HITACHI PC-ARC-E Eco Compact Wired Remote Controller Instruction Manual
- May 15, 2024
- Hitachi
Table of Contents
INSTALLATION & OPERATION MANUAL
ECO COMPACT
WIRED REMOTE CONTROLLER
MODELS
PC-ARC-E
Cooling & Heating
PMEN0630 rev.0 – 03/2023
PC-ARC-E Eco Compact Wired Remote Controller
Specifications in this manual are subject to change without notice in order
that Hitachi may bring the latest innovations to their customers. Whilst every
effort is made to ensure that all specifications are correct, printing errors
are beyond Hitachi’s control; Hitachi cannot be held responsible for these
errors.
The English version is the original one; other languages are translated from
English. Should any discrepancy occur between the English and the translated
versions, the English version shall prevail.
General information
1.1 Safety summary
Hitachi cannot anticipate every possible circumstance that might involve a
potential hazard.
Wired Remote Controller can be connected to any indoor unit that corresponds
to H-LINK II.
The indoor units are wired ausing twisted pair cable. Ensure that the total
length of the wire is shorter than 500m.
DANGER
- DO NOT pour water into the remote controller. This product is equipped with electrical parts. If poured, it will cause a serious electrical shock.
- DO NOT perform installation work and electrical wiring connection by yourself. Contact your Hitachi distributor or dealer and ask them for installation work and electrical wiring by service person.
CAUTION
-
DO NOT install the indoor unit, outdoor unit, controller and cable at such places as;
» Where there is oil vapour and the oil is dispersed.
» Where the hot springs are near (in a sulfuric environment).
» Where generation, flowing, staying or leaking of flammable gas is detected.
» Where the sea is near (in the salty environment).
» An acid or alkaline environment. -
DO NOT install the indoor unit, outdoor unit, controller and cable within approximately 3 meters from strong electro magnetic wave radiators such as medical equipment. In case that the controller is installed in a place where there is electromagnetic wave radiation, shield the controller and cables by covering with the steel box and running the cable through the metal conduit tube.
-
In case that there is electric noise at the power source for the indoor unit, provide a noise filter.
-
Use specified cables to connect between indoor unit and remote control switch. Selecting incorrect cables may lead to fire or electrical shock.
NOTE
-
The installer and system specialist shall comply with local regulations or standards for the safety.
The following standards may be applicable, if local regulations are not available. International Organization for Standardization, ISO 5149 or European Standard, EN 378 or Japan Standard, KHKS0010. -
Perform electrical work according to the Installation Manual. As for the electrical wiring work and check, turn OFF the main power supply before opening/closing the service cover of indoor unit. If service cover is opened with main power supply left on, it may result in an electrical shock.
-
It is assumed that this control remote will be operated and serviced by English speaking people.
If this is not the case, the customer should add safety such as operating signs in the native language for non English speakers. -
This manual should be considered as a permanent part of the air conditioning equipment and should remain with the air conditioning equipment.
-
This appliance must be used only by adult and capable people, having received the technical information or instructions to handle this appliance properly and safely.
-
Children should be supervised to ensure that they do not play with the appliance.
-
Important: read and understand this manual before using this remote controller.
If you have any questions, contact your Hitachi distributor or dealer.
1.2 Button names and functions
The figure below shows all the indications for reference. The actual display
during operation is different.
NOTE
- The backlight turns off 30 s after the last operation. If you press any button, the backlight is turned on. (When one button is pressed to activate the backlight, the related function of the button will be applied.)
- Make sure to press the buttons lightly with your fingertips.
- Do NOT press the buttons or anything with sharp points, such as a ball point pen. This may damage the controller.
Specifications
2.1 Indoor unit group control
For indoor unit group control, one PC-ARC-E can control up to 16 indoor units.
Up to 2 PC-ARC-E can be connected to the same indoor unit group.
2.2 Hardware specification
Item | Specification |
---|---|
Power supply | Powered by indoor unit, 15VDC ± 10% |
Dimensions | W 90mm × H 90mm × D15.5mm (thinnest part) |
W 90mm × H 90mm × D18.5mm (thickest part)
Weight| 100g (Approx.)
Installation Method| Installed on the wall or switch box
Installation Condition| Indoor
Temperature Condition| 0-40°C
Humidity Condition| 35 – 90% (non condensation)
2.3 Communication specification
Item | Specification |
---|---|
Communication Object | Indoor unit |
Communication Line | Non-polar 2-wire |
Communication Method | Half-duplex transmission |
Synchronization Method | Asynchronous |
Communication Speed | 9600bps |
Wiring Distance | 500m (total lenght) ▲ Use twist pair cable |
Number of Connectable Units | Up to 16 indoor units (with the same wired remote |
controller)
Operation
3.1 Icon description
The status of the remote controller is displayed on the home screen.
NOTE
- Some of the status icons below may not be displayed depending on the type of outdoor unit or indoor unit you are using.
Icon | Description |
---|---|
It is time to clean the air filter. | |
During the defrosting operation, the defrosting light turns on and the |
indoor fan stops.
When the defrosting process starts, the run indicator goes out until the
defrosting process is finished.
Then the run indicator comes on again.
| When setback operation is enabled and the card key is removed (when no one
is present). (1)
| The compressor cannot be operated because it is preheating.
| An alarm is in progress.
| The operation lock is set.
| Displayed when using the central controller. Operation from this wired
controller may be limited.
| Indicates the service function is performed.
SET| Displays the setting temperature.
| Displays the room temperature. (2)
| The operation is stopped.
MAIN| This is the main remote controller setting.
Use the main remote controller to set the main capacity control setting.
In the case of a single unit, the main does not light up.
| In communication with the indoor unit.
| The on timer is set.
| The off timer is set.
| “GentleCool Comfort” mode is ON.
The icon switches as “GentleCool Comfort Level” changes: Low= , Med= , High=
| “Power Saving” mode is ON.
The icon switches as “Power Saving Level” changes: Low= , Med= , High=
| “Sleep Mode” is ON.
| “AutoBoost” mode is ON.
| “On Timer” is set in the operation schedule.
| “Off Timer” is set in the operation schedule.
| NFC mode is ON.
| NFC mode is OFF.
NOTE
-
(*1): The default setting is cooling: set temperature +2.5°C, heating: set temperature -2.5°C.
If you want to change the correction value for this setback operation, please refer to the “Optional setting items for function selection”. -
(*2): It depends on the settings of the remote controller, please refer to the “Optional setting items for function selection”.
3.2 Operation start/stop
Press “ ” (run/stop). The run indicator will be turned on/off and the
operation will be started or stopped accordingly.
Operation start
Operation stop
NOTE
- When heating operation stops, indoor unit(s) may keep running in Fan mode for about 2 minutes.
3.3 Operation mode
Operation mode setting
- Home screen is displayed.
- Press “ ” to select “Mode”. The operation mode is switched in the following order:
The operation mode can be limited by some optional function settings or by the “5.3.1 Operation Lock/Unlock setting”.
