e2S IS-mA1 Intrinsically Safe Round Sounder Instruction Manual

June 10, 2024
e2S

e2S Logo INSTRUCTION MANUAL
IS-mA1 Minialarm
Intrinsically Safe Round Soundere2S IS mA1 Intrinsically Safe Round
Sounder

IS-mA1 Intrinsically Safe Round Sounder

The IS-mA1 sounder is CE marked for compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU

Introduction

The IS-mA1 mini alarm is an ATEX, IECEx and UKEX certified intrinsically safe sounder which produces a loud warning signal in a hazardous area. Forty-nine first stage alarm sounds can be selected by internal switches and each one can be externally changed to a second or third stage alarm sound. The sounder may be used in all gas groups IIA IIB and IIC.

Description

Fig 1 shows a simplified block diagram of an IS-mA1 mini-alarm sounder. The device operates immediately power is applied to the + and – terminals which are duplicated to allow a second sounder to be connected in parallel, or for an end of line monitoring resistor to be installed. The output tone is defined by the positions of the six internal switches and this tone can be changed to a second or third stage alarm tone by connecting terminals S2 or S3 to 0V. The tone generator is crystal controlled to ensure that when two sounders connected to the same power supply are started at the same time the output tones remain synchronized.

Supply Voltage

The IS-mA1 mini alarm sounder has been designed to operate in a hazardous area from a 24V dc supply via 28V 93 mA resistive ATEX and IECEx certified Zenger Barriers or Galvanic Isolators. The sounders may be tested or used in safe areas without a Zener Barrier or Galvanic Isolator, but at supply voltages above 16V the internal current limit  will function and therefore it is recommended that they are not operated continuously with a direct supply greater than 16V.e2S IS mA1 Intrinsically Safe Round Sounder -
Sounder

Intrinsic Safety Certification

4.1 ATEX certificate
The IS-mA1 mini alarm sounder complies with the following standards:-
EN IEC 60079-0:2018
EN 60079-11:2012
EN 60079-26:2014
II 1G Exit IIC T4 Ga (-40ºC <= Ta <= +60ºC)
The EC-Type Examination Certificate SIRA 05ATEX2084X has been issued by the Notified Body Sira. This confirms compliance with the European ATEX Directive 2014/34/EU for Group II, Category 1G equipment. The sounder carries the Community Mark and subject to local codes of practice, may be installed in any of the EEA member countries. This instruction sheet describes installations which conform to EN60079: Part 14: 2008 Electrical Installation in Hazardous Areas. When designing systems for installation outside the UK, the local Code of Practice should be consulted.

  1. The certification marking is as follows:
  2. The equipment may be used in zones 0, 1 and 2 with flammable gases and vapours with apparatus groups IIA, IIB & IIC and with temperature classes T1, T2, T3 and T4.
  3. The equipment is only certified for use in ambient temperatures in the range -40°C to +60°C and should not be used outside this range.
  4. The certificate number has an ‘X’ suffix, which indicates that the certificate contains one of more special conditions for safe use. Those installing or inspecting the equipment should refer to this section of the certificate.
  5. The equipment has not been assessed as a safety related device (as referred to by Directive 2014/34/EU Annex II, clause 1.5).
  6. Installation of this equipment shall be carried out by suitably-trained personnel in accordance with the applicable code of practice.
  7. Repair of this equipment shall only be carried out by the manufacturer or in accordance with the applicable code of practice.
  8. The certification of this equipment relies on the following materials used in its construction:

