnings and cautions
Risks of electrical shocks and fire
For safe installation and efficient performance of this system, read the
instruction manual thoroughly and keep it handy.
- Where applicable, installation must meet the requirements of the following codes:
- Canadian Electrical Code (CSA C22.1 Part 1);
- National Electrical Code (NFPA 70);
- Any other applicable local and/or national code.
- Where required by law, this product must be installed by a qualified person.
- To prevent any possibility of electrical shocks, the power supply must be turned off before handling the heating cables.
- A GROUND FAULT PROTECTION DEVICE MUST BE USED WITH THIS PRODUCT UNLESS EXEMPTEDTHE BY THE ELECTRICAL CODE IN FORCE.
- These heating cables must be used for indoor applications only.
- The heating cable and the mechanical joint (junction) must be installed and fully embedded in cement or an equivalent binder (cement glue, ceramic glue or self-levelling cement).
Product specifications and details
The floor heating system is designed exclusively for interior floor heating. The system is not designed for snow melting or any other outdoor uses; it is mainly designed to complement a building’s primary heating source by serving as a secondary (floor warming) or primary room heat source (radiant floor heating).
Mat floor heating cable
The floor heating system on the mat is the assembly of a twin conductor
heating cable attached to an adhesive fibreglass mat with 3″ (7.6 cm) spacing
between the cables. It is combined with a 10′ (3 m) cold lead.
Floor heating cable for membrane and strapping
- The floor heating system for the membrane is made of a twin conductor with a 10′ (3 m) cold lead.
- The heating cable consists of a resistance-heating element insulated with Fluoropolymer having high dielectric strength and high temperature withstand ability, which makes the heating cable safe. A metallic sheath provides additional mechanical strength and a ground path. A final PVC outer jacket makes it sturdier and provides corrosion protection. The hot and cold lead junction is uniquely designed to make it foolproof.
- The heating cables are available in a wide range of capacities and lengths to suit your requirements.
Selection of floor heating system
- The selection of a floor heating system will depend on the application.
- The maximum allowed power for installation is limited by the cable spacing. The minimum distance between the cables is 3 inches no matter the installation system. The 3 inches spacing gives a power density of 12 W/ft² (130 W/m²).
- Depending on the claimed result, the cable system can also be used in lower-density applications. To ensure optimal heating results, please contact a qualified person.
- Wet areas (in locations subject to saturation with water) like showers, saunas steam rooms, bathrooms, etc: 12 W/ft2 (130 W/m2).
- Note: The floor heating system can be installed under a shower floor only if the floor is ceramic or natural stone.
- A waterproof membrane must be used to maintain the heating cables in a dry environment. The manufacturer recommends using a separate cable for the shower area. The UL listing for this product covers use in wet locations for
- CANADA only. Wet location installation in the United States shall be by the National Electric Code, (NFPA 70) and any other applicable jurisdictional code and final acceptance is to be made by the Authority Having Jurisdiction (AHJ).
- Please note the above-indicated values are meant as a general guide, actual requirements will depend on insulation levels, floor construction, type of floor coverings, ambient temperature, movement of the people etc.
Critical information
-
The heating cable must not touch, crossover or overlap itself at any point. This could cause the cable to overheat.
-
The heating cable cannot be cut or shortened.
-
The heating cable length cannot be altered in any circumstances. This may cause overheating resulting in damage to the cable.
-
Take precautions to avoid damage to the heating cable during installation, due to dropping sharp objects or stepping or careless pouring of concrete or banging the trowel on the heating cable while applying cement mortar for tiling/flooring. In the case of remodelling floors, make sure that old mats/cables are removed before you lay new heating cables.
-
Heating cables should be separated from other heat sources such as floor luminaries and chimneys.
-
Do not install the heating cable below 5 °C (40 °F) ambient temperature.
-
MiThe minimum radius of the heating cable while laying shall not be less than 1″ (2.54 mm). The mechanical joint between the cold lead and the heating part of the cable must not be bent. 8 Floor thermostat sensor location shall be centred between two adjacent runs of heating cable. Do not locate the floor thermostat sensor closer than 1″ (2.54 cm) to the heating cable or allow it to overlap any other cable.
-
The maximum limit of the temperature setting on the thermostat should not exceed 30 °C (86 °F).
-
Check the main voltage and wattage of the heating cable as per the selection made. These are indicated on the product nameplate.
-
Keep the power leads conduit separated from the floor temperature sensor cable conduit.
-
It is highly recommended to connect the cable check electrical fault indicator at the free end of the cold lead during the installation to warn about accidental damage to the heating cable or lead wires.
