e2s GNExB2X05 Flameproof Xenon Beacons Instruction Manual
- June 2, 2024
- e2S
Table of Contents
- e2s GNExB2X05 Flameproof Xenon Beacons
- Product Table
- Marking & Rating Information
- NEC Class / Zone Ratings US Codes
- CEC Class / Zone Ratings Canada
- NEC & CEC Class / Division Ratings for US / Canada, USL CNL
- Zones, Gas Group, Category and Temperature Classification
- Special Conditions for Safe Use
- Product Mounting and Access
- Installation Requirements
- Cable Glands, Blanking Elements & Adapters
- Flash Pattern Settings
- End of Line Monitoring (DC Units)
- Interchangeable & Spare Parts
- SIL 2 Reliability Data
- EU Declaration of Conformity
- UKCA Declaration of Conformity
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
e2s GNExB2X05 Flameproof Xenon Beacons
Product Table
**Standard| ****Model| Nom. Voltage| ****Voltage
Range| Nom. Operating Current*| Max Current
---|---|---|---|---|---
** ATEX / IECEx / UKEX NEC / CEC| GNExB2X05DC012| 12Vdc| 12-14Vdc| 585mA|
600mA
GNExB2X05DC024| 24Vdc| 20-28Vdc| 295mA| 350mA
GNExB2X05DC048| 48Vdc| 42-54Vdc| 145mA| 150mA
GNExB2X05AC115| 115Vac| 110-120Vac 50/60Hz| 140mA| 200mA
GNExB2X05AC230| 230Vac| 220-240Vac 50/60Hz| 70mA| 100mA
GNExB2X10DC024| 24Vdc| 20-28Vdc| 605mA| 710mA
GNExB2X10DC048| 48Vdc| 42-54Vdc| 230mA| 250mA
GNExB2X10AC115| 115Vac| 110-120Vac 50/60Hz| 220mA| 300mA
GNExB2X10AC230| 230Vac| 220-240Vac 50/60Hz| 130mA| 180mA
*** ATEX / IECEx / UKEX| GNExB2X15DC024| 24Vdc| 20-28Vdc| 835mA| 920mA
GNExB2X15DC048| 48Vdc| 42-54Vdc| 330mA| 360mA
GNExB2X15AC115| 115Vac| 110-120Vac 50/60Hz| 310mA| 420mA
GNExB2X15AC230| 230Vac| 220-240Vac 50/60Hz| 170mA| 230mA
GNExB2X21DC024| 24Vdc| 20-28Vdc| 1130mA| 1240mA
GNExB2X21DC048| 48Vdc| 42-54Vdc| 530mA| 560mA
GNExB2X21AC115| 115Vac| 110-120Vac 50/60Hz| 500mA| 530mA
GNExB2X21AC230| 230Vac| 220-240Vac 50/60Hz| 195mA| 270mA
Rate at 1Hz
The table shows the input current taken by the various beacons. Nominal
current at nominal voltage and 1Hz flash rate.
Max. rated current at worst case supply voltage and flash rate.
Table 1: Electrical Ratings.
Ensure the system power supply is capable of providing the maximum current required for all beacons. Review associated cable size, length and quantity of beacons on each circuit.
Warnings
- POTENTIAL ELECTROSTATIC CHARGING HAZARD –CLEAN ONLY WITH A DAMP CLOTH.
- DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT.
ALL ENTRIES M20 X 1.5MM.
USE SUITABLE RATED CABLES AND CABLE GLANDS IF TEMPERATURE EXCEEDS AS PER
STANDARDS INDICATIONS BELOW.
FOR ATEX / IECEx / UKEX STANDARDS:
70ºC AT ENTRY OR 80ºC AT BRANCHING POINT.
FOR NEC / CEC STANDARDS: 60ºC AT ENTRY OR 60ºC AT BRANCHING POINT.
Marking & Rating Information
All units have a rating label, which carries the following important information:
- Unit Model.
- Voltage Range
- Nominal Voltage
- Max. Current
See Table 1 for electrical ratings of each Unit Model.