Enclosure: ABS Plastic
If the equipment is likely to come into contact with aggressive substances, then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection is not compromised.
“Aggressive substances” – e.g. acidic liquids or gases that may attack metals, or solvents that may affect polymeric materials.
“Suitable precautions” – e.g. regular checks as part of routine inspections or establishing from the material’s data sheet that it is resistant to specific chemicals.
SPECIAL CONDITIONS FOR SAFE USE (as stated in the EC Type Examination Certificate SIRA 05ATEX2084X)
Conditions for IS-mAl Sounder
The equipment has an ingress protection rating of IP65. However, if it has been supplied without cable entry devices, then the user shall ensure that the devices that are fitted will provide an ingress protection that is appropriate to the environment in which it is installed i.e. IP20 or better. If only one of the two cable entries are used, then the unused entry ‘knockout’ shall be left intact or fitted with a blanking device that ensures ingress protection appropriate to the environment in which it is installed i.e. IP20 or better.
The total capacitance connected to terminals + wrt – (i.e. the capacitance of the cable plus any other capacitance) shall not exceed 83nF.
The enclosure is non-conducting and may generate an ignition-capable level of electrostatic charges under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions that might cause a build-up of electrostatic charges on non-conducting surfaces, additionally, cleaning of the equipment should be done only with a damp cloth.
The equipment shall only be supplied via Terminals + w.r.t.
Terminals – from a barrier having a maximum open circuit voltage So that is < 28V and a maximum short circuit current Io that is < 93 mA, where Io is restively limited. The barrier shall be ATEX certified by a notified body.
4.2 Zones, Gas Groups and Temperature Classification
The IS-mA1 mini alarm sounder has been certified Ex ia IIC T4. When connected to an approved system it may be installed in:
Zone 0 explosive gas air mixture continuously present.
Zone 1 explosive gas air mixture likely to occur in normal operation.
Zone 2 explosive gas air mixture not likely to occur, and if it does, it will only exist for a short time.
Be used with gases in groups:
Group A propane
Group B ethylene
Group C hydrogen
Having a temperature classification of:

T1 450ºC
T2 300ºC
T3 200ºC
T4 135ºC

4.3 Terminals + and –
Power is supplied to the sounder via the + and – terminals which have the following input safety parameters:
Ui = 28V
Ii = 93mA
Pi = 660mW
Ci = 0 Li = 0
The IS-mA1 sounder may be powered from an ATEX certified Zener barrier or galvanic isolator which have output parameters equal to or less than 28V, 93mA and 660mW, where Io is restively limited. The cable parameters stated on the selected Zener barrier or galvanic isolator certificate must be observed.
Up to three IS-mA1 sounders can be connected in parallel and powered from a common barrier or isolator. Connecting two sounders in parallel will reduce the output from each by about 3dB. Three sounders should only be powered from a common supply when the maximum supply voltage is available.
4.4 Terminals S2 and S3
When terminals S2 or S3 are connected to 0V (- terminal) the sounder output tone changes to the second or third stage alarm respectively. The input safety parameters for these terminals are:
Ui = 28V
Ii = 0mA
Because the permitted input current is zero, these terminals may only be connected to a diode return barrier, an intrinsically safe relay or a galvanic isolator, all of which must have been certified by an EC Notified Body. Only diode return barriers with a voltage drop of less than 0.9V may be used. Alternatively, these terminals may be connected directly to a mechanically activated switch within the hazardous area.
Tone Selection – To select the required first stage tone set the tone switches 1 to 6 (see Fig 2) to the tone setting shown in the table below. The table also shows which 2nd and 3rd stage tones are available for use with the selected first stage tone if more than one tone output stage is required.