NOTE
- The “b8” function selection setting is required for “Auto” operation. By default, “Auto” mode is not available, as “b8” factory setting is “00”.
- “Dry” mode may not be available depending on the type of indoor unit.
3.4 Temperature setting
-
Home screen is displayed.
-
By pressing “ ”, the temperature is increased by 0.5 or 1°C step to a maximum of 30°C.
By pressing “ ”, the temperature is decreased by 0.5 or 1°C step. -
Cooling, Dry, Fan operation: a minimum of 19°C.
-
Heating operation: a minimum of 17°C.
NOTE
- Depending on the type and setting of the indoor unit, it may not be possible to set the temperature by 0.5°C. In such case, the default temperature step is 1°C.
- The unit of setting temperature can be set in “Temperature Unit Setting” of the “Function Selection” mode.
- The maximum/ minimum temperature may differ depending on the type of indoor unit.
- Minimum and maximum temperature set-point limits can be configured by selecting a cooling lower limit and heating upper limit in the “Function Selection” mode.
- When the “Automatic Reset of Setting Temperature” function is selected, the temperature is automatically returned to the preset temperature after the temperature set-point change.
- Contact your distributor for detailed information about “Automatic Reset of Setting Temperature” and “Cooling Lower Limit Value and Heating Upper Limit Value for Setting Temperature” functions.
3.5 Fan speed
- Home screen is displayed.
- Press “ ” to set “Fan Speed”. The fan speed changes as below depending on the indoor unit type.
NOTE
- Some of the fan speed settings as “High2” or “Auto” may not be available depending on the indoor unit type.
- Once the Temperature and Fan Speed settings are set, the setting status is stored and does not need to be reset.
3.6 Swing louver direction
- Press “ ” (On/Off). Make sure that the power is ON.
- Press “ ” and select “Louver Direction”.
- By pressing “ ” or “ ”, the louver direction changes as below diagram, and the direction of different types of louver is displayed differently. : Auto swing operation will be started. At this time, the louver icon on the LCD will keep swinging repeatedly.
- Press “ ” to save the setting and return to the home screen.
NOTE
- For the indoor unit without the auto louver mechanism, the indication of “Louver” is NOT displayed on the LCD.
- The air flow angle is different for each indoor unit type. Check for detailed information in the technical information of indoor unit.
- The louver position on the LCD and the actual louver position may not match during the Auto-Swing. To set the louver positions, set the angle after checking the position on the LCD.
- The louver may NOT stop immediately after the switch is pressed.
Advanced functions settings
NOTE
- If some functions are not supported on the indoor unit, the relevant setting will be skipped automatically.
- If schedule timer is not set, “Operation Schedule Setting” screen is not available, please refer to the Operation Schedule Details Setting.
4.1 Clock setting
This function is to set the date and time.
NOTE
-
The clock accuracy is within ±70 seconds each month. It is recommended to set the clock to the current time on regular basis.
-
The clock can run for 72 hours even if the electricity is cut off.
If the power failure lasts for more than 72 hours, or the clock has been powered down for a long time, please set the clock again. -
If the clock is set on the main wired remote controller, the sub controller of the same refrigerant system will be also set to the same time.
The clock can be also set on the sub wired remote controller. After the sub controller is changed for more than 2 minutes, the main controller will be set to the same time.
Main and sub controller can be distinguished on the home screen. For the main wired remote controller, “MAIN” is displayed on the screen.
-
Press “ ” and “ ” at the same time for 3 seconds to display the clock setting screen.
-
Set the clock in order of “Year” ↔ “Month” ↔ “Day” ↔ “Hour” ↔ “Minute”.
✓ Press “ ” or “ ” to change the settings of selected item, and press “ ” to switch to the next item.
“Year” setting “Minute” setting -
After “Minute” is set, press “ ” to return to the home screen.
-
To end the operation during the setup, press “ ” to return to the home screen.
4.2 Function menu
4.2.1 Access to the function menu
- Each time the “Menu” button “ ” is pressed, the menu screen changes as below.
No.| Item
---|---
1| Louver
2| On/Off Timer
3| Comfort Setting
4| Capacity Control On/Off
5| Sleep Mode On/Off
6| AutoBoost On/Off
7| Operation Schedule On/Off
NOTE
Icons are displayed alternatively, starting by the Louver icon 1 or the Weekly
Timer 2, depending on the indoor unit model and the available functions for
this unit.
Use the “Menu” button “ ” to navigate through the available options.
- Press “ ” or “ ” to modify the value of the selected function.
NOTE
Some functions can be activated from this menu, whereas their detailled
settings shall be done from the “4.3 Detailed menu operation”.
4.2.2 Louver setting
NOTE
Refer to chapter 4.4 for details.
4.2.3 Simple (On/Off) timer
This function is used to start or stop the unit operation at the set time.
NOTE
- If clock has not been set, it is not possible to set the simple timer or the weekly timer. Please set the clock in a first step, if these functions have to be used.
- When the wired remote controller is stopped, only “On Timer” can be set. And when the wired remote controller is ON, only “Off Timer” is available.
- Do not set the same time for both ON/OFF timers.
- After the set time is reached, the simple timer settings are cancelled.
- “Off Timer” setting will be automatically cancelled if the “Run/stop” button “ ” is pressed to stop the operation of the unit manually.
◆ Set the simple timer
- Select “Simple Timer Setting” on the menu screen.
- Press “ ” or “ ” to select the setting item:
✓ When the wired remote controller is ON, set the “Off Timer”. ✓ When the wired remote controller is OFF, set the “On Timer”. ✓ The timer can be set from 0.5 to 23 hours.
✓ Press “ ” or “ ” to increase or decrease 30 minutes of each step for 0.5 to 9.5 hours, 1 hour of each step for 10 to 23 hours.
3 Press “ ” to save the setting and return to the home screen.
✓ When “On Timer” is set,“ ” is displayed on the home screen.
✓ When “Off Timer” is set,“ ” is displayed on the home screen.
4.2.4 Comfort setting
This function is used to control the discharge air temperature when the system
is operating in cooling mode.
NOTE
- This function cannot be set when the indoor unit does not support this function.
- According to the selected setting between LOW/MED/HIGH, the system will apply a determined air outlet target temperature value in order to prevent air flow from being too cold.
- The Gentlecool function may not be enough if two or more units are operating in the same room.
- This function is somehow limiting the cooling capacity of the indoor units. Hence, once activated, it may take time to cool down the entire room or system.
◆ Set the GentleCool comfort ON/OFF
- Select “GentleCool Comfort Setting” on the menu screen.
- Press “ ” or “ ” to switch the mode between ON and OFF.
- Press “ ” to save the setting and return to the home screen.
When “GentleCool Comfort” mode is ON, “ ” is displayed on the home screen. The “ ” icon switches as “GentleCool Comfort Level” changes.
Capacity Control Level | Icon |
---|---|
Low | |
Med | |
High |
NOTE
Refer to the detailed settings for more information.