ATEX / IECEx / UKEX Ratings
Standards
EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7):
Explosive Atmospheres – Equipment. General Requirements EN60079-1:2014 /
IEC60079-1:2014 (Ed 7):
Explosive Atmospheres – Equipment Protection by Flameproof Enclosures “d” BS
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2):
Explosive Atmospheres – Equipment Dust Ignition Protection by Enclosure “t”
Ratings
GNExB2:| Ex db IIC T5 Gb Ta -50°C to +70°C
X05DC012| Ex db IIC T6 Gb Ta -50°C to +60°C
X05DC024| Ex tb IIIC T89°C Db Ta -50°C to +70°C
X05DC048|
GNExB2:| Ex db IIC T4 Gb Ta -50°C to +70°C
X05AC115| Ex db IIC T5 Gb Ta -50°C to +55°C
X05AC230| Ex db IIC T6 Gb Ta -50°C to +40°C
| Ex tb IIIC T110°C Db Ta -50°C to +70°C
GNExB2:| Ex db IIC T4 Gb Ta -50°C to +70°C
X10DC024| Ex db IIC T5 Gb Ta -50°C to +45°C
X10DC048| Ex tb IIIC T117°C Db Ta -50°C to +70°C
GNExB2:| Ex db IIC T4 Gb Ta -50°C to +70°C
X10AC115| Ex db IIC T5 Gb Ta -50°C to +40°C
X10AC230| Ex tb IIIC T122°C Db Ta -50°C to +70°C
GNExB2:| Ex db IIC T4 Gb Ta -50°C to +70°C
X15DC024| Ex tb IIIC T125°C Db Ta -55°C to +70°C
X15DC048|
GNExB2:| Ex db IIC T3 Gb Ta -50°C to +70°C
X15AC115| Ex db IIC T4 Gb Ta -50°C to +65°C
X15AC230| Ex tb IIIC T134°C Db Ta -55°C to +70°C
GNExB2: X21DC024 X21DC048| Ex db IIC T3 Gb Ta -50°C to +60°C Ex db IIC T4 Gb
Ta -50°C to +55°C Ex tb IIIC T135°C Db Ta -50°C to +60°C
---|---
GNExB2:| Ex db IIC T3 Gb Ta -50°C to +70°C
X21AC115| Ex db IIC T4 Gb Ta -50°C to +60°C
X21AC230| Ex tb IIIC T138°C Db Ta -50°C to +70°C
Certificate No.
DEMKO 15ATEX1448X IECEx UL15.0003X UL21UKEX2136X
NEC / CEC Ratings
All models are approved for use as Visual Signal Device for use as General
Signalling:
UL1638A & CSA C22.2 No 205-17
NEC Class / Zone Ratings US Codes
Standards
UL 60079-0 (Ed. 7) 04/15/2020
Explosive Atmospheres – part 0: Equipment – General Requirements
UL 60079-1 (Ed. 7) 2015
Explosive Atmospheres – Part 1: Equipment Protection by Flameproof Enclosures
‘d’
Ratings
GNExB2: X05DC012 X05DC024 X05DC048| Class I Zone 1 AEx db IIC T5 Gb Ta -50°C
to +70°C Class I Zone 1 AEx db IIC T6 Gb Ta -50°C to +60°C
GNExB2: X05AC115 X05AC230| Class I Zone 1 AEx db IIC T4 Gb Ta -50°C to +70°C
Class I Zone 1 AEx db IIC T5 Gb Ta -50°C to +55°C Class I Zone 1 AEx db IIC T6
Gb Ta -50°C to +40°C
GNExB2: X10DC024 X10DC048| Class I Zone 1 AEx db IIC T4 Gb Ta -50°C to +70°C
Class I Zone 1 AEx db IIC T5 Gb Ta -50°C to +45°C
GNExB2: X10AC115 X10AC230| Class I Zone 1 AEx db IIC T4 Gb Ta -50°C to +70°C
Class I Zone 1 AEx db IIC T5 Gb Ta -50°C to +40°C
*SIL Suitable
Installation must be carried out in compliance with the National Electric Code.