-
In case GFCI trips during normal operation, and cannot be reset, there is likely a fault in the cable. No attempt should be made to re-energize the heating cable. GFCI must not be bypassed in any circumstances. Consult a qualified person.
-
Do not install the heating cable under permanent fixtures.
-
Allow sufficient drying or curing period of the subfloor and finished floor before and after installing the heating cable.
-
Indicate which branch circuits supply the power to the heating cable and retain the UL label for each heating cable in a convenient location, i.e. taped to the circuit breaker box, for reference by the electrical inspector or homeowner. Leave one UL label attached to the heating cable. Attach a warning label in a convenient location to show the room location where the heating cable is installed.
-
Use only listed conduits, fittings, and or other components.
-
Heating cables shall not extend beyond the room or area in which they originate.
-
The heating cable shall not be installed in closets, over walls or partitions that extend to the ceiling or over cabinets.
-
This heating cable shall be installed only by qualified people who are familiar with the construction and operation of the heating cable and the risks involved.
-
The installation of the heating cable shall according to the manufacturer’s instructions and local cal national codes.
-
The manufacturer recommends using a separate cable for the shower area. It can be installed under a shower floor only if the floor is ceramic or natural stone. A waterproofing membrane must be used to maintain the heating cable in a dry environment. The UL listing for this product does not cover use in wet locations in the United States.
-
Use copper wires only.
-
The heating cable (including the mechanical joint) must not be installed in walls.
-
Install the thermostat where it is not accessible from the shower or bath (install at least 3′ 4″ (1 m) away). 26 Avoid walking on the cable. Wear soft rubber-soled shoes.
-
Required distances and clearances
CAUTION!
NEVER install a heating cable under an interior wall or any fixed unit, a closet or in any other location where air cannot circulate freely over the floor surface. Always maintain the following minimum clearance:- 3″ (7.6 cm) between heating cables;
- 3″ (7.6 cm) from any exterior wall, interior wall, drain, or any fixed obstacle you need to go around; Note: 10″ (25.4 cm) from a toilet drain with a wax ring seal.
- 3″ (7.6 cm) from any fixed unit (e.g., vanity sink, shower, refrigerator, etc.);
- 8″ (20 cm) from any heating appliance affixed to or in contact with the floor;
- 2″ (5 cm) between the floor surface and the furniture to allow air to circulate freely;
- 0.5″ (1.3 cm) between the heating cable and any exposed combustible surface;
- If the cable must cover a distance greater than 10 ft. (3 m), a U-shaped loop must be used to minimize conductor thermal expansion and prevent it from breaking while respecting the minimum bending radius of the cable.
-
The system is only one step in the floor construction process. Each trade is responsible for the quality of its work and must ensure that the work performed by the previous tradesman has been duly completed according to code. All tradesmen are engaged in the installation process and share joint responsibility for it.
-
Perform all six (6) insulation and resistance test steps required during installation:
-
Before breaking the security seal and opening the product.
Note: Once the seal is broken, you are then in charge of the cable integrity throughout the entire installation process. Be sure to follow instructions and observe all precautionary measures. -
After the installation of the heating cable.
-
Before embedding the heating cable.
-
After embedding the heating cable.
-
After the final installation of flooring.
-
Before connecting the heating cable system.
* Enter the results in the measurement table found in the envelope. All 6 measurements must be correctly recorded for the warranty to be applicable.
* Once completed, affix the measurement table to the electrical panel and mark the specific circuit breaker that powers the heating cable circuit.
A qualified electrician must measure the system’s insulation resistance as
follows:
Megohmmeter
- Use a calibrated megohmmeter only;
- Measure insulation resistance at the free end of the cold lead, between the phase conductors and ground;
- Write the reading in the measurement table;
- This reading must be over 1 000 000 ohms;
- If the reading is under 1 1,000,000hms, stop work and contact the manufacturer’s technical support.
Multimeter
- Use a calibrated multimeter only;
- Measure resistance at the free end of the cold lead, between the two phase conductors;
- Write the reading in the measurement table;
- Verify the heating cable integrity by comparing your reading to the value on the cold lead label;
- If your reading is very different from the nominal resistance at any step, stop work and contact the manufacturer’s technical support.
WARNING!
- “Risk of electric shock and fire”.
- “Damage to supply conductor insulation may occur if conductors are routed less than 3″ (7.6 cm) from this heating product. Refer to installation instructions for recommended means of routing supply conductors”.
Selection of floor covering material
Caution:
- Check with the manufacturer to make sure your floor covering is compatible with the heating cable system.