4.2.5 Power saving setting
This function can be activated to reduce the power consumption of the air
conditioning system.
Use the “Capacity Control On/Off” function from the “Function Menu” to
activate or deactivate this function.
Use the detailed function menu to set the level of power saving, from the
“Capacity Control Details setting”‘.
NOTE
This function is not available if the indoor unit and outdoor unit do not
support this function.
◆ Set the power saving
- Select “Power Saving On/Off” on the menu screen.
- Press “ ” or “ ” to switch the Power Saving between ON and OFF.
- Press “ ” to save the setting and return to the home screen.
- Refer to the detailed function menu to set the level of power saving if necessary.
4.3 Detailed menu operation
- From home screen and IU “OFF”, press “ ” for 3 seconds to display the detailed menu screen.
- Press “ ” or “ ” to switch the item number:
Item No.| Description
---|---
| Run Indicator Setting
| Capacity Control Details Setting
| GentleCool Comfort Details Setting
| Sleep Mode Details Setting
| Operation Sound Setting
| IR Receiver Setting
- Press “ ” after selecting the desired item number and the set value of the selected item starts to flash.
- Press “ ” or “ ” to modify the set value.
- Press “ ” to save the setting. Once done, the item number starts flashing again.
- Press “ ” (On/Off) once, or press “ ” for 3 seconds to return to the home screen.
4.3.1 Run indicator setting
This function is used to activate or deactivate the run indicator.
NOTE
When this function is deactivated, the operation indicator cannot light up
during operation.
-
Enter “Run Indicator Setting” by selecting “01” as the item number, refer to “4.3 Detailed menu operation”.
-
Press “ ” or “ ” to switch the set value between “00” and “01” to activate or deactivate the run indicator.
Set Value| Description
---|---
| Run Indicator is deactivated
| Run Indicator is activated (default setting) -
Press “ ” to save the setting. Once done, the item number starts flashing again.
-
Press “ ” (On/Off) once, or press “ ” for 3 seconds to return to the home screen.
NOTE
This process is only valid when the item number is blinking.
4.3.2 Capacity control details setting
This function is used to set “Capacity Control Level”, e.g.the intensity
level of the power saving function.
NOTE
- This function cannot be set when the indoor unit and outdoor unit do not support this function.
- Refer to “Power Saving On/Off”.
-
Enter “Capacity Control Details Setting” by selecting “02” as the item number.
-
Press “ ” or “ ” to switch the set value “00 ↔01↔02” to set the ”Capacity Control Level”.
Set Value| Description
---|---
| Capacity Control Level is Low
| Capacity Control Level is Med
| Capacity Control Level is High -
Press “ ” to save the setting and the item number “02” starts to flash.
-
Press “ ” (On/Off) once, or press “ ” for 3 seconds to return to the home screen.
When “Capacity Control” mode is ON, “ ” is displayed on the home screen. The “ ” icon switches as “Capacity Control Level” changes.
Capacity Control Level | Icon |
---|---|
Low | |
Med | |
High |
4.3.3 GentleCool comfort details setting
This function is used to set “GentleCool Comfort Level”.
NOTE
- This function cannot be set when the indoor unit does not support this function.
- Refer to “Set the GentleCool comfort ON/OFF”.
- Enter “GentleCool Comfort Details Setting” by selecting “03” as the item number.
- Press “ ” or “ ” to switch the set value “00 ↔01↔02” to set the ”GentleCool Comfort Level”. 3 Press “ ” to save the setting and the item number “03” starts to flash.
4 Press “ ” (On/Off) once, or press “ ” for 3 seconds to return to the home screen.
When “GentleCool Comfort” mode is ON, “ ” is displayed on the home screen. The “ ” icon switches as “GentleCool Comfort Level” changes.
4.3.4 Operation sound setting
This function is used to set the operation sound ON/OFF.
- Enter “Operation Sound Setting” by selecting “05” as the item number.
- Press “ ” or “ ” to switch the set value between “00 ↔01” to set the ”Operation Sound” ON/OFF.
Set Value| Description
---|---
| Operation sound is OFF
| Operation sound is ON
- Press “ ” to save the setting and the item number “05” starts to flash.
- Press “ ” (On/Off) once, or press “ ” for 3 seconds to return to the home screen.
4.3.5 Set the “IR Receiver” ON/OFF
- Enter “IR Receiver Setting” by selecting “06” as the item number.
- Press “ ” or “ ” to switch the set value between “00 ↔ 01” to set the ”IR Receiver” ON/OFF.
- Press “ ” to save the setting and the item number “06” starts to flash.
- Press “ ” (On/Off) once, or press “ ” for 3 seconds to return to the home screen.
4.4 Individual louver operation
This function is to individually set the air direction of multiple air
outlets.
NOTE
- This function is available when the indoor unit supports individual louvers.
- It cannot be set while the air conditioner is stopped.
- The fan speed changes to “LOW” while this function is being set. After the setting is completed, the unit operation is back to normal.
- As for “Start-up of Heating Operation”, “During Defrost Operation” and “Activation of Thermo- Controller”, all the louver angles are automatically secured horizontally when this function is activated.
- This function is not available if two remote controllers (including a combination of wired controller + wireless controller) are used.
4.4.1 Individual louver setting
-
Press “ ” for 3 seconds to start the setting.
NOTE
If there is only one indoor unit connected with the wired remote controller, Step 5 is displayed. -
Indoor unit selecting screen is displayed.
✓ Each indoor unit has its own index number, the corresponding refrigerant number and indoor unit address are displayed at the upper right corner of the screen. -
Press “ ” or “ ” to select the indoor unit by changing the index number.
-
Press “ ” to confirm the selection.
NOTE
To select all the indoor units managed by this remote controller, set the “Index number” as “FF” and confirm the selection.
Individual louver setting screen is displayed. -
Press “ ” to select the individual louver.
-
Press “ ” to select the louver angle.
-
Press “ ” to save the setting and return to the home screen.
The louver angle is changed as follows. -
Press “ ” (On/Off) once, or press “ ” for 3 seconds to end the operation during the setup and return to the home screen.
4.4.2 Cancel individual louver setting
- Press “ ” to select the louver angle and set the louver to “ ”.
- Press “ ” to save the setting and return to the home screen.
4.5 Sleep mode setting
This function is used to get the air conditioner operation sleep-friendly.
- When the sleep mode starts, “Off Timer” will be set.
- After the sleep mode operates for a period of time, the set temperature will change according to the selected operating mode, as indicated in the table below.
| After 1 hour (1)| After 2 hours| After more than 2 hours
---|---|---|---
Cool Mode| Increase 1°C (2)| Increase 1°C again (2)| Not change
Heat Mode| Decrease 2°C (3)| Decrease 2°C again (*3)
Other Modes| | The setting temperature will not change|
(1). After an hour or when the room temperature reaches the setting
temperature for the first time.
(2). For Cool Mode, the upper limit of the setting temperatura is 28°C.
(*3). For Heat Mode, the lower limit of the setting temperature is 20°C.