Tone Number| Tone Description| Switch Settings
1 2 3 4 5 6| Second Stage Alarm| Third Stage alarm
---|---|---|---|---
Tone 1|  Continuous 340Hz| 0 0 0 0 0 0| Tone 2| Tone 5
Tone 2|  Alternating 800/1000Hz @ 0.25s intervals| 1 0 0 0 0 0| Tone 17| Tone 5
Tone 3|  Slow whoop 500/1200Hz @ 0.3Hz with 0.5s gap repeated| 0 1 0 0 0 0| Tone 2| Tone 5
Tone 4|  Sweeping 500/1000Hz @ 1Hz| 1 1 0 0 0 0| Tone 6| Tone 5
Tone 5|  Continuous 2400Hz| 0 0 1 0 0 0| Tone 3| Tone 20
Tone 6|  Sweeping 2400/2900Hz @ 7Hz| 1 0 1 0 0 0| Tone 7| Tone 5
Tone 7|  Sweeping 2400/2900Hz @ 1Hz| 0 1 1 0 0 0| Tone 10| Tone 5
Tone 8|  Siren 500/1200/500Hz @ 0.3Hz| 1 1 1 0 0 0| Tone 2| Tone 5
Tone 9|  Saw tooth 1200/500Hz @ 1Hz – D.I.N.| 0 0 0 1 0 0| Tone 15| Tone 2
Tone 10|  Alternating 2400/2900Hz @ 2Hz| 1 0 0 1 0 0| Tone 7| Tone 5
Tone 11|  Intermittent 1000Hz @ 1Hz| 0 1 0 1 0 0| Tone 2| Tone 5
Tone 12|  Alternating 800/1000Hz @ 0.875Hz| 1 1 0 1 0 0| Tone 4| Tone 5
Tone 13|  Intermittent 2400Hz @ 1Hz| 0 0 1 1 0 0| Tone 15| Tone 5
Tone 14|  Intermittent 800Hz 0.25s ON, 1s OFF| 1 0 1 1 0 0| Tone 4| Tone 5
Tone 15|  Continuous 800Hz| 0 1 1 1 0 0| Tone 2| Tone 5
Tone 16|  Intermittent 660Hz 150Ns ON, 150ms OFF| 1 1 1 1 0 0| Tone 18| Tone 5
Tone 17|  Alternating 544Hz (100ms) / 440Hz (400ms) – NFS 32-001| 0 0 0 0 1 0| Tone 2| Tone 27
Tone 18|  Intermittent 660Hz 1.8s ON, 1.8s OFF| 1 0 0 0 1 0| Tone 2| Tone 5
Tone 19|  Sweep 1400Hz to 1600Hz up 1s 1600Hz to 1400Hz down 0.5s| 0 1 0 0 1 0| Tone 2| Tone 5
Tone 20|  Continuous 660Hz| 1 1 0 0 1 0| Tone 2| Tone 5
Tone 21|  Alternating 554/440Hz @ 1Hz| 0 0 1 0 1 0| Tone 2| Tone 5
Tone 22|  Intermittent 544Hz @ 0.875Hz| 1 0 1 0 1 0| Tone 2| Tone 5
Tone 23|  Intermittent 800Hz @ 2Hz| 0 1 1 0 1 0| Tone 6| Tone 5
Tone 24|  Sweeping 800/1000Hz @ 50Hz| 1 1 1 0 1 0| Tone 29| Tone 5
Tone 25|  Sweeping 2400/2900Hz @ 50Hz| 0 0 0 1 1 0| Tone 29| Tone 5
Tone 26|  Simulated bell| 1 0 0 1 1 0| Tone 2| Tone 15
Tone 27|  Continuous 554Hz| 0 1 0 1 1 0| Tone 26| Tone 5
Tone 28|  Continuous 440Hz| 1 1 0 1 1 0| Tone 2| Tone 5
Tone 29|  Sweeping 800/1000Hz @ 7Hz| 0 0 1 1 1 0| Tone 7| Tone 5
Tone 30|  Continuous 300Hz| 1 0 1 1 1 0| Tone 2| Tone 5
Tone 31|  Sweeping 660/1200 @ 1Hz| 0 1 1 1 1 0| Tone 26| Tone 5
Tone 32|  Two Tone Chime| 1 1 1 1 1 0| Tone 26| Tone 15
Tone 33|   Intermittent 745Hz| 0 0 0 0 0 1| Tone 2| Tone 5
Tone 34|   Alternating 1000/2000Hz @ 0.5s – Singapore| 1 0 0 0 0 1| Tone 38| Tone 45
Tone 35|   420Hz @ 0.625s – Australian Alert| 0 1 0 0 0 1| Tone 36| Tone 5
Tone 36|   500-1200Hz 3.75s / 0.25s – Australian Evacuate| 1 1 0 0 0 1| Tone 35| Tone 5
Tone 37|   Continuous 1000Hz| 0 0 1 0 0 1| Tone 9| Tone 45
Tone 38|   Continuous 2000Hz| 1 0 1 0 0 1| Tone 34| Tone 45
Tone 39|   Intermittent 800Hz 0.25s ON 1s OFF| 0 1 1 0 0 1| Tone 23| Tone 17
Tone 40|   Alternating 544Hz (100ms) / 440Hz (400ms) – NFS 32-001| 1 1 1 0 0 1| Tone 31| Tone 27
Tone 41|   Motor Siren – Slow rise to 1200Hz| 0 0 0 1 0 1| Tone 2| Tone 5
Tone 42|   Motor Siren – Slow rise to 800Hz| 1 0 0 1 0 1| Tone 2| Tone 5
Tone 43|   Continuous 1200Hz| 0 1 0 1 0 1| Tone 2| Tone 5
Tone 44|   Motor Siren – Slow rise to 2400Hz| 1 1 0 1 0 1| Tone 2| Tone 5
Tone 45|   Intermittent 1000Hz 1s ON, 1s OFF| 0 0 1 1 0 1| Tone 38| Tone 34
Tone 46|   Saw tooth 1200/500Hz @ 1Hz – D.I.N. (PFEER P.T.A.P)| 1 0 1 1 0 1| Tone 47| Tone 37
Tone 47|   Intermittent 1000Hz 1s ON, 1s OFF – PFEER General Alarm| 0 1 1 1 0 1| Tone 46| Tone 37
Tone 48|   420Hz @ 0.625s – Australian Alert| 1 1 1 1 0 1| Tone 49| Tone 5
Tone 49|   500-1200Hz 3.75s / 0.25s – Australian Evacuate| 0 0 0 0 1 1| Tone 26| Tone 37