- The type and thickness of floor covering materials used with this product must not exceed a thermal insulation “R” value of 1 (RSI = 0.176).
- There is no thermal insulation limit under the floor.
Typical floor covering | Thermal resistance |
---|---|
R | RSI |
Ceramic | 0.25 |
Floating floor 3/8” to 5/8” (10 mm to 16 mm) (Laminate) | 0.70 |
Linoleum | 0.40 |
Low-pile carpet | 1.00 |
Natural stone (Granite, limestone, marble, sandstone) 1” | 0.10 – 0.40 |
0.07
Parquet flooring| 0.70| 0.12
Plywood 1/2”| 0.55| 0.10
Vinyl tiles| 0.20| 0.04
Engineering floor| 1.60| 0.28
Wood on lathe (strapping)| 2.10| 0.37
The floor covering highlighted in grey is prohibited.
IMPORTANT!
For engineered wood floorings, laminated hardwood flooring, vinyl coverings,
and linoleum glued to a concrete surface, consult your floor covering
manufacturer to ensure they are compatible with floor heating systems.
Thermal insulation
- The insulation levels of a floor will affect both the performance & running costs of the floor heating system.
- The thermal insulation reflects the heat upwards into the floor instead of allowing heat to penetrate the sub-floor and keeps the floor warmer for a longer period. While installing the floor heating system, the user should install adequate thermal insulation below it. In cases where the floor heating system is being installed over large areas, insulation boards will greatly reduce warm-up times & running costs.
- When floor heating systems are installed on a concrete slab, we strongly recommend adding a layer of insulation to the slab before installing the heating cables. Adding insulation on top of the concrete slab or board, and beneath any floor heating system will allow a greater percentage of heat generated to transfer to the flooring surface.
- The heating cable system is approved for the following type of installation:
- On a subfloor
CAUTION!
The subfloor material in contact with the heating cable must be able to
withstand a temperature of at least 90 °C (194 °F).
IMPORTANT!
The efficiency will depend on factors such as the available surface of the
room to be covered with a heating cable (or a sufficient percentage of the
surface to be heated), the heat conductivity of the floor covering, insulation
on outside walls, etc. We recommend that you verify these points and seek
professional advice before investing time and money.
Installation instructions
Room layout and corresponding floor heating system product
Plan the installation taking into account the guidelines below.
- Create a room layout plan to scale (for maximum accuracy, use the manufacturer form designed for this purpose);
- Identify all stationary elements (toilet, bath, shower, counters, dressers, and permanent furnishings) and never install the heating cable under these stationary elements (Figure 1);
- Determine thermostat or temperature control location;
- Indicate all the dimensions of the space that requires heating;
- Determine the electric cable (cold lead) location that will be connected to the heating control;
- When calculating the area to be covered by the heating cable, remember that the cable must be installed 3″ (7.6 cm) from any exterior wall, interior wall, drain, or any fixed obstacle you need to go around.
- Once you have determined the area to be heated, calculate the total required output by multiplying the aby rea the watt density required for the room. Choose the nearest suitable wattage cable from the available range. When cacalculatedize required is between two sizes of offered cables, select the smallest of the two.
Cable rating| Density and distance between
cables
---|---
Strapping| Membrane| Mat
3 W/sq.ft
(9.84 W/m)
| 3 inches| 4 inches| 5 inches| Every 3 sockets| Every 4 sockets| 3 inches
12 W/sq.ft.| 9 W/sq.ft.| 7.5 W/sq.ft.| 10 W/sq.ft.| 7.5 W/sq.ft.| 12 W/sq.ft.
- Each cable’s length is listed in the product sheet; combine cables if more than one is being used.
- We recommend the installation of the cable at a spacing of 3 or 4 inches for a uniform floor temperature.
Room layout example
Need help to optimize your work plan? Contact our technical support. Indicate all dimensions. A minimum of one horizontal and one vertical dimension are necessary to validate the scale.
Work planning
Materials provided by the manufacturer
- Heating cable
- Installation instructions
- Measurement table label
- Floor temperature sensor
Note:
Always use the temperature sensor supplied with the thermostat. The
temperature sensor supplied with the heating cable is installed in case of
failure of the thermostat sensor.
Material required
- Temperature control with GFCI (available at the manufacturer)
- Electrical fault indicator (available at the manufacturer)
- Stapler
- Safety glasses
- Measuring tape
- Broom
- Felt marker
- Tape
- Hot glue gun
- Wood chisel
- Hammer
- Multimeter and megohmeter
- Electrician tools
- Electrical tape
For installation over a concrete slab, add the following:
- Concrete chisel
- Drilling machine
- Percussion drill for concrete
General recommendation and subfloor preparation
- Clean and remove any debris, dust or protruding objects that could damage the heating cable. The surface must be clean and dry for the adhesive mat to adhere perfectly to the surface.