NOTES
- If clock has not been set, the On/Off setting will be skipped automatically.
- “Off Timer” is set at 8 hours as default. It can be changed from “Sleep Mode Details Setting”, refer to “4.3 Detailed menu operation”.
4.5.1 Set the sleep mode ON/OFF
- Select “Sleep Mode Setting”, refer to “Menu Operation”.
- Press “ ” or “ ” to switch the sleep mode between ON and OFF.
- Press “ ” to save the setting and return to the home screen.
When the sleep mode is ON, “ ” is displayed on the home screen.
4.5.2 Sleep mode details setting
This function is used to set “Off Timer” in the sleep mode.
NOTE
- The default value of “Off Timer” is 8 hours.
- Refer to “4.5.1 Set the sleep mode ON/OFF”.
- Enter “Sleep Mode Details Setting” by selecting “04” as the item number.
- Press “ ” or “ ” to increase or decrease 30 minutes of each step for 3.0 to 8.0 hours.
- Press “ ” to save the setting and the item number “02” starts to flash.
- Press “ ” (On/Off) once, or press “ ” for 3 seconds to return to the home screen.
4.6 Autoboost setting
This function increases the cooling or the heating capacity for 30 minutes
since the beginning of operation, in order to reach the setting temperature in
the room as quickly as possible. It is only available when the operation mode
is cooling or heating. This function makes operation begin with “Autoboost”
option every time ON operation is set, until this function is deactivated
(Autoboost setting = “Not Set”).
NOTE
- Autoboost cannot be set when the outdoor unit does not support this function.
- Autoboost cannot be used if Power Savings is not supported.
- When quick function is activated while mode is “Cool”, fan speed changes and is locked as “Auto” for 30 minutes at the longest regardless of the current setting. While in this operation (fan speed “Auto”), fan level may drop as low as “Low” when the room temperature gets close to the setting temperature. The operation starts regardless of the fan speed.
- The wired remote controller only supports the function of “Quick + Heat” in the AutoBoost mode.
4.6.1 Set the autoboost
- Select “AutoBoost Setting” on the menu screen.
- Press “ ” or “ ” to switch AutoBoost mode between ON and OFF.
- Press “ ” to save the setting and return to the home screen.
When the AutoBoost mode is ON, “ ” is displayed on the home screen.
4.7 Operation schedule setting
This function is used to start or stop the unit operation at the set time.
NOTE
- Scheduled operation (stop) is not possible when the remote control is prohibited.
- If current time is not set, scheduled operation (stop) is not available. Refer to “4.1 Clock setting” to set the date and time.
- Schedule timer can be changed from “Operation Schedule Details Setting”.
4.7.1 Set the operation schedule ON/OFF
- Select “Operation Schedule” on the menu screen.
- Press “ ” or “ ” to switch the operation schedule between ON and OFF.
- Press “ ” to save the setting and return to the home screen.
- When the “Operation Schedule” is ON, “ ”, “ ”, or “ ” can be displayed on the home screen based on the timer setting in scheduled operation.
When the “Operation Schedule” is OFF, this function is turned off and no operation schedule icons are displayed on the home screen.
4.7.2 Operation schedule details setting
This function is set the schedule timer (“On Timer” and “Off Timer”) and the
weekly schedule.
-
Press “ ” and “ ” at the same time for 3 seconds to display the operation schedule details setting screen.
✓ If current time is not set, the clock setting screen will appear instead. -
Press “ ” or “ ” to set the time, and press “ ” to switch between “Hour” and “Minute”.
-
Press “ ” to save the setting and skip to the “Off Timer” screen.
✓ Press “ ” (On/Off) to cancel the setting of “On Timer” and skip to the “Off Timer” screen.
The previous settings of “On Timer” are invalid. -
Press “ ” or “ ” to set the time, and press “ ” to switch between “Hour” and “Minute”.
-
Press “ ” to save the setting.
✓ Press “ ” (On/Off) to cancel the setting of “Off Timer” and skip to the weekly schedule screen. The previous settings of “Off Timer” are invalid.
✓ When both “On Timer” and “Off Timer” are not set, the wired remote controller returns to the home screen. -
Press “ ” to select the day(s) into the schedule or press “ ” to remove the day(s) from the schedule.
-
Press “ ” to save the setting and return to the home screen.
4.8 IR receiver setting
The wired remote control PC-ARC-E has a built-in “IR Receiver” which can
receive commands from the wireless remote controller (sold separately, model:
PC-AWR).
Setting temperature, operation mode, etc. it’s possible from the wireless
remote controller by pointing to the wired remote controller.
This function is only available when the IR receiver function is set at ON and
the default setting of “IR Receiver” is ON.
4.8.1 Send commands from wireless remote controller
After the transmitter of the wireless remote controller is directed to the
wired remote controller, press the buttons to send commands.
- When the commands are sent, the indication “ ” on the LCD of wireless remote controller flashes once.
- When the “IR Receiver” receives the commands, the buzzer sounds.
NOTE
- The IR receiver function can only be used on the home screen.
- The wired remote controller does not support “Differentiate Indoor Units Set Close Together” at the wireless remote controller.
- The wired remote controller does not support “Test Run” at the wireless remote controller.
- When the wireless remote controller is in OFF status, even if the Operation Mode, Fan Speed, or Temperature Setting is changed on the wireless remote controller, the settings on the compact remote controller will not be changed because no signal is sent.
4.9 Filter reminder reset setting
This function is used to turn off the filter reminder indication and to reset
the time of use for the filter.
The “ ” icon will be displayed on the home screen when the time of use for the
air filter has been elapsed.
- Clean the air filter according to the indoor unit.
- Press “ ” for 3 seconds to reset the filter reminder time.
After Filter Reminder Reset is completed, “ ” icon will disappear from the home screen.
Service & Installation menu
5.1 Test run
-
Press “ ” and “ ” simultaneously for 3 seconds to display the test run screen of Operation Stop state.
-
Press “ ” to switch mode and press “ ” to switch fan speed.
-
Press “ ” to enter into the test run screen of Operation Start state.
-
Press “ ” to switch mode and press “ ” to switch fan speed, and press “ ” or “ ” to set the test run time.
✓ The setting time range is from 30 minutes to 600 minutes.
✓ Press “ ” or “ ” can adjust the test run time by 30 minutes with each single press. -
Press “ ” to end the test run and return to home screen.
NOTE
- When a test run request is made from the outdoor unit or central controller, the screen automatically turns to test run screen.
- After transition to the test run screen, the operation mode and fan speed will remain the same state before the test run setting.
- In the case of two wired remote controllers, only the primary one can change the test run time.
5.2 Function selection
-
Press “ ” for 3 seconds to display the function selection setting screen.
✓ If only one indoor unit is connected with the wired remote controller, step4 is displayed.
✓ If multiple indoor units are connected with the wired remote controller, step2 is displayed. -
Indoor unit selecting screen is displayed.