e2S IS mA1 Intrinsically Safe Round Sounder - Sounder
1 4.5 Other intrinsic safety certifications
Please contact European Safety Systems Ltd. for details of non-European intrinsic safety approvals.

Installation

IS-mA1 minialarm sounders should only be installed by trained competent personnel.
5.1 Mounting
The IS-mA1 minialarm sounder may be secured to any flat surface by inserting two mounting screws through the back of the round base (see figure 3). The enclosure provides IP65 protection and is suitable for installation in exterior locations provided that the area around the two mounting screws through the back of the base moulding has been sealed and that suitable cable glands with the required IP rating have been used.
5.2 Installation procedure
a. Unscrew the sounder unit security screw and remove the sounder section from the base by turning it anticlockwise.
Ensure that the ‘O’ ring seal remains in place.
b. Remove the required 20mm knockout section(s) depending on system wiring and mount the base to a flat surface by inserting two screws through the back of the base.
c. Fit the required number of 20mm cable glands or conduit entries into the base and connect the field wiring to the appropriate sounder terminals as shown in section 6 and fig 2 of this manual. The power supply terminals + and – are duplicated so that sounders may be connected in parallel, or an end of line monitoring resistor may be fitted.
d. Select the required output tone by positioning the six switches as shown in Table 1 and Fig 2.
e. Apply power to the sounder and adjust the internal volume control to provide the required sound level.
f. Check that the ‘O’ ring seal is correctly located on the sounder section (see Fig. 2) and insert the sounder section into the base. Push it fully home and turn it clockwise to align the mouldings before tightening the security screw.e2S IS mA1 Intrinsically Safe Round Sounder - Sounde
2