- Subfloor cracks must be filled with polyester wood filler.
- The subfloor must be solidly fastened in place to prevent movement.
- For floor heating cable for the membrane, it is important to refer to the uncoupling membrane manufacturer’s instructions to ensure that it is compatible with the heating cable.
- Always ensure that the uncoupling membrane is installed properly according to the manufacturer’s- recommendations.
- Vacuum and clean any mortar residue that could damage or prevent the proper installation of the cable between the membrane studs.
- For concrete subfloors, apply a surface sealer that is compatible with electrical heating systems in the cement glue manufacturer’s instructions. Completely coat the surface.
- Always let the sealer dry before installing the floor heating system (refer to the manufacturer’s instructions for drying time).
Floor marking
On the floor of an empty room (under construction or major renovations), draw
the location of stationary elements (toilet, bath, shower, counters, dressers,
permanent furnishings) that will be installed later. These marks will outline
the heating area to ensure the heating cable is not placed under these
stationary elements.
- If an uncoupling membrane is used, install it before marking the floor (see section 8.1 for installation of the membrane).
Installation instruction for floor heating cable with strapping
Identification of components
Floor marking
- On the floor of an empty room (under construction or major renovations), draw the location of stationary elements (toilet, bath, shower, counters, dressers, permanent furnishings) that will be installed later. These marks will outline the heating area to ensure the heating cable system is not placed under these stationary elements.
- The floor temperature sensor must be centred between two parallel heating cables. The ideal location is one where it is likely to be away from stationary objects and sheltered from outside influences (sunlight) that could skew floor temperature readings. For maximum comfort, the area above the sensor must be free of obstruction.
Installation of the floor heating system
- 1) First insulation and resistance test.
Before breaking the security seal and opening the product, measure the cable’s electrical and insulation resistance and record the readings on line 1) Before breaking the seal.
Installation of the plastic strapping
- The strappings are fixed on the floor with staples or screws (when the floor is made of plywood or wood) or with a hot glue gun.
- The strappings must follow the outline drawn on the room layout (section 7.1).
- If the lacing distance between two strappings is over 2′ (0.625 m), it is necessary to place an intermediate strapping to maintain the cable in position during the pouring of the self-leveller. This strapping is installed at theend, after the lacing of the cable to have a good finish and a regular laying.
- The cable can be installed under the ceramic tile of a shower or other wet surfaces, the strappings and the heating cable must be glued under the waterproofing membrane and not stapled, staples could damage the waterproofing membrane. The UL listing for this product does not cover use in wet locations in the United States.
Installation of the heating cable
- Set the cable near the connection box. Ensure that the cold lead is long enough to be connected to the thermostat or junction box.
- To minimize floor height, chisel a 3/8” x 3/8” x 10” (10 mm x 10 mm x 250 mm) channel in the subfloor to receive the cold lead/heating cable junction. The junction has an extra insulation sheath and a slightly larger diameter than the heating cable. Attention: The mechanical joint (junction) must not be bent.
- Regularly lace the heating cable respecting the distance between the sections; 3” (7.6 cm) minimum.
- Do not bend the cable at 90° when setting it in the strapping hooks; leave a 1“ (2.5 cm) radius. This radius comes naturally; the cable must not be forced to have a tight bend.
- A tag is located at 50% of the cable length. During installation of the product, verify the cable half tag to compare with your cable layout planification. Adjust the pattern with the result to cover the surface. Never shorten the heating cable. The heating cable must not be shortened, or cut.
- Always start the cable at least 3” (7.6 cm) from the walls.
- It is important not to subject the heating cable to any mechanical strain (stretching, bending radius under 1“ [2.5 cm], scoring). Attention: The mechanical joint (junction) must not be bent.
- Avoid walking on the cable.
ATTENTION!
Never exceed the 10′ (3 m) maximum allowed length of a free cable in a
straight line.
IMPORTANT!
- 2) Second insulation and resistance test.
After the installation of the heating cable, measure the cable’s electrical and insulation resistance and record the readings on line 2) After cable installation.
Installation of the temperature sensor
IMPORTANT!
The sensor must be embedded in cement or an equivalent binder (cement glue,
ceramic glue, self-levelling cement).
- The floor temperature sensor must be centred between two parallel heating cables. The ideal location is one where it is likely to be away from stationary objects and sheltered from outside influences (sunlight) that could skew floor temperature readings. For maximum comfort, the area above the sensor must be free of obstruction.