✓ Each indoor unit has its own index number. The corresponding refrigerant system number and address number are displayed on the upper right corner of the screen. -
Press “ ” or “ ” to select the indoor unit by changing the “Index number”. Then press “ ” to confirm the selection.
✓ If all the indoor units are selected, the Index number is indicated as FF. -
Press “ ” or “ ” to select the setting item, and press “ ” to confirm the selection.
-
Press “ ” or “ ” to switch the set value.
-
Press “ ” to confirm the set value, the screen returns to Step4.
-
Press “ ” in step4 or step5 to return to home screen.
◆ Optional setting items for function selection
Element| Optional function| Individual setting| Settings|
Setting conditions| Description
---|---|---|---|---|---
| Heating temperature compensation| O| | Normal (factory setting)
(Setting Temperature + 4°C) (1)|
| No compensation
(Setting Temperature)
| Setting Temperature + 2°C (2)
| Setting Temperature + 3°C
| Setting Temperature + 1°C
| Circulation function at
heating Thermo-OFF| O| | Function disabled|
| Function enabled
| Not used| X| | –|
| Change of filter cleaning
period| O| | Standard (1200 hours) (3)|
| 100 hours
| 1200 hours (factory setting)
| 2500 hours
| No indication
| Locking of operation
mode on controller| X| | Factory setting|
| Locked (4)
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Locking of temperature
setting on remote controller| X| | Standard|
| Fixed
| Setting operation mode
as cooling Unit| X| | Usual setting|
| Locked
| Automatic COOL/HEAT operation| X| | Function disabled|
| Function enabled
| Locking of fan speed setting on controller| X| | Standard|
| Locked
| Not available| —| _| Not available (Use as 00 setting conditions)|
| Cooling setting temperature
compensation| X| | No compensation (factory setting)|
| Setting temperature decreased by 1°C
| Setting temperature decreased by 2°C
| Not used| —| | –|
| Not used| —| | –|
| Not used| —| | –|
| Not used| —| | –|
| Not used| —| –| Not available (Use as 00 setting conditions)| —
| Not used| —| | –|
| Not used| —| | –|
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Static pressure selection / Increase of Fan Hi speed| 0| | Standard static
pressure / Standard speed|
| High static pressure / Hi speed 1 (*5)
| Low static pressure / Hi speed 2
| Increase of fan speed at heating Thermo-OFF| 0| | Function disabled|
| Function enabled
| Cancellation of 3 minutes compressor operation delay| 0| | Standard|
| Cancellation
| Sensor selection for indoor temperature
control| 0| | Indoor air inlet sensor / Average air inlet-TH M4|
| Wired controller sensor / THM4 (remote sensor)|
| Average return air sensor and controller sensor or remote sensor|
| Not used| —| –| Not available (Use as 00 setting conditions)|
| Not used| —| –| Not available (Use as 00 setting conditions)|
| Selection of forced stoppage logic| 0| | Normally Open|
| Normally Closed
| Not used| —| | –|
| Not used| —| | –|
| Not used| —| | –|
| Modification of louver swing angle| 0| | Standard (7 steps) (factory
setting)|
| Cold draft prevention (5 steps)
| High ceilings (5 steps)
| Power supply ON/OFF – option 1| 0| | Function disabled|
| Function enabled
| Not used| —| –| Not available (Use as 00 setting conditions)| —
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Power supply ON/OFF –
option 2| | | Function disabled|
0| *| Function enabled
| Fan Control (Only for RPI-(4.0-6.0)
FSRE) (6)| | | Normal PID Fan Control| Dedicated optional function applied to
RPI units in combination with Airzone.
0| **| Zoning system specific fan control
| Prevention of low air outlet temperature in heating mode| | | Function
disabled (factory setting)|
0| | Function enabled
| Not used| | | –|
—|
| Not used| | | –|
—| ****
| Not used| —| | –|
| Not used| —| | –|
| Not used| —| | –|
| Not used| —| | –|
| Not used| —| | |
| –
| Period of indoor fan operation after cooling operation stoppage| 0| |
Disabled function (factory setting)|
| 60 minutes|
| 120 minutes|
| Not used| —| | |
| –
| Control for stop of the indoor unit fan during heating Thermo-OFF
conditions (with remote sensor)| 0| | Fan operation in Low speed|
| Fan stopped (with remote sensor) or Slow speed (without remote sensor)|
| Not used| —| | |
| –
| Not used| —| | |
|
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Indoor unit fan control during cooling
Thermo-OFF conditions| 0| | Function disabled (factory setting)|
| Low
| Slow
| Forced Thermo-ON when stopping in cooling operation| 0| | Function disabled
(factory setting)|
| Enabled
| Not used| —| | –|
| Control in “Automatic” indoor fan speed mode| 0| | Function disabled
(factory setting)|
| Enabled
| Control in “Automatic” indoor fan speed mode (supporting High 2)| 0| |
Function disabled|
| Function enabled
| Not used| —| | –|
| Automatic OFF Timer setting| X| | Function disabled (Factory setting)|
| 1 hour
| 2 hours
| •
| •
| 23 hours
| 24 hours
| 30 minutes|
| 90 minutes|
| 40 minutes| } Do not set these
when two wired
controllers are
used.|
| 45 minutes
| 50 minutes
| 55 minutes
| Remote control primary-secondary setting| X| | Primary|
| Secondary|
| Automatic reset of setting temperature (7)| X| | Function disabled|
| Function enabled|
| Automatic reset time| X| | 30 minutes (factory setting)|
| 15 minutes|
| 60 minutes|
| 90 minutes|
Element| Optional function| individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Automatic reset temperature for cooling
(8)| X| | 19°C|
| 20°C
| 21°C
| 22°C
| 23°C
| 24°C
| 25°C
| 26°C
| 27°C
| 28°C
| 29°C
| 30°C
| Automatic reset temperature for heating
(9)| X| | 17°C|
| 18°C
| 19°C
| 20°C
| 21°C
| 22°C
| 23°C
| 24°C
| 25°C
| 26°C
| 27°C
| 28°C
| 29°C
| 30°C
| Prevention of operation stoppage due to wrong operation of the remote
controller (10)| X| | Function disabled|
| Function enabled
| Lock function for operation mode selection| X| | Function disabled|
| Function enabled
| Lock function for temperature setting| X| | Function disabled|
| Function enabled
| Lock function for fan speed selection| X| | Function disabled|
| Function enabled
| Lock function for swing louver operation| | | Function disabled|
