TROVE T3MB777K1 Altronix Mercury Wired Kits Installation Guide

June 1, 2024
TROVE

TROVE T3MB777K1 Altronix Mercury Wired Kits

Specifications

  • Models: T3MB777K1, T3MB777K1D
  • Configuration: 24 Door Kit with Fused Outputs or PTC Outputs
  • Components: Trove3 enclosure, TM3B Altronix/Mercury backplane, eFlow104NB Power Supply/Chargers, ACMS8/PDS8 Dual Input/Output Modules, Rocker Switches, Wire harnesses
  • UL Listed sub-assemblies
  • Nominal DC Output Voltage Range: 24VDC
  • Maximum Supply Current: 9.4A

Overview
Altronix Trove Plus kits are pre-wired and pre-assembled for easy installation. The kits include all necessary components housed in a Trove3 enclosure.

Installation Guide
All wiring methods should comply with the National Electrical Code and local regulations. The product is designed for indoor use only.

Enclosure Mounting

  1. Remove the backplane from the enclosure without discarding any hardware.
  2. Mark and predrill holes in the wall to align with the top three keyholes in the enclosure.
  3. Install three upper fasteners and screws in the wall to mount the enclosure securely.

FAQ
Q: Can the Trove kits be used outdoors?
A: No, the product is intended for indoor use only.

Access & Power Integration

Altronix/Mercury Wired Kits
Models Include

T3MB777K1
24 Door Kit with Fused Outputs
Accommodates one (1) Intelligent Dual Reader Controller and eleven (11) Dual Reader Interface Modules.

Each fully assembled kit includes

  • Trove3 enclosure with TM3B Altronix/Mercury backplane and 36 BR3M mounting brackets.

  • Three (3) eFlow104NB – Power Supply/Chargers

  • Three (3) ACMS8 – Dual Input/Output Fuse Protected Access Power Controllers

  • Three (3) PDS8 – Dual Input/Output Fuse Protected Power Distribution Modules

  • Two (2) Rocker Switch Brackets with
    Three (3) Rocker Switches (Not evaluated by UL)

  • Wire harnesses and management

T3MB777K1D
24 Door Kit with PTC Outputs
Accommodates one (1) Intelligent Dual Reader Controller and eleven (11) Dual Reader Interface Modules.

Each fully assembled kit includes:

  • Trove3 enclosure with TM3B Altronix/Mercury backplane and 36 BR3M mounting brackets.

  • Three (3) eFlow104NB – Power Supply/Chargers

  • Three (3) ACMS8CB – Dual Input/Output PTC Protected Access Power Controllers

  • Three (3) PDS8CB – Dual Input/Output PTC Protected Power Distribution Modules

  • Two (2) Rocker Switch Brackets with
    Three (3) Rocker Switches (Not evaluated by UL)

  • Wire harnesses and management

All components of these Trove kits are UL Listed sub-assemblies.
Please refer to the included corresponding Sub-Assembly Installation Guides for further information.

Installation Guide

All registered trademarks are property of their respective owners.

  • Rev. T3MB777K1_051823
  • Installing Company: _____
  • Service Rep. Name: __
  • Address: _____
  • Phone #: _____

Overview

Altronix Trove Plus kits are pre-wired, pre-assembled and consist of Trove3M3 enclosure/backplane with factory installed Altronix power supply/chargers and sub-assemblies, wire harnesses and finger duct.

Configuration Chart

Altronix

Model Number

| 120VAC 60Hz

Input Current (A)

| Power Supply Board Input Fuse Rating| Power Supply Board Battery Fuse Rating| **** Nominal DC Output Voltage Range| Maximum Supply Current for Main and Aux. Outputs on Power Supply board and ACMS8(CB) Access Power Controller’s outputs| Fail-Safe/Fail-Secure or Dry Form “C” Outputs| Current Per ACMS8(CB) and PDS8(CB) Output (A)| ACMS8(CB) Board

Input Fuse (PTC) Rating

| ACMS8(CB) Board

Output Fuse (PTC) Rating

| PDS8(CB) Board

Input Fuse (PTC) Rating

| PDS8(CB) Board

Output Fuse (PTC) Rating

---|---|---|---|---|---|---|---|---|---|---|---
Power Supply 1| Power Supply 2| Power Supply 3
Output Range (VDC)| Output Range (VDC)| Output Range (VDC)
T3MB777K1| **** 13.5| **** 6.3A/

250V

| **** 15A/

32V

| **** 20.17-

26.4

| **** 20.17-

26.4

| **** 20.17-

26.4

| 24VDC @ 9.4A| **** 24| 2.5| 15A/

32V

| 3A/

32V

| 10A/

32V

| 3A/

32V

T3MB777K1D| 2.0| 9A| 2.5A| 9A| 2.5A

Hardware and Accessories

  • Two (2) tamper switches (Altronix Model TS112 or equivalent).
  • Cam lock.
  • Battery leads.

Mechanical

  • 16 Gauge enclosure with ample knockouts for convenient access.
  • Enclosure Dimensions (H x W x D): 36.12” x 30.125” x 7.06” (917.5mm x 768.1mm x 179.3mm).

Installation Instructions:

Enclosure Mounting:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.

  1. Remove backplane from enclosure. Do not discard hardware.

  2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes
    over the three upper screws. Install the three lower screws and make sure to tighten all screws. Fig. 1

  3. Mount included UL Listed tamper switches (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
    Installing and Connecting Lenel/Mercury Modules:

  4. Altronix power supplies and sub-assemblies are factory installed and wired.
    Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB and corresponding Sub-Assembly Installation Guides for PDS8(CB) and ACMS8(CB) for further installation instructions.

  5. Position Lenel/Mercury access controller modules over corresponding spacers and depress onto factory installed snap on spacers on the brackets (Fig. 2, pg. 3). When mounting Lenel/Mercury modules, start with the bottom to facilitate easy mounting.

  6. Connect wire harnesses to Lenel/Mercury access controller modules (Fig. 2, pg. 3).

  7. Mount backplane to enclosure with hardware.

T3MB777K1(D) Configuration

  1. Position access controller module over corresponding spacers and depress onto snap on spacers (Fig. 2, pg. 3).
  2. Mount backplane to enclosure with hardware.

Access Controller Position Chart for the Following ModelsTROVE-
T3MB777K1-Altronix-Mercury-Wired-Kits-2 TROVE-T3MB777K1-Altronix-Mercury-Wired-Kits-3

Trove3 Enclosure Dimensions (H x W x D approximate): 36.12” x 30.125” x 7.06” (917.5mm x 768.1mm x 179.3mm) TROVE-T3MB777K1-Altronix-Mercury-Wired-
Kits-4

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. –140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty IIT3MB777K1 Kit Series