Electrical System Design For Installation In Hazardous Areas Using Zener

Barriers

6.1 Single stage alarm
If the control switch is in the positive supply, or the power supply is being turned on and off, only a single channel Zener barrier is required as shown in Fig 4. This circuit  may also be used if the sounder is being controlled by a mechanically activated switch on the hazardous area side of the barrier. e2S
IS mA1 Intrinsically Safe Round Sounder - Sounde 3If the control switch must be in the negative supply, the circuit shown in Fig 5 may be used. Any diode return barrier certified Ex ia by a EC Notified Body may be used, providing its voltage drop is less than 0.9V. e2S
IS mA1 Intrinsically Safe Round Sounder - Sounde 46.2 Multi-stage alarm
Connecting terminal S2 to 0V activates the second stage alarm, and similarly terminal S3 for the third stage alarm. Fig 6 shows how the diode return barriers may be used. If only two stages of alarm are required the third stage barrier should be omitted, the 28V 93mA barrier and the single diode return channel may then be contained in one package.e2S IS mA1 Intrinsically Safe
Round Sounder - Sounde 5 Electrical System Design For Installation In Hazardous Areas Using Galvanic Isolators
Galvanic violators do not require a high integrity earth connection. For small systems where a high integrity earth is not already available, the use of galvanic violators often reduces the overall installation cost and simplifies design.
7.1 Single stage alarm
The IS-mA1 minialarm sounder may be powered by any galvanic isolator having output parameters within the limits specified in section 4.3, which has been certified Ex ia by an EC Notified Body. The sounder may be controlled by turning the galvanic isolator on and off, or by a mechanically activated switch on the hazardous area side of the isolator.e2S IS mA1 Intrinsically
Safe Round Sounder - Sounde 6 7.2 Multi stage alarm
The IS-mA1 sounder second and third stages may be activated by using Galvanic ally Isolated Relays that have output parameters within the limits specified in section 4.4. which have been certified Ex ia by an EC Notified Body.e2S
IS mA1 Intrinsically Safe Round Sounder - Sounde 7

Cable Parameters

The maximum permitted cable parameters are as specified on the certificate of the Zener barrier or galvanic isolator that has been selected for the installation. Normally the limits are not restrictive, but care should be taken not to exceed a capacitive limit of 83nF for installations when very long cables are used.
Volume Control
The output level of the IS-mA1 sounder can be set by adjusting the volume control potentiometer (see Fig 2).

Maintenance

The sounder should be regularly inspected to ensure that it has not been damaged. Frequency of inspection depends upon environmental conditions, but initially we recommend that this should be done annually.
No attempt should be made to repair a faulty ISmA1 sounder. Suspect sounders must be returned to European Safety Systems Ltd. or to your local agent for repair.
Guarantee
Sounders that fail within the guarantee period should be returned to European safety Systems Ltd. It is helpful if a brief description of the fault symptoms is provided.
Customer Comments
European Safety Systems Ltd. is always pleased to receive comments from customers about our products and services. All communications are acknowledged and whenever possible, suggestions are implemented.

IECEx Approval

The IS-mA1 Sounder has also been approved to the IECEx scheme.
The installation requirements for IS-mA1 sounders approved to the IECEx scheme are the same as the installation requirements for IS-mA1 sounders approved to the ATEX directive.
Certificate No.
IECEx SIR 06.0045X
Marking:
Ex ia IIC T4 Ga (Ta = -40ºC to +60ºC)
Standards:
IEC 60079-0:2017
IEC 60079-11:2011
IEC 60079-26:2014-10
CONDITIONS OF CERTIFICATION (as stated on the IECEx Certificate of Conformity IECEx SIR 06.0045X)

  • The equipment has an ingress protection rating of IP65. However, if it has been supplied without a cable entry device, then the user shall ensure that the devices that are fitted will provide an ingress protection that is appropriate to the environment in which it is installed i.e. IP20 on better. If only one of the two cable entries are used, then the unused entry ‘knockout’ shall be left intact or fitted with a blanking device that ensues ingress protection appropriate to the environment in which it is installed i.e. IP20 or better.
  • The total capacitance connected to terminals + w.r.t. terminals – (i.e. the capacitance of the cable plus any other capacitance) shall not exceed 83nF.
  • The enclosure is non-conducting and may generate an ignition-capable level of electrostatic charges under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions that might cause a build-up of electrostatic charges on non-conducting surfaces, additionally, cleaning of the equipment should be done only with a damp cloth.
  • The equipment shall only be supplied via terminal + w.r.t. terminal – from a barrier having a maximum open circuit voltage Uo that is ≤ 28V and a maximum short circuit current Io that is ≤ 93mA, where Io is restively limited.