CEC Class / Zone Ratings Canada
Standards
CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019
Explosive Atmospheres – Part 0: Equipment – General Requirements
CAN/CSA C22.2 No. 60079-1 (Ed. 3) 2016
Electrical Apparatus for Explosive Gas Atmospheres – Part 1: Flameproof
Enclosures ‘d’
Rating
GNExB2:| Ex db IIC T5 Gb Ta -50°C to +70°C
X05DC012| Ex db IIC T6 Gb Ta -50°C to +60°C
X05DC024|
X05DC048|
GNExB2:| Ex db IIC T4 Gb Ta -50°C to +70°C
X05AC115| Ex db IIC T5 Gb Ta -50°C to +55°C
X05AC230| Ex db IIC T6 Gb Ta -50°C to +40°C
GNExB2:| Ex db IIC T4 Gb Ta -50°C to +70°C
X10DC024| Ex db IIC T5 Gb Ta -50°C to +45°C
X10DC048|
GNExB2:| Ex db IIC T4 Gb Ta -50°C to +70°C
X10AC115| Ex db IIC T5 Gb Ta -50°C to +40°C
X10AC230|
Installation must be carried out in compliance with the Canadian Electric Code.
NEC & CEC Class / Division Ratings for US / Canada, USL CNL
Standards
GNExB2X
Xenon beacons| UL1638A (Ed. 1) 2016
Standard for Visual Signal Appliances for General Signalling Use
CSA C22.2 No. 205-17 (Ed. 3) 2017
Signal Equipment
Ratings
GNExB2:| Class I Div 2 Group ABCD T5 Ta -50°C to +70°C
X05DC012| Class I Div 2 Group ABCD T6 Ta -50°C to +60°C
X05DC024|
X05DC048|
GNExB2:| Class I Div 2 Group ABCD T4 Ta -50°C to +70°C
X05AC115| Class I Div 2 Group ABCD T5 Ta -50°C to +55°C
X05AC230| Class I Div 2 Group ABCD T6 Ta -50°C to +40°C
GNExB2:| Class I Div 2 Group ABCD T4 Ta -50°C to +70°C
X10DC024| Class I Div 2 Group ABCD T5 Ta -50°C to +45°C
X10DC048|
GNExB2:| Class I Div 2 Group ABCD T4 Ta -50°C to +70°C
X10AC115| Class I Div 2 Group ABCD T5 Ta -50°C to +40°C
X10AC230|
The certification approval has validated continuous use up to 38°C ambient and
are for transient use up to 70°C ambient.
Installation must be carried out in compliance with the National Electric Code
/ Canadian Electric Code.
Zones, Gas Group, Category and Temperature Classification
The units can be installed in locations with the following conditions:
Area Classification
Zone 1| Explosive gas air mixture likely to occur in normal operation.
Zone 2| Explosive gas air mixture not likely to occur in normal operation, and
if it does, it will only exist for a short time.
Zone 21 (ATEX / IECEx / UKEX only)| Explosive dust air mixture likely
to occur in normal operation.
Zone 22 (ATEX / IECEx / UKEX only)| Explosive dust air mixture not
likely to occur in normal operation, and if it does, it will only exist for a
short time.
Gas Groupings
Group IIA| Propane
Group IIB| Ethylene
Group IIC| Hydrogen and Acetylene
Temperature Classification for Gas Applications
T1| 450ºC
T2| 300ºC
T3| 200ºC
(GNExB2X15AC & GNExB2X21AC up to 70°C
ambient; GNExB2X21DC up to 60°C ambient)
T4| 135ºC
(GNExB2X05AC, GNExB2X10DC, GNExB2X10AC & GNExB2X15DC up to 70°C ambient;
GNExB2X15AC up to 65°C ambient; GNExB2X21DC up to 55°C ambient; GNExB2X21AC up
to 60°C ambient)
T5| 100ºC (GNExB2X05DC up to 70°C ambient; GNExB2X05AC up to 55°C ambient;
GNExB2X10DC up to 45°C ambient; GNExB2X10AC up to 40°C ambient)
T6| 85ºC| ATEX / IECEx / UKEX: GNExB2X05DC up to 60°C ambient, GNExB2X05AC up
to 40°C ambient NEC / CEC: Up to 65ºC ambient
Dust Groupings (ATEX / IECEx / UKEX only)
Group IIIA| Combustible Flyings
Group IIIB| Non-conductive Dust
Group IIIC| Conductive Dust
Maximum Surface Temperature for Dust Applications (ATEX / IECEx / UKEX
only)
GNExB2X05DC| 89ºC
GNExB2X05AC| 110ºC
GNExB2X10DC| 117ºC
GNExB2X10AC| 122ºC
GNExB2X15DC| 125 ºC
GNExB2X15AC| 134ºC
GNExB2X21DC| 135ºC
GNExB2X21AC| 138ºC
Equipment Category
2G / 2D
Ambient Temperature Range
-50°C to +70°C
IP Rating
IP6X to EN/IEC60079-0 IP66 to EN60529
Special Conditions for Safe Use
Repair of the flame path / cemented joints is not permitted.