- To minimize floor height, chisel a 3/8” x 3/8” x 10” (10 mm x 10 mm x 250 mm) channel in the subfloor to receive the floor temperature sensor.
- Glue the sensor to the subfloor (figure 15). The sensor must be solidly fastened to the subfloor to ensure it stays in place when the cement or an equivalent binder (cement glue, ceramic glue, self-levelling cement) is applied.
Note:
- It is recommended to install two (2) temperature sensors; in case of malfunction of the first one, the second sensor is already encased and ready for connection.
- Always use the temperature sensor supplied with the temperature control as your primary sensor. The one supplied with the heating cable should be used as backup.
Application of the self-levelling cement
- 3) Third insulation and resistance test
Before embedding the heating cable in self-levelling, measure the cable’s electrical and insulation resistance and record the readings on line 3) Before embedding the cable.
IMPORTANT!
All the heating portion of the cable (including the mechanical joint) must be
completly embedded in mortar. The floor covering must be in direct contact
with the mortar the cable is in.
- Applying a minimum 1/4″ (6.4 mm) layer of self-levelling cement on the heating cable is recommended. To completely embed the cable in the cement or cement glue.
- Only use cement or an equivalent binder compatible with floor heating systems (cement glue, ceramic glue, self-levelling cement).
- Consult the manufacturer’s instructions for the type of floor covering (ceramic, linoleum, or other) (see section 5).
IMPORTANT!
Do not turn on the floor heating system before the cement has completely
dried. Follow the manufacturer’s recommendations (may take up to 30-40 days,
depending on the product).
- 4) Fourth insulation and resistance test.
Once the cement or binder has been applied, measure the cable’s electrical resistance and record the readings on line 4) After embedding the cable.
Final view (exploded view of the installation)
- 5) Fifth insulation and resistance test.
After final surfacing. Once the cement or binder has been applied and completely dried, measure the cable’s electrical resistance and record the readings on line 5) After final surfacing.
Installation instructions for floor heating cable on uncoupling membrane
IMPORTANT!
This product was designed for installation in an uncoupling membrane with a
minimum regular spacing of 3″ (7.6 cm).
Uncoupling membrane installation
Refer to membrane manufacturer installation instructions and follow the
recommendations. The uncoupling membrane must be specifically designed for
heating cable and installed before the cable is inserted.
Cable installation on the uncoupling membrane
- 1) First insulation and resistance test.
Before breaking the security seal and opening the product, measure the cable’s electrical and insulation resistance and record the readings on line 1) Before breaking the seal.
Begin installation of the cable near where the thermostat will be located. The mechanical joint between the cold lead and the heating part of the cable must be inserted in the membrane and embedded in a thin-set mortar or adhesive.
Attention:
The mechanical joint (junction) must not be bent.
Make an incision in the membrane and the floor to insert the spliced section of the cable. For the types of thin-set mortar that can be used, refer to the membrane manufacturer’s installation instructions.
- Install the heating cable in the membrane’s castellations by applying light pressure on the cable
- Install the heating cable in the membrane while respecting all the required distances and clearances at a minimum spacing of 3’’ (7.6 cm) between the heating cables.
- Be careful not to damage the cable while inserting it into the membrane and avoid walking on the cable.
ATTENTION!
Never exceed the 10′ (3 m) maximum allowed length of a free cable in a
straight line.
-
- Second insulation and resistance test.
After the installation of the heating cable, measure the cable’s electrical and insulation resistance and record the readings online
-
- After cable installation.
- Second insulation and resistance test.
Installation of temperature sensor
IMPORTANT!
The sensor must be embedded in cement or an equivalent binder (cement glue,
ceramic glue, self-levelling cement).
- The floor temperature sensor must be centred between two parallel heating cables. The ideal location is one where it is likely to be away from stationary objects and sheltered from outside influences (sunlight) that could skew floor temperature readings. For maximum comfort, the area above the sensor must be free of obstruction.
- Make an incision in the membrane and the floor to insert the floor sensor. The floor sensor mustn’t extend the height of the membrane.
- Install the floor temperature sensor in the membrane’s castellations. It should be centred between two heating cables. Hot glue can be used to fix the sensor cable to the surface.
Note:
- It is recommended to install two (2) temperature sensors; in case of malfunction of the first one, the second sensor is already encased and ready for connection.
- Always use the temperature sensor supplied with the temperature control as your primary sensor. The one supplied with the heating cable should be used as a backup.
Installation of the floor covering
Please refer to the membrane manufacturer installation guide for
recommendations on the types of mortar compatible with the uncoupling membrane
and the installation of the floor covering.