The IS-mA1 sounders are marked with the certification requirements for the ATEX and IECEx and approvals.
IS-mA1 Sounder
II 1G Ex ia IIC T4 Ga (-40ºC <=Ta<= +60°C)
Ui = 28V Ii = 93mA Pi = 660mW Ci = 0 Li = 0 Terminal + w.r.t. Terminal Ui = 28V Ii = 0mA
Terminals S2&S3 w.r.t. Terminal – Year / Serial No. 09 / 1MA000001
2813
VdS
EN54-3
Type B
0786-CPD-20338
SIRA 05ATEX2084X
IECEx SIR 06.0045X
WARNING: TO AVOID A POSSIBLE ELECTROSTATIC CHARGE ONLY CLEAN WITH A DAMP CLOTH
e2S
european safety systems ltd.
London W3 7QH UK
www.e2s.com
UKEX Approval
The IS-mA1 Sounder has also been approved to the UKEX scheme.
The installation requirements for IS-mA1 sounders approved to the UKEX scheme are the same as the installation requirements for IS-mA1 sounders approved to the ATEX directive.
Certificate No. CSAE 21UKEX2553X
Marking:
Ex ia IIC T4 Ga (Ta = -40ºC to +60ºC)
Standards: EN IEC 60079-0:2018
EN 60079-11:2012
EN 60079-26:2014
The IS-mA1 sounders are marked with the certification requirements for the UKEX approval.

e2S IS mA1 Intrinsically Safe Round Sounder - UKEX
approvalwww.e2s.com

FM Approval
The IS-mA1 Sounder has also been FM Listed.
Marking: IS Class I, Zone 0, AEx ia IIC T4 IS Class I, Division 1, Groups A, B, C, D See the Control Drawings D 5035 Sheets 1 and 2 for installation details and entity parameters.
IS-mA1 Sounder
FM
APPROVED
IS Class l, Division 1, Groups A, B, C, D
IS Class I, Zone 0, AEx ia IIC T4 (-40ºC <=Ta<= +60°C)
Control Drawing D 5035
Year / Serial No. 09 / 1MA000001
WARNINGS: Substitution of components may impair safety To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing TO AVOID A POSSIBLE ELECTROSTATIC CHARGE ONLY CLEAN WITH A DAMP CLOTH
e2S european safety systems ltd.
London W3 7QH UK
www.e2s.com
CPD Directive 89/106/EEC
The IS-mA1 Sounder is compliant with the requirements of the Construction Products Directive 89/106/EEC.
EN54-3
Type B
IP65
Voltage Range 18 – 28V DC via a safety barrier (see sections 6 and 7).

Tone Description
2 800/1000Hz @ 0.25 Seconds Alternating
3 500/1200Hz @ 0.3Hz 0.5 Sec Gap  Slow Whoop
9 1200/500Hz @ 1Hz DIN
15 800Hz Continuous
16 660Hz 150mS ON 150ms OFF
17 554Hz (100mS) / 440Hz (400mS)  NF S 32-001

The tones listed have been tested to EN54-3 and are compliant with the Construction Products Directive 89/106/EEC.
EN54-3 Test data document D5073

e2S IS mA1 Intrinsically Safe Round Sounder - Sounde8e2S IS mA1 Intrinsically Safe Round Sounder -
Sounde9

EU Declaration of Conformity

Manufacturer:| European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
---|---
Authorised Representative:| E2S Warnsignaltechnik UG
Charlottenstrasse 45-51
72764 Reutlingen
Germany
Equipment Type:| IS-mA1, IS-mA2, IS-mA3, IS-mB1, IS-mC1, IS-mA1M

Directive 2014/34/EU: Equipment and Protective Systems for use in Potentially Explosive Atmospheres (ATEX)

Notified Body for EU type Examination (Module B):| Sira Certification Service
Notified Body No.: 2813
CSA Group Netherlands B.V, Utrechtseweg 310, 6812 AR, Arnhem, Netherlands
---|---
EU-type Examination Certificate (Module B):| SIRA 05ATEX2084X
Notified Body for Quality Assurance Notification / Conformity to EU-type based on quality assurance of the production process (Module D):| Sira Certification Service
Notified Body No.: 2813
CSA Group Netherlands B.V, Utrechtseweg 310, 6812 AR, Arnhem, Netherlands
Quality Assurance Notification (Module D):| SIRA 05 ATEX M342
Provisions fulfilled by the equipment:| II 1 G Ex ia IIC T4 Ga (-40 °C ≤ Ta ≤ +60 °C) or
I M1 Ex ia I Ma (-40 °C ≤ Ta ≤ +60 °C)
Standards applied:| EN IEC 60079-0:2018
EN 60079-11:2012
IEC 60079-26:2014