| Function enabled
| Lower limit of setting temperature for cooling
(8)| X| | 19°C (factory setting)|
---|---|---|---|---|---
| +1°C (Lower limit 20°C)
| +2°C (Lower limit 21°C)
| +3°C (Lower limit 22°C)
| +4°C (Lower limit 23°C)
| +5°C (Lower limit 24°C)
| +6°C (Lower limit 25°C)
| +7°C (Lower limit 26°C)
| +8°C (Lower limit 27°C)
| +9°C (Lower limit 28°C)
| +10°C (Lower limit 29°C)
| Upper limit of setting temperature for heating (Maximum value of setting
temperature allowed in heating)| X| | 30°C (factory setting)|
| -1°C (Upper limit 29°C)
| -2°C (Upper limit 28°C)
| -3°C (Upper limit 27°C)
| -4°C (Upper limit 26°C)
| -5°C (Upper limit 25°C)
| -6°C (Upper limit 24°C)
| -7°C (Upper limit 23°C)
| -8°C (Upper limit 22°C)
| -9°C (Upper limit 21°C)
| -10°C (Upper limit 20°C)
| -11°C (Upper limit 19°C)
| -12°C (Upper limit 18°C)
| Not used| —| | –|
| Not used| —| | |
| Not used| —| | |
| Indication of hot start| X| | Indication|
| No Indications
| Not used| —| | –|
| Not used| —| | –|
| Not used| —| | –|
| Not used| –| –| Not available
(Use as 00 setting conditions)|
---|---|---|---|---|---
| Colour of the run Colour indicator| | | Green|
| Red
| Not used| | | –|
X|
| Not used| —| | |
| Not used| X| | –|
| Not used| X| | –|
| Eco-operation (10)| X| | Function disabled (factory setting)|
| Function enabled
| Not used| —| | –|
| Not used| X| | –|
| Not used| —| | –|
| –
| Calibration of remote controller temperature sensor| X| | 0°C|
| -0.5°C|
| -1.0°C|
| -1.5°C|
| -2.0°C|
| -2.5°C|
| -3.0°C|
| -3.5°C|
| +0.5°C|
| +1.0°C|
| +1.5°C|
| +2.0°C|
| +2.5°C|
| +3.0°C|
| +3.5°C|
| 0°C|
| Upper limit for cooling temperature setting| | | 30°C (factory setting)|
---|---|---|---|---|---
| -1°C (Upper limit 29°C)
| -2°C (Upper limit 28°C)
| -3°C (Upper limit 27°C)
| -4°C (Upper limit 26°C)
| -5°C (Upper limit 25°C)
| -6°C (Upper limit 24°C)
| -7°C (Upper limit 23°C)
| -8°C (Upper limit 22°C)
| -9°C (Upper limit 21°C)
| -10°C (Upper limit 20°C)
| Lower limit for heating temperature setting| –| | 17°C (factory setting)|
| +1°C (Lower limit 18°C)
| +2°C (Lower limit 19°C)
| +3°C (Lower limit 20°C)
| +4°C (Lower limit 21°C)
| +5°C (Lower limit 22°C)
| +6°C (Lower limit 23°C)
| +7°C (Lower limit 24°C)
| +8°C (Lower limit 25°C)
| +9°C (Lower limit 26°C)
| +10°C (Lower limit 27°C)
| +11°C (Lower limit 28°C)
| +12°C (Lower limit 29°C)
| Not used| –| | –
| Not used| –| | –
| Not used| –| | –
| Not used| –| | –
| Not used| –| | –
| Selection of allowed operation modes when the control sensor of the indoor
unit is set by C8 function| 0| | All modes allowed|
| Only cooling/dry allowed
| Only heating allowed
| All modes allowed
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Not used| | | –|
—|
| Not used| | | –|
—|
| Not used| | | –|
—|
| Not used| | | –|
—|
| Not used| | | –|
—|
| Not used| —| | –|
| Operation of the louvers in energy-saving Thermo -OFF (Cooling / Dry mode)
(*11)| 0| | Direct air blow Low (factory setting)|
| Direct air blow Medium
| Direct air blow High
| Fan speed in energy- saving Thermo-OFF (cooling mode)| 0| | Function
disabled (factory setting)|
| Function enabled
| Louver swing operation during energy-saving forced Thermo-OFF| 0| | Function
disabled (factory setting)|
| Function enabled
| Not used| —| | |
| –
| Not used| —| | Not available|
| (Use as 00 setting conditions)
| Not used| —| | |
| –
| Not used| —| | |
| –
| Not used| —| | |
| –
| Not used| —| | |
| –
| Setting temperature in 0.5°C steps| X| | 0.5°C steps|
| 1°C steps|
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Temperature Unit °C/°F Selection| | | °C|
| | °F
| Temperature sensor displayed (12)| | | Inlet air thermistor (Tin)|
| | Outdoor air thermistor (Tout)
X| | Remote controller sensor (RCS)
| | Remote temperature sensor (THM4)
| Display of sensor temperature (13)| | | Function disabled|
X| | Function enabled
| Display of setting temperature when
operation mode is Fan| | | Shown|
X| | Hidden
| Not used| | | –|
—|
| Not used| X| | –|
| Not used| X| | –|
| Not used| X| | –|
| Daylight saving time| X| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| X| | |
| –
| Not used| X| | |
| –
| Not used| X| | |
|
| Not used| X| | –|
|
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Not used| | | –|
X|
| Not used| | | –|
X|
| Not used| | | –|
X|
| Not used| | | –|
–|
| Not used| –| | –|
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| X| | |
| –
| Not used| X| | |
| –
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Setback Temperature Compensation| | | 0.5°C (1°F)|
| | 1.0°C (2 °F)
| | 1.5°C (3 °F)
| | 2.0°C (3 °F)
| | 2.5°C (4 °F)
–| | 3.0°C (5 °F)
| | 3.5°C (6 °F)
| | 4.0°C (7 °F)
| | 4.5°C (8 °F)
| | 5.0°C (9 °F)
| | 5.5°C (10 °F)
| Not used| | | –|
–|
| Not used| –| | –|
| Not used| –| | –|
| Not used| –| | –|
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | |
| –
Element| Optional function| Individual
setting| Settings| Setting conditions| Description
---|---|---|---|---|---
| Not used| | | –|
|
| Not used| | | –|
–|
| Not used| | | –|
–|
| Not used| –| | –|
| Not used| –| | –|
| Not used| –| | |
| –
| Not used| –| | |
| –
| Not used| –| | –|
|
| Not used| | | |
| –
NOTE
-
O: allows for individual setting.
-
X: the setting is made for all outdoor units.
-
–: not used.
-
(*1) Temperatures for Floor Exposed Type & Floor Concealed Types are not offset. Setting temperature are used as they are.
-
(*2) The “02”, “03”, “04” settings may not be available depending on the type of indoor unit.
When connecting multiple indoor units, do separate settings. -
(*3) Standard type.
-
(*4) It is not applicable for Auto mode.
-
(*5) If Duct type models, 00= Increasing fan speed 1 (standard), 01= Increasing fan speed 2 (high static pressure), 02= Standard (low static pressure).
-
(*6) Only RPI-(4.0-6.0)FSRE units are affected: Once this optional function is activated from the remote controller (d4=1), normal fan PID control is deactivated, fan motor control starts operating with voltage as a target instead of rpm.
In this case, duty (output Vsp for fan control) is fixed and it is not recalculated in basis of the target rpm as always does.
