Functional Devices PSH600-UPS-BC Uninterruptible Power Supply Kit Instructions

June 1, 2024
Functional Devices

Functional-Devices-logo

Functional Devices PSH600-UPS-BC Uninterruptible Power Supply Kit

Functional-Devices-PSH600-UPS-BC-Uninterruptible-Power-Supply-Kit-
product

Product Information

Specifications

  • Model: PSH600-UPS-BC
  • Description: 600 VA UPS Backup Power Control Center, BACnet MS/TP Network, 12 x 14 x 6 Metal Enclosure
  • Line Input: 120Vac, 10A(max)
  • Convenience Receptacles: 120Vac, 10A(max combined)
  • Backup Time: 2.5 minutes at full 600 VA load
  • Network Media: Twisted Pair 22-24 AWG, shielded recommended (MS/TP)
  • Terminations: Functional Devices products installed at both ends of the MS/TP network

Product Usage Instructions

Installation

  1. Connect the UPS to a power source using the provided cable.
  2. Install the UPS at both ends of the MS/TP network using DIP switches for power-up.
  3. Ensure proper termination with 120 ohms of Line Resistors for the MS/TP network.

Operation

  1. Power on the UPS using the main breaker switch.
  2. Monitor the LED indicators for device power, status, network communication, backup power, and USB status.
  3. Adjust DIP switches for the desired baud rate and MS/TP address according to the setup requirements.

Maintenance

  1. Regularly check the UPS for any physical damage or signs of wear.
  2. Test the UPS backup power function periodically to ensure proper functionality.

Frequently Asked Questions (FAQ)

  • Q: How long does the UPS provide backup power?
    A: The UPS provides approximately 2.5 minutes of backup power at a full 600 VA load.

  • Q: What is the recommended network media for the UPS?
    A: Twisted Pair 22-24 AWG shielded cables are recommended for the MS/TP network.

  • Q: How do I set the baud rate and MS/TP address for the UPS?
    A: Use the DIP switches to select the baud rate (options: 9600, 19200, 38400, 57600, 76800, 115200) and configure the MS/TP address accordingly.

Wiring

PSH600-UPS-BC
600 VA UPS Backup Power Control Center, BACnet MS/TP Network, 12” x 14” x 6” Metal Enclosure.

Functional-Devices-PSH600-UPS-BC-Uninterruptible-Power-Supply-Kit-
fig-1

SPECIFICATIONS

BOARD AND ENCLOSURE:

  • Operating Temperature: -30 to 140° F
  • Humidity Range: 5 to 95% (noncondensing)
  • Indicators:
    • Device Power: Red LED
    • Device Status: Pink LED
    • Network Communication: Green LED
    • Backup Power: Yellow LED
    • USB Status: Blue LED
  • Main Breaker ON/OFF: Switch / Breaker (10 Amp)
  • Dimensions: 12” H x 14˝ W x 6˝ D
  • Origin: Made of US and non-US parts
  • Track Mount: 2.750˝ x 8.000˝ MT212-8N Mounting Track Included
  • Approvals: UL Listed, UL916, C-UL, CE, RoHS
  • Line Input: 120Vac, 10A(max)
  • Convenience Receptacles: 120Vac, 10A(max combined)

UPS:

  • UPS: 600VA
  • Backup Time:
    • 2.5 Min. @ Full 600 VA Load
    • 10.2 Min. @ 1/2 Load
  • Input: 120 Vac, 12 Amp
  • Output: 120 Vac, 4.6 Amp
  • Max Load: 330 Watt
  • Frequency: 50/60 Hz
  • Temperature Rating of UPS: 32 to 104° F
  • UPS Transfer Time: 6ms
  • Approvals: UL Listed, UL1778

Notes:

  1. Average battery life: 3-5 years depending on the number of discharge cycles and environmental temperature
  2. This model is not designed to notify users of battery failure.
  3. This model is designed to work exclusively with Functional Devices Model UPS600
  • Power Input Rating:
    25mA @ 120Vac

  • Network Media:

    • Twisted Pair 22-24 AWG, shielded recommended (MS/TP)
    • USB A/B (device to UPS, included)
  • Terminations:
    Functional Devices product installed at both ends of the MS/TP network – Use 120 Ohm End of Line Resistors. All other cases follow instructions from the device installed at the end of the MS/TP network.

  • Polarity:
    The network is polarity-sensitive.

  • Baud Rate:
    9600, 192000, 38400, 76800, 115200 ( DIP Switch Selectable)

**DIP SWITCHES***   BAUD RATE
8 9 10
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1

All other combinations=9600 baud

Notes:

  • Circuit breaker for short-circuit protection.
  • 14/3 Line Cord included (3´).

BACnet® Details:

  • MS/TP Address & Baud Rate must be set before powering up via DIP switches.

  • Device ID will default to 277XXX where XXX is the MS/TP Address.
    Examples:

    • MS/TP Address – 004
      Device ID – 277004

    • MS/TP Address – 121
      Device ID – 277121

  • The device ID can be changed via network command. Once changed, it will no longer default to 277XXX. (MS/TP Address & Device ID must be unique.)

  • Devices Instance changed via Object Identifier Property of Device Object.

  • The statthe UPthe S connection, Battery run time, line power, UPS load (VA and %), and battery capacity can be read from the BACnet network.

ESTIMATED BACKUP TIME VS. LOAD

Functional-Devices-PSH600-UPS-BC-Uninterruptible-Power-Supply-Kit-
fig-2

INFORMATION PROVIDED OVER THE BACNET® NETWORK CAN BE USED TO SCHEDULE “PREDICTIVE MAINTENANCE” SUCH AS UPS BATTERY REPLACEMENT, ETC.