TRIPP-LITE S3MT-100K600V S3MT-Series 3-Phase 100kVA Input Isolation Transformer 600V Delta to 208V Wye Instructions
- June 3, 2024
- Tripp Lite
Table of Contents
TRIPP-LITE S3MT-100K600V S3MT-Series 3-Phase 100kVA Input Isolation
Transformer 600V Delta to 208V Wye
MODEL NUMBER: S3MT-100K600V
100kVA/kW transformer provides 600V (Delta) to 208V (Wye) step-down and isolation protection to a 3-phase UPS and its load.
Features
Get Complete Step-Down/Step-Up and Isolation Protection
Tripp Lite’s S3MT-100K600V 100kVA/kW transformer offers line isolation and
protection to the connected 3-phase UPS system and its load. It isolates the
UPS and connected components from line surges and spikes caused by utility
power disruptions that can damage equipment or corrupt data. The step-down
input isolation transformer is ideal for 4-wire (3Ph+N+PE) IT loads in
government, manufacturing, healthcare and corporate settings with a 600V
electrical feed and 208/120V equipment.
Performs with High Efficiency up to 97.7%
Not only is the S3MT-100K600V very efficient, with up to 97.7 percent
efficiency, but it is also very quiet with a noise profile less than 65 dBA. A
built-in circuit breaker on the output side helps prevent dangerous power
overloads. Three ball-bearing cooling fans help prevent overheating. An
overheat-sensing relay and switch combine with a red LED indicator to provide
over-temperature warning and overheating protection.
Small Footprint for Quick Installation in a Compact Space
The compact footprint enables installation of the S3MT-100K600V with minimal
space. The rugged stainless steel housing ships ready for immediate tower
installation with a compatible 80–100kVA/kW Tripp Lite S3M-Series 208V 3-phase
UPS system.
Highlights
- Recommended for government, manufacturing, healthcare and corporate settings
- Up to 97.7% efficiency with a quiet acoustic profile less than 65 dBA
- Resettable protection relay/switch and red LED indicator warn against overheating
- Rugged stainless steel housing with compact footprint comes ready for installation Compatible with 80–100kVA/kW Tripp Lite S3M-Series 208V 3-phase UPS systems
Applications
Protect healthcare, manufacturing, corporate and other IT equipment where the upstream power source is 600V and the load requires a 208V 3-phase UPS
System Requirements
80–100kVA/kW Tripp Lite S3M-Series 208V 3-phase UPS system
Package Includes
S3MT-100K600V 3-Phase 100kVA Input Isolation Transformer
- (4) Bottom skirts
- (24) Screws
- Owner’s manual
Specifications
OVERVIEW
UPC Code| 037332253170
Efficiency| 96.7% @ full load
---|---
Nominal Voltage / Frequency| 600V 3-PH / 60Hz
VA / Watt Capacity| 100000
Transformer Type| Dry type, Input step-down isolation transformer
INPUT
Nominal Input Voltage(s) Supported| 600V 3-PH Delta
UPS Input Connection Type| Hardwire
Input Phase| 3-Phase
OUTPUT
Output Volt Amp Capacity (VA)| 100000
Output Receptacles| Hardwire
PHYSICAL
Cooling Method| 3 x BALL BEARING, 172x152mm (723 TOTAL CFM)
Form Factors Supported| Tower
Primary Form Factor| Tower
Shipping Dimensions (hwd / in.)| 55.10 x 27.60 x 37.80
Shipping Weight (kg)| 499.86
Unit Dimensions (hwd / cm)| 120 x 60 x 85
Unit Dimensions (hwd / in.)| 47.2 x 23.6 x 33.5
Unit Weight (kg)| 475.82
Unit Weight (lbs.)| 1049
ENVIRONMENTAL
Heat Dissipation (BTU/Hr) @ Full Load| ****
11263
INPUT TRANSFORMER
Input Voltage| 600V
Input Voltage Range| (-45%, +25%) for 40% load (-20%, +25%) for 100% load
Input Amp(s)| 134 A
AC Input Configuration| Delta
AC Input Frequency| 50/60
Frequency Range| 40/70Hz
Voltage Selection| NONE
Input Inrush Current| 1160 A
VA Rating| 100K
---|---
Input Number of Phases| 3PH
AC Output Voltage (V)| 600 V
AC Output Amps| 374 A
Output Number of Phases| 3PH + N
AC Output Configuration| WYE
Output Isolation| Yes
Output Breaker Rating| 400 A
Connection Type| COPPER BAR
LED Warning Light Functions| The over-temperature warning LED light will turn
ON when the output/secondary of the Input transformer reaches 160°C ±5°C and
will turn OFF wthen the corresponding transfomer cools down to 125°C ±5°C
Over Temperature Reset| If the secondary side of the input transformer reaches
temperatures of or higher than 160°C ± 5°C, i.e. a range of 155°C to 165°C
(311°F to 329°F), an over-temperature protection relay and thermal switch will
activate and will open the breaker on secondary side of the transformer. Once
the transformer temperature has cooled down to 125°C ± 5°C, i.e. a range of
120°C to 130°C ( 248°F to 266°F) the warning LED light will turn OFF, and you
may manually re- activate (close) the output breaker on the transformer to
restart normal operation.
Efficiency @ Half Load| 97.7%
Efficiency @ Full Load| 96.7%
Heat Dissipation (BTU/Hr) @ Full Load| ****
11263
Audible Noise (dBA @ 1m)| 65dB max
WARRANTY
Product Warranty Period (Worldwide)| ****
2-year limited warranty
Product Warranty Period (U.S. & Canada)| ****
2-year limited warranty
© 2021 Tripp Lite. All rights reserved. All product and company names are
trademarks or registered trademarks of their respective holders. Use of them
does not imply any affiliation with or endorsement by them. Tripp Lite has a
policy of continuous improvement. Specifications are subject to change without
notice. Tripp Lite uses primary and third-party agencies to test its products
for compliance with standards. See a list of Tripp Lite’s testing agencies:
https://www.tripplite.com/products/product-certification-agencies