This new feature also avoids the starting PID calculation, means that when a particular fan speed is demanded (e.g.High speed) from zoning system control to Hitachi control, the fan speed is automatically fixed without any possible oscillation. -
(*7) When the unit is restarted by the controller, the temperature automatically changes to the setting temperature of “F5” or “F6”.
-
(*8) Applicable to the fan, cooling and dry operation modes.
-
(*9) Applicable to the heating operation mode.
-
(*10) When the unit is restarted by the controller, the temperature automatically changes to the setting temperature of “F5” or “F6”.
-
(*11) Available only for 4-Way Cassette Type, 4-Way Cassette Compact Type, 2-Way Cassette Type, 1-Way Cassette Type, Ceiling Type.
-
(*12) Setting “P4” to “01”, then the temperature of selected thermistor (sensor) can be shown.
-
(*13) Setting “01” can show sensor temperature selected in “P3”.
NOTE
- On modifying the ”CF” (air outlet louver angle change) setting, restore the power supply or allow the automatic louver to make a full cycle in automatic mode to apply the optional setting.
- The changes to the optional function settings must be done after 3 minutes have passed after startup.
- It is recommended to keep track of the changes made to optional function settings, for further reference.
- The optional settings are different according to the indoor and outdoor unit models. Check to ensure that the unit has the optional setting or not.
- The optional functions with “X” mark at the individual setting column can change the condition only when “All Rooms” is set.
5.2.1 Input / Output setting
-
Press “ ” and “ ” simultaneously for 3 seconds to display input/output setting screen.
✓ If only one indoor unit is connected with the wired remote controller, step4 is displayed.
✓ If multiple indoor units are connected with the wired remote controller, step2 is displayed. -
Indoor unit selecting screen is displayed.
✓ Each indoor unit has its own index number. And the corresponding refrigerant system number and address number are displayed on the upper right corner of the screen. -
Press “ ” or “ ” to select the indoor unit by changing the “Index number”. Then press “ ” to confirm the selection.
✓ If all the indoor units are selected, the Index number is indicated as FF. -
Press “ ” or “ ” to select the setting item, and press “ ” to confirm the selection.
Setting items| Display
---|---
Input 1|
Input 2|
Output 1|
Output 2|
Output 3| -
Press “ ” or “ ” to change the set values, and press “ ” to save the setting and return to step4.
-
Press “ ” in step4 or step5 to return to home screen.
◆ Input and output number display and connectors
Input Number Display | Port | Factory Setting | Setting | |
---|---|---|---|---|
Input/Output Indication | Setting Item | Indication | ||
Input 1 | CN3 1-2 | Remote ON/OFF 1 (Level) | ||
Input 2 | CN3 2-3 | Prohibiting Remote Control after Manual Stoppage | ||
Output 1 | CN7 1-2 | Operation | ||
Output 2 | CN7 1-3 | Alarm | ||
Output 3 | CN8 1-2 | Thermo-ON for Heating |
◆ Input and output settings and display codes
Code Indicated | Input |
---|---|
Not set | |
Room Thermostat (for Cooling) | |
Room Thermostat (for Heating) | |
Remote ON/OFF 1 (Level) | |
Remote ON/OFF 2 (Operation) | |
Remote ON/OFF 2 (Stoppage) | |
Forbidding Remote Control after Manual Stoppage | |
Remote Cooling / Heating Change | |
Elevate Grille Input | |
Setback Operation | |
Not set | |
Not set | |
Operation | |
Alarm | |
Cooling | |
Thermo-ON for Cooling | |
Heating | |
Thermo-ON for Heating | |
Total Heat Exchanger | |
Elevate Grille Input | |
Fan Operation | |
Not set |
NOTE
- Change the optional setting after waiting at least three minutes elapsed time after start-up.
- Do not set the elevating grille for the total heat exchanger.
- Record the setting conditions for each input and output in the “Setting” column of the table.
5.2.2 Main remote setting
If multiple remote control groups exist in the same outdoor system, main/sub
setting is automatically allocated. Set the desired Wired Remote Controller as
the “Main” remote controller.
Using this function, a sub remote controller can be set as main.
◆ Example of a refrigeration system containing a group of multiple
controllers
Limitations can be faced with such systems as the outdoor and indoor units may
not be compatible with all the functions proposed by the wired remote
controller. Settings of some functions may also be different between a main
and a sub controller, refer to the table below for details.Main Controller — Only One Controller in Same Refrigerant
System
Sub Controller — Controller in addition to the Main Controller in the same
Refrigerant System
◆ Relation between Main/Sub controller and function settings
NOTE
Concerning main and sub controllers, the range of settings may differ for the
functions shown below.
Function | Main | Sub |
---|---|---|
Outdoor Unit Capacity Control | Power Savings Level Switch | ● |
●: Available
×: Not Available
◆ Changing from the sub controller to the main controller
- Press “ ” and “ ” simultaneously for 3 seconds to start changing from the sub controller to the main controller. The changed screen is displayed.
- When the change is completed, it returns to the home screen.
NOTE
-
When using two controllers, only the primary controller can be set as the main controller.
In cases where two controllers are both sub controllers, the “Main Remote Setting” is only accessible from the primary controller. -
In case the primary controller is a “Main Controller” and the secondary controller is a “Sub
Controller”, when the primary controller and the secondary controller are changed by the function selection, Main and Sub controllers will also be switched simultaneously. -
If the main controller “ ” icon is not displayed, the main controller may not function normally. In this case, check the connection wiring on the related wired controller.
-
If a remote control group is operating with multiple refrigerant systems, the Outdoor Unit Capacity Control function may not operate normally.
5.3 Service menu
5.3.1 Operation Lock/Unlock setting
This function disables the setting mode of the remote controller.
In the operation lock, when the lock icon “ ” is getting displayed, that means
this setting is locked and cannot be changed by the user using the “ ”, “ ”, “
” or “ ” buttons.
The following settings can be locked:
- Temperature setting (Temp)
- Operation mode (Mode)
- Fan speed
- Louver swing (Louver)
NOTE
- Don’t use the operation lock function when remote control is set to “prohibit” on the central controller.
- If both the “prohibit lock” and “prohibit remote control” operations are set at the same time, the “prohibit remote control” operation has priority.
- If the setting is changed from “prohibit remote control operations” to “permit all remote control operations”, all operation locks are released.
-
Set Operation Lock.
✓ Press “ ”, “ ” and “ ” simultaneously for 3 seconds, the lock icon “ ” lights up and the operation lock is in valid. -
Set Operation Unlock.
✓ Press “ ”, “ ” and “ ” simultaneously for 3 seconds, the lock icon “ ” lights up and the operation unlock is in valid.
5.3.2 NFC setting
The default setting of NFC is “Disabled”. When using NFC, the function should
be enabled firstly.
Once enabled, there is no need for subsequent enabling process because of its
memory function.
Please refer to related manual of airCloud Tap for the operation method of
NFC, when available.
NOTE
- NFC is the abbreviation of “Near field communication”. NFC can improve service and installation.