Figure 1: Flame Path.
The enclosure is non-conducting and may generate an ignition-capable level of
electrostatic charges under certain extreme conditions. The user should ensure
that the equipment is not installed in a location where it may be subjected to
external conditions that might cause a build-up of electrostatic charges on
non-conducting surfaces. The stainless steel beacon guard is not earthed and
may generate an ignition-capable level of electrostatic charges. It has a
capacitance of 10pF according to EN/IEC60079-0, clause 7.5. All entries must
be fitted with a suitable seal at the interface with enclosure.
Product Mounting and Access
Location and Mounting
The location of the beacons should be made with due regard to the area over
which the warning signal must be visible. They should only be fixed to
services that can carry the weight of the unit. The beacons should be securely
bolted to a suitable surface using the 9.4mm diameter bolt holes in the base
of the unit (see figure 2).
Access to the Flameproof Enclosure
In order to connect the electrical supply cables to the beacon it is necessary
to remove the flameproof cover to gain access to the flameproof chamber. To
access the Ex d chamber, loosen the M4 grub screw on the beacon cover. Open
the enclosure by turning the beacon cover counterclockwise and remove the
cover, taking extreme care not to damage the flameproof threads in the process
(see figure 3).
On completion of the installation the flameproof threaded joint should be inspected to ensure that they are clean and that they have not been damaged during installation. Flameproof threaded joints are not intended to be repaired. Ensure that the ‘O’ ring seal is in place and undamaged. When fitting the flameproof cover ensure the thread is engaged correctly. Fully tighten the cover all the way, ensure no gap is visible between the cover and base of the beacon enclosure. Tighten the M4 grub screw.
Installation Requirements
Installation Standards Compliance
Attention: Disconnect from power source before installation or service
to prevent electric shock.
The beacons must only be installed by suitably qualified personnel in
accordance with the latest issues of the relevant standards.
ATEX / IECEx & UKEx installation standards
- EN60079-14 / IEC60079-14: Explosive atmospheres – Electrical installations design, selection and erection.
- EN60079-10-1 / IEC60079-10-1: Explosive atmospheres – Classification of areas. Explosive gas atmospheres.
- EN60079-10-2 / IEC60079-10-2: Explosive atmospheres – Classification of areas. Explosive dust atmospheres.
- The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training.
NEC / CEC Installation Standards
Cautions
Attention: Installation must be carried out by an electrician in
compliance with the National Electrical Code, NFPA 70 or CSA 22.1 Canadian
Electrical Code, Part I, Safety Standard for Electrical Installations, Section
32.
Attention: Disconnect from power source before installation or service to
prevent electric shock
The installation of the units must also be in accordance with any local codes
that may apply and should only be carried out by a competent electrical
engineer who has the necessary training.
Cable Selection and Connections
When selecting the cable size, consideration must be given to the input
current that each unit draws (see table 1), the number of beacons on the line
and the length of the cable runs. The cable size selected must have the
necessary capacity to provide the input current to all of the beacons
connected to the line. Electrical connections are to be made into the terminal
blocks on the PCBA, using solid wire 0.5-4mm2 / AWG 20-12 or stranded wire,
sizes 0.5-2.5mm2 / AWG 24-14. Wire insulation needs to be stripped 8mm. Wires
may be fitted securely with crimped ferrules.