- 3) Third insulation and resistance test
Before embedding the heating cable in self-levelling, measure the cable’s electrical and insulation resistance and record the readings on line 3) Before embedding the cable.
IMPORTANT!
All the heating portion of the cable (including the mechanical joint) must
be completly embedded in mortar. The floor covering must be in direct contact
with the mortar the cable is in. Do not turn on the floor heating system
before the cement has completely dried. Follow manufacturer recommendations
(may take up to 30 to 40 days, depending on the product).
- 4) Fourth insulation and resistance test.
Once the cement or binder has been applied, measure the cable’s electrical resistance and record the readings on line 4) After embedding the cable.
Final view (exploded view of the installation)
- 5) Fifth insulation and resistance test.
After final surfacing. Once the cement or binder has been applied, measure the cable’s electrical resistance and record the readings on line 5) After final surfacing.
Installation instructions for floor heating cable on the mat
Identification of components
Floor marking
- Draw lines on the floor the width of the mat.
- Indicate in which direction the mat will be unrolled.
- The floor temperature sensor must be centred between two parallel heating cables under the mat (figure 9). The ideal location is one where it is likely to be away from stationary objects and sheltered from outside influences (sunlight) that could skew floor temperature readings. For maximum comfort, the area above the sensor must be free of obstruction.
Installation of the floor heating system
1) First insulation and resistance test.
Before breaking the security seal and opening the product, measure the cable’s
electrical and insulation resistance and record the readings on line 1) Before
breaking the seal.
- Unroll the mat, adhesive side down (figure 10);
- Ensure that the cold lead is long enough to be connected to the thermostat or junction box;
- To minimize floor height, chisel a 3/8” x 3/8” x 10” (10 mm x 10 mm x 250 mm) channel in the subfloor to receive the cold lead/heating cable junction. The junction has an extra insulation sheath and a slightly larger diameter than the heating cable. Attention: The mechanical joint (junction) must not be bent;
- Continue to unroll the mat on the floor, working around the stationary elements marked out beforehand;
- As needed, reposition the mat: its adhesive allows it to be positioned more than once.
- You may use hot glue or tape to fasten the mat to the subfloor;
2) Second insulation and resistance test.
After the installation of the heating cable, measure the cable’s electrical
and insulation resistance and record the readings on line 2) After cable
installation.
- Staple the mat to the plywood subfloor to prevent the mat ends from curling (figure 11.1);
- Use adhesive spray to fasten the heating mat to a concrete subfloor (figure 11.2).
IMPORTANT!
Never staple the heating cable directly to the subfloor.
Working around walls and obstacles
When the heating mat roll meets a wall or obstacle, simply cut the mat and
pivot it in another direction (figure 12);
- When two adjacent rooms are heated by the heating cable, it is recommended to cover the traffic area between these rooms to avoid cold spots. To do so, simply cut the mesh and remove the cable from the mesh over a certain length to cover the traffic area (figure 13). Use scissors to cut the mat, being very careful not to damage the cable and use the floor fasteners or stapler to secure both extremities of the mat onto the subfloor.
IMPORTANT!
Never cut or try to shorten the heating cable.
- Ensure that the mat surface is flat against the subfloor;
- Always start unrolling the heating mat at least 3″ (7.6 cm) from the walls;
- To work around stationary elements, detach a section of heating cable from the mat and use it to cover a tight space or work around an object;
- It is important not to subject the heating cable to any mechanical strain (stretching, radius bending under 3/4” [19 mm], scoring).
Mat rippling
- Carefully flatten the mat against the subfloor to ensure it and the heating cable can be completely embedded in the cement or other binder to be applied in the next step;
- If the mat ripples, score the cecentref the rippled section and flatten the edges (figure 14).
ATTENTION!
Never cut or score the heating cable.
2) Second insulation and resistance test.
After the installation of the heating cable, measure the cable’s electrical
and insulation resistance and record the readings on line 2) After cable
installation.
Installation of the temperature sensor
IMPORTANT!
The sensor must be embedded in cement or an equivalent binder (cement glue,
ceramic glue, self-levelling cement).
- The floor temperature sensor must be centred between two parallel heating cables. The ideal location is one where it is likely to be away from stationary objects and sheltered from outside influences (sunlight) that could skew floor temperature readings. For maximum comfort, the area above the sensor must be free of obstruction.
- To minimize floor height, chisel a 3/8” x 3/8” x 10” (10 mm x 10 mm x 250 mm) channel in the subfloor to receive the floor temperature sensor.