Regulation EU No. 305/2011: Construction Products Regulation (CPR) – IS-mA1 (tones 2, 3, 9, 15, 16, 17) only

 Notified Product Certification Body for Certificate of Constancy of
Performance or EC Type Examination Certificate and continuous
surveillance, assessment and evaluation of factory production control:| VdS Schadensverhütung GmbH
Notified Body No.: 0786
Amsterdamer Str 172-174, 50735 Köln, Germany
---|---
Certificate of Constancy of Performance or EC Type Examination
Certificate:| 0786-CPD-20338
Standards applied:| EN 54-3:2001 + A1:2002 + A2:2006

Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:

  • EN 61000-6-1:2007
  • EN 61000-6-2:2005
  • EN 61000-6-3:2007 / A1:2011 / AC: 2012
  • EN 61000-6-4:2007 / A1: 2011

Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS)
The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment, including amendment by Directive 2015/863/EU.
Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
The product and all the components contained within it are free from substances of very high concern.
Other Standards and Regulations
EN 60529:1992+A2: 2013 – Degrees of protection provided by enclosures (IP code) – enclosure rated IP65
EU Declaration of Conformity
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.
UKCA Declaration of Conformity
Manufacturer:
European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
Equipment Type:
IS-mA1, IS-mA2, IS-mA3, IS-mB1, IS-mC1, IS-mA1M
Directive UKSI 2016:1107 (as amended by UKSI 2019:696) – Schedule 3A, Part 1 : Product or Protective System Intended for use in Potentially Explosive Atmospheres (UKCA)

Notified Body for UK type Examination (Module B):| Sira Certification Service
Notified Body No.: 0518
Rake Lane, Ecclesiastes, Chester CH4 9JN, UK
---|---
UK-type Examination Certificate (Module B):| CSAE 21UKEX2553X
Notified Body for Quality Assurance Notification / Conformity to EU-type
based on quality assurance of the production process (Module D):| Sira Certification Service
Notified Body No.: 0518
Rake Lane, Ecclesiastes, Chester CH4 9JN, UK
Quality Assurance Notification (Module D):| CSAE 22UKQAN0046
Provisions fulfilled by the equipment:| II 1 G Ex ia IIC T4 Ga (-40 °C ≤ Ta ≤ +60 °C) or I M1 Ex ia I Ma (-40 °C ≤ Ta ≤ +60 °C)
Standards applied:| EN IEC 60079-0:2018
EN 60079-11:2012
IEC 60079-26:2014

Regulation EU No. 305/2011: Construction Products Regulation (CPR) – IS-mA1 (tones 2, 3, 9, 15, 16, 17) only

Notified Product Certification Body for Certificate of Constancy of
Performance or EC Type Examination Certificate and continuous
surveillance, assessment and evaluation of factory production control:| VdS Schadenfreude GmbH
Notified Body No.: 0786
Amsterdam-er Str 172-174, 50735 Köln, Germany
---|---
Certificate of Constancy of Performance or EC Type Examination Certificate:| 0786-CPD-20338
Standards applied:| EN 54-3:2001 + A1:2002 + A2:2006

Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000-6-1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007 / A1:2011 / AC: 2012
EN 61000-6-4:2007 / A1: 2011
Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS)
The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment, including amendment by Directive 2015/863/EU.
Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
The product and all the components contained within it are free from substances of very high concern.
Other Standards and Regulations
EN 60529:1992+A2: 2013 – Degrees of protection provided by enclosures (IP code) – enclosure rated IP65
UKCA Declaration of Conformity
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.

Document No.: DC-088_Issue_A
Date and Place of Issue: London, 04/02/2022
E2S Telephone: +44 (0)20 8743 8880
Fax: +44 (0)20 8740 4200
Email: sales@e2s.com
www.e2s.com
DC-088_Issue_A (IS-Mini) – Page 2 of 2 – QAF_252_Issue_5

Documents / Resources