Terminal screws need to be tightened down with a tightening torque of 0.45 Nm / 5 Lb-in. A 5-way terminal block is provided on the AC Beacon: 2-off Live, 2-off Neutral and 1-off Earth terminals in total. A 4-way terminal block is provided on the DC Beacon: 2-off +ve and 2-off -ve terminals.
When connecting wires to the terminals great care should be taken to dress the wires so that when the cover is inserted into the chamber the wires do not exert excess pressure on the terminal blocks. This is particularly important when using cables with large cross-sectional areas such as 2.5mm².
Earthing
Please note that for AC supply voltage product versions the Earth terminal on
the PCBA does not provide an earth connection to the product enclosure. The
enclosure must be independently earthed using either the external or internal
earth fixing point, (see fig 5 and notes below). Internal earthing connections
should be made to the Internal Earth terminal in the base of the housing using
a ring crimp terminal to secure the earth conductor under the earth clamp. The
earth conductor should be at least equal in size and rating to the incoming
power conductors. External earthing connections should be made to the M4 earth
stud, using a ring crimp terminal to secure the earth conductor to the earth
stud. The external earth conductor should be at least 4mm2 in size.
Cable Glands, Blanking Elements & Adapters
Follow the minimum temperature ratings of cables and cable glands according to the approvals applied.
ATEX / IECEx & UKEx Requirements
The cable entry temperature may exceed +70ºC or the cable branching point
temperature may exceed 80ºC at high ambient temperatures and therefore
suitable heat resisting cables and cable glands must be used, rated as
follows:
Table 2: ATEX / IECEx & UKEx Min. Ratings of Cables & Cable Glands.
NEC / CEC Requirements Only
For high ambient temperatures the cable entry temperature may exceed 60ºC or
the cable branching point temperature may exceed 60ºC and therefore suitable
heat resisting cables and cable glands must be used, with a rated service
temperature at least as stated below:
Table 3: NEC / CEC Min. Ratings of Cables & Cable Glands. Cable Glands &
Blanking Plugs
Appropriate cable glands to be customer supplied.
ATEX / IECEx & UKEx Requirements Only
The cable gland entries have an M20 x 1.5 entry thread. Only suitably rated
and ATEX / IECEx & UKEx certified cable glands which must be suitable for the
type of cable being used and also meet the requirements of the current Ex ‘d’
flameproof installation standards EN 60079-14 / IEC60079-14. If the
installation is made using conduit, openings must have a sealing fitting
connected as close as practical to the wall of the enclosure, but in no case
more than the size of the conduit or 50mm, whichever is the lesser. When only
one cable entry is used the other entries must be closed with suitably rated
and ATEX / IECEx & UKEx certified blanking plugs.
NEC / CEC Requirements Only
The cable entries have an M20 x 1.5 – 6H entry thread. If the installation is
made using cable glands, only suitably rated and certified cable glands must
be used. They must be suitable for the type of cable being used and also meet
the requirements of the current NEC / CEC installation standards. If the
installation is made using conduit, openings must have a sealing fitting
connected as close as practical to the wall of the enclosure, but in no case
more than the size of the conduit or 50mm, whichever is the lesser. For use in
Class I Division II locations, in order to maintain the db type protection,
flameproof conduit seals and/or cable glands must be used. Any unused cable
entries must be closed with suitably rated and certified blanking plugs.
Ingress Protection
Follow instructions according to the approvals applied.
ATEX / IECEx & UKEx Requirements Only
If a high IP (Ingress Protection) rating is required then a suitable sealing
washer must be fitted under the cable glands or blanking plugs. A minimum
ingress protection rating of IP6X must be maintained for installations in
explosive dust atmospheres.
NEC / CEC Requirements Only
If a high IP (Ingress Protection) rating is required then a suitable sealing
washer must be fitted under the cable glands or blanking plugs. A minimum
ingress protection rating of IP6X must be maintained for installations in
explosive dust atmospheres.
Adapters
The GNEx Beacon Range can be supplied with the following types of
adapters:
- M20 to 1/2” NPT
- M20 to 3/4” NPT
- M20 to M25
It is important to note that stopping plugs cannot be fitted onto adapters, only directly onto the M20 entries. Any other adapters used must be suitably rated as per the applicable standards.
Flash Pattern Settings
Warning – high-intensity light source. Avoid looking directly at the
light source for extended periods of time.