- Glue the sensor to the subfloor (figure 15). The sensor must be solidly fastened to the subfloor to ensure it stays in place when the cement or an equivalent binder (cement glue, ceramic glue, self-levelling cement)
is applied.
Note:
- It is recommended to install two (2) temperature sensors; in case of malfunction of the first one, the second sensor is already encased and ready for connection.
- Always use the temperature sensor supplied with the temperature control as your primary sensor. The one supplied with the heating cable should be used as a backup.
Application of the self-levelling cement
3) Third insulation and resistance test
Before embedding the heating cable in self-levelling, measure the cable’s
electrical and insulation resistance and record the readings on line 3) Before
embedding the cable.
IMPORTANT!
All the heating portion of the cable (including the mechanical joint) must be
completly embedded in mortar. The floor covering must be in direct contact
with the mortar the cable is in.
- Applying a minimum 1/4″ (6.4 mm) layer of self-levelling cement on the heating cable is recommended. To completely embed the cable in the cement or cement glue;
- Only use cement or an equivalent binder compatible with floor heating systems (cement glue, ceramic glue, self-levelling cement).
- Consult the manufacturer’s instructions for the type of floor covering (ceramic, linoleum, or other) (see section 5).
IMPORTANT!
Do not turn on the floor heating system before the cement has completely
dried. Follow the manufacturer’s recommendations (from 30 to 40 days,
depending on the product).
4) Fourth insulation and resistance test.
Once the cement or binder has been applied, measure the cable’s electrical
resistance and record the readings on line 4) After embedding the cable.
Final view (exploded view of the installation)
5) Fifth insulation and resistance test.
After final surfacing. Once the cement or binder has been applied and
completely dried, measure the cable’s electrical resistance and record the
readings on line 5) After final surfacing.
Electrical connection
IMPORTANT!
Electrical connection must be performed by a master electrician, only after
the cable has been installed and encased in concrete and the curing of
concrete period is complete.
WARNING!
DANGER OF ELECTROCUTION: always make sure the power supply circuit is turned
off before proceeding with the electrical connection.
6) Sixth insulation and resistance test.
Before wiring the system, measure the cable’s electrical resistance and record
the readings on line 6) Before wiring the thermostat.
-
Perform the connection in compliance with instructions provided by the temperature controller and in compliance with local and national electrical specifications in effect.
Cold lead: -
240V/208V connection
* Line 1 – Black sheat
* Line 2 – Red sheat
* Ground – Yellow/green sheat
2. **120V connection:**
* Line – Black sheat
* Neutral – Yellow sheat
* Ground – Yellow/green sheet
IMPORTANT
* Check the product nameplate to make sure that the voltage supply is correct.
* Never connect a 208/240V product at 347V or vice versa.
- The master electrician who installed and connected the floor heating system must complete the measurement table (this label is available at the opening of the product) and give it to the customer. This label must be kept on the electrical panel.
CAUTION!
If the table is not duly completed, the warranty may be void. Warranty terms
are set on the back of the cover page.
Operation of the floor heating system
The floor heating system is now ready for use. However, before turning on the system, make sure the curing period specified by the concrete manufacturer has expired. Adjust the thermostat’s temperature based on your needs and desired comfort level.
Control device
Important
- The floor heating system must be controlled by a temperature control system.
- An electronic floor temperature control featuring a floor sensor is recommended to ensure heat levels never exceed the floor covering maximum temperature tolerance.
- The room temperature control and floor temperature sensor must never be installed where they will be exposed to sunlight or air drafts.
IMPORTANT!
Recommended temperature regulation devices:
- Thermostat with floor sensor and integrated GFCI (floor warming only).
- Electronic ambient thermostat with a GFCI (radiant room heating).
- For installations requiring more than one electrical circuit, get a set of adequate controls including a master thermostat and the required number of slave units, according to the total power of the system.
- We recommend using a thermostat with a floor sensor specially designed for the control of floor heating systems.
- The floor sensor comes with a lead wire/cable of 15’ (4.6 m) length.
- The floor sensor location shall be centred between two adjacent runs of heating cable.
- Sensor cable shall be routed to the thermostat located in the wall at a suitable operating height.
- Do not allow any other cable to overlap with the sensor cable.
- The details of thermostat installation will be available in the instruction manual provided with the thermostat. We strongly recommend using the cable manufacturer thermostat.
- If other thermostats/ controls are used, make sure they are double poles, i.e. they cut off both power lines to the cable(s).
Refer to instructions that came with your specific thermostat for electrical schematics
Operating tips
- When first energized, the heating cables may take some time to fully warm your floor.
- Energy consumption will vary depending on user preferences.
