Functional Devices PSH600-UPS-BC Uninterruptible Power Supply Kit Instructions
- June 1, 2024
- Functional Devices
Table of Contents
Functional Devices PSH600-UPS-BC Uninterruptible Power Supply Kit
Product Information
Specifications
- Model: PSH600-UPS-BC
- Description: 600 VA UPS Backup Power Control Center, BACnet MS/TP Network, 12 x 14 x 6 Metal Enclosure
- Line Input: 120Vac, 10A(max)
- Convenience Receptacles: 120Vac, 10A(max combined)
- Backup Time: 2.5 minutes at full 600 VA load
- Network Media: Twisted Pair 22-24 AWG, shielded recommended (MS/TP)
- Terminations: Functional Devices products installed at both ends of the MS/TP network
Product Usage Instructions
Installation
- Connect the UPS to a power source using the provided cable.
- Install the UPS at both ends of the MS/TP network using DIP switches for power-up.
- Ensure proper termination with 120 ohms of Line Resistors for the MS/TP network.
Operation
- Power on the UPS using the main breaker switch.
- Monitor the LED indicators for device power, status, network communication, backup power, and USB status.
- Adjust DIP switches for the desired baud rate and MS/TP address according to the setup requirements.
Maintenance
- Regularly check the UPS for any physical damage or signs of wear.
- Test the UPS backup power function periodically to ensure proper functionality.
Frequently Asked Questions (FAQ)
-
Q: How long does the UPS provide backup power?
A: The UPS provides approximately 2.5 minutes of backup power at a full 600 VA load. -
Q: What is the recommended network media for the UPS?
A: Twisted Pair 22-24 AWG shielded cables are recommended for the MS/TP network. -
Q: How do I set the baud rate and MS/TP address for the UPS?
A: Use the DIP switches to select the baud rate (options: 9600, 19200, 38400, 57600, 76800, 115200) and configure the MS/TP address accordingly.
Wiring
PSH600-UPS-BC
600 VA UPS Backup Power Control Center, BACnet MS/TP Network, 12” x 14” x 6”
Metal Enclosure.
SPECIFICATIONS
BOARD AND ENCLOSURE:
- Operating Temperature: -30 to 140° F
- Humidity Range: 5 to 95% (noncondensing)
- Indicators:
- Device Power: Red LED
- Device Status: Pink LED
- Network Communication: Green LED
- Backup Power: Yellow LED
- USB Status: Blue LED
- Main Breaker ON/OFF: Switch / Breaker (10 Amp)
- Dimensions: 12” H x 14˝ W x 6˝ D
- Origin: Made of US and non-US parts
- Track Mount: 2.750˝ x 8.000˝ MT212-8N Mounting Track Included
- Approvals: UL Listed, UL916, C-UL, CE, RoHS
- Line Input: 120Vac, 10A(max)
- Convenience Receptacles: 120Vac, 10A(max combined)
UPS:
- UPS: 600VA
- Backup Time:
- 2.5 Min. @ Full 600 VA Load
- 10.2 Min. @ 1/2 Load
- Input: 120 Vac, 12 Amp
- Output: 120 Vac, 4.6 Amp
- Max Load: 330 Watt
- Frequency: 50/60 Hz
- Temperature Rating of UPS: 32 to 104° F
- UPS Transfer Time: 6ms
- Approvals: UL Listed, UL1778
Notes:
- Average battery life: 3-5 years depending on the number of discharge cycles and environmental temperature
- This model is not designed to notify users of battery failure.
- This model is designed to work exclusively with Functional Devices Model UPS600
-
Power Input Rating:
25mA @ 120Vac -
Network Media:
- Twisted Pair 22-24 AWG, shielded recommended (MS/TP)
- USB A/B (device to UPS, included)
-
Terminations:
Functional Devices product installed at both ends of the MS/TP network – Use 120 Ohm End of Line Resistors. All other cases follow instructions from the device installed at the end of the MS/TP network. -
Polarity:
The network is polarity-sensitive. -
Baud Rate:
9600, 192000, 38400, 76800, 115200 ( DIP Switch Selectable)
**DIP SWITCHES*** | BAUD RATE | |
---|---|---|
8 | 9 | 10 |
0 | 0 | 0 |
0 | 0 | 1 |
0 | 1 | 0 |
0 | 1 | 1 |
1 | 0 | 0 |
1 | 0 | 1 |
All other combinations=9600 baud
Notes:
- Circuit breaker for short-circuit protection.
- 14/3 Line Cord included (3´).
BACnet® Details:
-
MS/TP Address & Baud Rate must be set before powering up via DIP switches.
-
Device ID will default to 277XXX where XXX is the MS/TP Address.
Examples:-
MS/TP Address – 004
Device ID – 277004 -
MS/TP Address – 121
Device ID – 277121
-
-
The device ID can be changed via network command. Once changed, it will no longer default to 277XXX. (MS/TP Address & Device ID must be unique.)
-
Devices Instance changed via Object Identifier Property of Device Object.
-
The statthe UPthe S connection, Battery run time, line power, UPS load (VA and %), and battery capacity can be read from the BACnet network.
ESTIMATED BACKUP TIME VS. LOAD
INFORMATION PROVIDED OVER THE BACNET® NETWORK CAN BE USED TO SCHEDULE “PREDICTIVE MAINTENANCE” SUCH AS UPS BATTERY REPLACEMENT, ETC.
Contact Information
- Functional Devices, Inc. 101 Commerce Drive, Sharpsville, IN 46068
- Email: sales@functionaldevices.com
- Website: www.functionaldevices.com
- Toll-Free: 800-888-5538
- Office: 765-883-5538
- Fax: 765-883-7505