The GNExB2 beacon can produce different flash patterns as shown in Table 4.
The flash patterns are selected by operation of the flash setting DIP switch
on the PCB, Fig 6.
Switch Setting | S1 Mode |
---|---|
00 | 1Hz (60FPM) |
01 | 1.33Hz (80FPM) |
10 | 1.5Hz (90FPM) |
11 | Double Flash |
Table 4: Switch Positions for Flash Patterns
End of Line Monitoring (DC Units)
All DC units have a blocking diode fitted in their supply input lines. An end of line monitoring diode or an end of line monitoring resistor can be connected across the +ve and –ve terminals in the flameproof chamber. If an end of line resistor is used it must have a minimum resistance value of 3k3 ohms and a minimum wattage of 0.5W or a minimum resistance value of 500 ohms and a minimum wattage of 2W. The resistor must be connected directly across the +ve and – ve terminals as shown in the following drawing. The resistor leads should be kept as short as possible.
Interchangeable & Spare Parts
Warning – Hot surfaces. External surfaces and internal components may be hot after operation, take care when handling the equipment.
- The beacon lens is interchangeable, contact European Safety Systems Ltd for a replacement lens available in various colours.
- The guard is an integral part of the protection and must be reassembled exactly the same way as it was disassembled.
- To change the lens, unscrew the M5 socket head screws and remove the M5 screws, M5 spring & flat washers.
Remove the guard and replace the old lens with the new lens.
Fit the guard back on to the lens and casting, align the holes of the guard, lens and casting. To reattach the lens, the fixings MUST be in the order shown in figure 10.
Maintenance, Overhaul and Repair
Maintenance, repair and overhaul of the equipment should only be carried out
by suitably qualified personnel in accordance with the current relevant
standards: EN60079 19/IEC60079-19 Explosive atmospheres Equipment repair,
overhaul and reclamation EN 60079-17/IEC60079-17 Explosive atmospheres
Electrical installations inspection and maintenance Units must not be opened
while an explosive atmosphere is present. If opening the unit during
maintenance operations a clean environment must be maintained and any dust
layer removed prior to opening the unit. Repair of the flameproof threaded
joints and cemented joints is not permitted.
Electrostatic charging hazard – Clean only with a damp cloth.
SIL 2 Reliability Data
Reliability and Functional safety IEC/EN61508 which has been assessed and is considered suitable for use in low demand safety function:
-
Random Hardware Failures and Architectural constraints (route 2H).
-
As an unvoted item (i.e. hardware fault tolerance of 0) at SIL 2.
The product was assessed against failure modes:- Failure respond to an input by lighting a beacon.
- Spurious light output despite no input.
-
When employing the device in a SIL2 compliant system the user should ensure frequent or continuous automatic monitoring of continuity.
Integrity in respect of failure to function | SIL2 & SIL1 |
---|---|
Total Failure rate | 0.48 pmh |
“Hazardous” failure rate (revealed) | 0 pmh |
“Hazardous” failure rate (unrevealed) | 0.48 pmh |
“Safe” failure rate (revealed) | 0 pmh |
“Safe” failure rate (unrevealed) | 0 |
System type | B |
Hardware Fault Tolerance | 0 |
Diagnostic Coverage | >60% |
PFD (hazardous failure) | 2.1 x 10-3 |
Proof Test Interval | Up to 1 year |
EU Declaration of Conformity
Manufacturer:
European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
Authorised Representative:
E2S Warnsignaltechnik UG
Charlottenstrasse 45‐51
72764 Reutlingen
Germany
Equipment Type:
GNExB1X05
GNExB2X05, GNExB2X10, GNExB2X15, GNExB2X21 GNExB2LD2N GNExJ2
Directive 2014/34/EU: Equipment and Protective Systems for use in Potentially
Explosive Atmospheres (ATEX)
Notified Body for EU type Examination (Module B):
UL International Demko A/S
Notified Body No.: 0539
Borupvang 5A, 2750 Ballerup, Denmark
EU‐type Examination Certificate (Module B):
DEMKO 15ATEX1448X
Sira Certification Service
Notified Body No.: 2813
CSA Group Netherlands B.V, Utrechtseweg 310, 6812 AR, Arnhem, Netherlands
Notified Body for Quality Assurance Notification / Conformity to EU‐type
based on quality assurance of the production process (Module D):
Quality Assurance Notification (Module D):
Provisions fulfilled by the equipment:
SIRA 05 ATEX M342
II 2G Ex db IIC T4…T6 Gb
II 2D Ex tb IIIC T80°C…T138°C Db
IP6X Dust Protection to EN60079‐0 / EN60079‐31
Standards applied:
EN IEC 60079‐0:2018
EN 60079‐1: 2014
EN 60079‐31: 2014
Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000‐6‐1:2007 EN 61000‐6‐2:2005
EN 61000‐6‐3:2007 / A1:2011 / AC: 2012 EN 61000‐6‐4:2007 / A1: 2011
Directive 2011/65/EU: Restriction of the use of certain hazardous
substances in electrical and electronic equipment (RoHS) The product and all
the components contained within it are in accordance with the restriction of
the use of hazardous substances in electrical and electronic equipment,
including amendment by Directive 2015/863/EU.
Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and
Restriction of Chemicals (REACH)
The product and all the components contained within it are free from
substances of very high concern.
Other Standards and Regulations
EN 60529:1992+A2:2013 ‐ Degrees of protection provided by enclosures (IP code)
– enclosure rated IP66/67
On behalf of European Safety Systems Ltd., I declare that, on the date the
equipment accompanied by this declaration is placed on the market, the
equipment conforms with all technical and regulatory requirements of the above
listed directives, regulations and standards. This Declaration is issued under
the sole responsibility of the manufacturer.
UKCA Declaration of Conformity
Manufacturer:
European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
Equipment Type:
GNExB1X05 GNExB2X05, GNExB2X10, GNExB2X15, GNExB2X21 GNExB2LD2 GNExJ2
Directive UKSI 2016:1107 (as amended by UKSI 2019:696) – Schedule 3A, Part 1 :
Product or Protective System Intended for use in Potentially Explosive
Atmospheres (UKCA)
Notified Body for UK type Examination (Module B):
UL International (UK) Ltd
Notified Body No.: 0843
Unit 1-3 Horizon Kingsland Business Park, Wade Road, Basingstoke, Hampshire
RG24 8AH UK
UK-type Examination Certificate (Module B):
UL21UKEX2136X
Sira Certification Service
Notified Body No.: 0518
Rake Lane, Eccleston, Chester CH4 9JN, UK
Notified Body for Quality Assurance Notification / Conformity to EU-type
based on quality assurance of the production process (Module D):
Quality Assurance Notification (Module D):
CSAE 22UKQAN0046
II 2G Ex db IIC T4…T6 Gb
II 2D Ex tb IIIC T80°C…T138°C Db
IP6X Dust Protection to EN60079-0 / EN60079-31
Provisions fulfilled by the equipment:
Standards applied:
EN IEC 60079-0:2018
EN 60079-1: 2014
EN 60079-31: 2014
Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000-6-1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007 / A1:2011 / AC: 2012
EN 61000-6-4:2007 / A1: 2011
Directive 2011/65/EU: Restriction of the use of certain hazardous substances
in electrical and electronic equipment (RoHS) The product and all the
components contained within it are in accordance with the restriction of the
use of hazardous substances in electrical and electronic equipment, including
amendment by Directive 2015/863/EU. Regulation (EC) 1907/2006: Registration,
Evaluation, Authorisation and Restriction of Chemicals (REACH) The product and
all the components contained within it are free from substances of very high
concern.
Other Standards and Regulations
EN 60529:1992+A2:2013 – Degrees of protection provided by enclosures (IP code)
– enclosure rated IP66/67
E2S Telephone: +44 (0)20 8743 8880
Fax: +44 (0)20 8740 4200
Email: sales@e2s.com
www.e2s.com DC-098_Issue_A (GNExB, GNExJ UKCA).docx –
Page 1 of 2 – QAF_252_Issue_5
On behalf of European Safety Systems Ltd., I declare that, on the date the
equipment accompanied by this declaration is placed on the market, the
equipment conforms with all technical and regulatory requirements of the above
listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>