- Energy consumption can be minimized by turning the system OFF when floor heat is not required, but you will have to allow time for the floor to warm up once the system is turned ON again.
- Do not place thick mats/rugs/mattresses on your heated floor. These restrict the heat transfer and may result in the cable overheating.
- Avoid mats with rubber or vinyl-type backing, as these may decompose with heat and could stain flooring.
Locating fault
If the cable gets damaged during installation, the Cablecheck electrical fault indicator (sold separately) will warn you about the damage.
Electrical fault finding
Once the system has been turned off and made safe, have a qualified person:
- Ensure all wires have been connected as per the wiring diagrams;
- Make sure multiple rolls have been wired in parallel and not in series;
- Confirm that control devices are receiving the correct voltage.
- Using a well-calibrated multimeter with good batteries, or preferably, a digital multimeter, the ohm resistance level of each heating cable should be checked and the reading compared with the resistance that was recorded during installation and the nominal value indicated on the corresponding UL label.
- If your reading is not within the original reading range, the cable may have been damaged in some way.
- This indicates an open or short circuit beneath the finished flooring. The qualified individual must locate the point of break or short.
- At all times, turn off the power at the main panel and disconnect the heating cable from the thermostat to take readings.
Locating a break or a short
If your installation is complete, all wiring connections have been verified to
be correct, including grounding of the system, you have checked the sensor
wire for proper Ohms reading, and you suspect the system is still not working;
you need to determine if there is a break or a short under the floor.
WARNING!
Danger of electrocution.
- Always make sure the power supply circuit is turned off at the panel before proceeding with tests.
- Always disconnect the heating cable from the controller to take a resistance reading.
Checking for breaks
- The ohm resistance of each cable should be measured. Make sure the probes of the multimeter do not touch the ground wire of the power connector. Make sure you do not touch either of the probe ends, or the meter will be reading your internal body resistance.
- Make sure your multimeter is set on the proper scale (0 to 2000Ω for the heating cable, or 0 to 20,000Ω for the floor temperature sensor wire).
- Your ohm resistance readings should be within +10%/-5% of the nominal resistance indicated by the factory on the UL label.
- If your ohm reading is within +10% / -5% of what it should be, there is no break. However, you still need to check for an electrical short.
- If your ohm reading is lower (outside the range), but there is some continuity, check your multimeter and your batteries. If these are good, there is a possibility that you have several electrical shorts.
- If you have no reading (infinity on your meter), and you are sure you adjusted the setting of the multimeter to the correct reading range (0 to 2000Ω for the heating cable, or 0 to 20,000 Ω for the floor temperature sensor wire), then you have a break (total cut) in the conductor.
Checking for electrical short:
In some rare occasions, an installation may have suffered a high-pressure
point that broke the insulation between the core conductor and the metal
sheath. Such an opening in the insulation layer can create an electrical
short, even though the Ohm reading from the line conductor to the other line
conductor is normal and does not indicate any circuit break. In these rare
occasions, a continuity test will show continuity between the line conductor
and the ground wire, and/or between the other line core conductor and the
ground.
- There should be no continuity (“infinite” resistance reading, not zero) between the line conductor and the ground.
- There should be no continuity (“infinite” resistance reading, not zero) between the other line conductor and the ground.
- If your instrument reveals continuity between both the line conductors and the ground, there is a short in the circuit.
There are three ways to locate breaks or electrical shorts with underground fault detectors:
- A break can be found with a “thumper”, an impulse-generating device that generates a sound at the breakpoint. The thumper includes a stethoscope to locate the exact placement of the break under the floor.
- A short can be found with a “time domain reflectometer” tester, which will measure the distance of the wire between the tester and the short point.
- Breaks and shorts may generate some heat and they can also be found with infrared cameras scanned over the floor.
Control card
Perform all six (6) insulation and resistance test steps required during installation:
-
Before breaking the security seal and opening the product.
Note: Once the seal is broken, you are then in charge of the cable integrity throughout the entire installation process. Be sure to follow instructions and observe all precautionary measures. 2 After the installation of the heating cable. -
Before embedding the heating cable.
-
After embedding the heating cable.
-
After the final installation of floor covering.
-
Before connecting the heating cable system.
- Enter the results in the measurement table found in the envelope.
- Affix the measurement table to the electrical panel, once completed.
Measurement table – Place in the electrical panel| Resistance
(Ω)
| Insulation
1MΩ
---|---|---
Factory results| Ex. : 11.52| OK
1. Before breaking the seal| |
2. After cable installation| |
3. Before embedding cable| |
4. After embedding cable| |
5. After final surfacing| |
6. Before wiring system| |