- If the wired remote controller may be accessible to unauthorized third-party, please set the NFC to “Disabled”.
◆ Enable NFC function (if NFC is in disabled state)
- Press “ ” and “ ” simultaneously for 3 seconds to display NFC setting screen.
- Press “ ” or “ ” to enable / disable NFC.
NFC OFF/ON state code is indicated on the screen.State Code| State Description
---|---
| NFC mode is disabled
| NFC mode is enabled - Press “ ” to complete the setting and return to the home screen.
NOTE
- When NFC is OFF, “ ” is displayed on the home screen.
- When NFC is ON, “ ” is displayed on the home screen.
◆ Start NFC
- Press “ ” and “ ” simultaneously for 3 seconds to display NFC function screen, which indicates wired controller can start to receive NFC data from the App.
- Use NFC App airCloud Tap in your smartphone to write data. Please refer to the related manual of airCloud Tap App for the detailed operation, when available.
✓ If all data received from the App cannot be written to the controller, NFC alarm screen is displayed.
Alarm Code | Alarm Description |
---|---|
An anomaly has occurred in the operation of NFC. | |
NFC function is not supported. | |
Other issue. |
✓ Under NFC alarm state, press “ ” to confirm the warning and it returns to
NFC function screen. The controller can restart to receive data.
✓ If the data received from the App can be written to the wired remote
controller, data writing confirmation screen is displayed. On the screen, NFC
icon keeps flashing. ✓ Under the state of data writting confirmation screen,
press “ ” to confirm to write data and the screen returns to NFC function
screen.
NOTE
Flashing NFC icon indicates the controller is receiving the data from a phone.
5.4 Check menu
This menu displays various statuses of the air conditioner.
Item | Function |
---|---|
Check 1 | Sensor condition of the heat pump are monitored and displayed. |
Check 2 | Sensor data from the heat pump prior to alarm occurrence is |
displayed.
-
Press “ ” and “ ” simultaneously for 3 seconds to display the check screen.
-
Press “ ” or “ ” to select “Check 1” or “Check 2” and press “ ” to turn to next step.
-
Indoor unit selecting screen is displayed if multiple indoor units are connected.
✓ Each indoor unit has its own index number.
✓ The corresponding refrigerant system number and address number are displayed on the upper right corner of the screen. -
Press “ ” or “ ” to select the indoor unit by changing the “Index No.”. Then press “ ” to confirm the selection.
-
Press “ ” or “ ” to switch the check item and check data.
-
Press “ ” to return to home screen.
In alarm condition
6.1 Alarm display
- The RUN indicator on the wired remote controller turns from green to red.
- Alarm icon is displayed and keeps flashing.
- The indoor unit number and alarm code are displayed on the screen.
- When the wired remote controller is connected to more than one indoor unit, press “ ” to switch to the next unit.
6.2 Power failure
- All the indicators are OFF.
- Once the air conditioner is stopped by power failure for longer than 2 seconds, the air conditioner is not started again, although power recovers. Perform the starting procedures again.
- If the power recovers within 2 seconds, the air conditioner starts again automatically.
6.3 Electromagnetic interference (EMI)
- There could be an instance where all the indications are OFF and the unit is stopped.
- This can occur through activation of the microcomputer for the air conditioner protection from the Electromagnetic Interference (EMI).
- Perform the starting procedures again.
Checking functions
7.1 List of installation functions
Item | Description |
---|---|
Test Run | To perform a test run of the outdoor unit and indoor unit. |
Function Selection | To set Function Selection for the outdoor unit, indoor |
unit, and wired remote controller.
Input/Output| To assign signals to the external input/output ports of the
indoor unit.
Indoor Unit Address Change| To change the indoor unit address and refrigerant
system number.
Setting Initialization| Select indoor unit address to restore factory default
settings for function selection and input/output on indoor unit and wired
remote controller.
Main Controller Setting| To change the sub remote controller to the main
remote controller.
Do not operate the air conditioner except for the test run
7.1.1 Indoor unit address change
This function is used to change the indoor unit address.
NOTE
- When using two controllers (the main and sub remote controllers), Indoor Unit Address Change is not available.
- Address may not be changed on some indoor unit types.
- Do not operate from the central controller in the mode of Indoor Unit Address Change.
- Eco compact wired remote controller doesn’t support Address Check Operation and Indoor Unit Address Initialization.
- Refrigerant system “99” is used to temporarily save the address when the refrigerant system number or address number of the indoor unit are all used (there is no vacant space).
After setting Refrigerant System “99”, be sure to change the address within the normal range.
-
Press “ ” and “ ” simultaneously for 3 seconds.
✓ For the indoor units without address change function, this operation is invalid. -
Indoor unit selecting screen is displayed. ✓ If there is only one indoor unit connected to the wired remote controller, this screen is not displayed. (The screen in step4 is shown.)
✓ Each indoor unit has its own index number. And the corresponding refrigerant system number and address number are displayed on the upper right corner of the screen. -
Press “ ” or “ ” to select the indoor unit by changing the “Index number”. Then press “ ” to confirm the selection.
✓ For the indoor units without address change function, this operation is invalid. -
Select the “Address No.” of the indoor unit to be changed.
-
Press “ ” to select the setting items “Indoor Unit number” (refrigerant system) ↔ “Address No.” of the selected unit.
-
Press “ ” or “ ” to change the “Indoor Unit number” (refrigerant system) and “Address number” of the selected unit within the range of 00 to 63.
✓ The selected setting item keeps flashing. -
Press “ ” to start the indoor unit address changing process and the result is displayed.
✓ “P5” indicates that the address changing process is completed and successful. ✓ “FL” indicates that the address changing process is abnormal and failed. -
When need to continue multiple indoor units address changing or to end the operation, press “ ” or “ ” to select “bk” or “Ed”. ✓ To continue other indoor unit address changing, select “bb” and press “ ” to return to the step2.
✓ To end the operation, select “Ed” and press “ ” to confirm the selection. -
Turn OFF the indoor unit 3 to 5 minutes after step7.
After all indicators on the remote controller are OFF, turn ON the power of the indoor unit again.
7.1.2 Setting initialization
This function is used to restore the factory default settings of Function
Selection and Input/Output.
NOTE
- The history display on the “Function Selection” screen is also updated to the factory default setting.
- If the indoor unit that does not support Setting Initialization is selected, the factory default settings of Function Selection and Input/Output is not available.
- Even if “All indoor units” are selected, the settings of Function Selection and Input/Output for the indoor unit that does not support Setting Initialization cannot be initialized to the factory default settings.
-
Press “ ” and “ ” simultaneously for 3 seconds.
NOTE
• Use this function only when setting restored to the factory default settings causes no problem and inconvenience.
• For the indoor units without setting initialization function, this operation is invalid. -
Indoor unit selecting screen is displayed if multiple indoor units are connected. ✓ If there is only one indoor unit connected to the wired remote controller, this screen is not displayed and the screen in step3 is shown.
-
Indoor unit selecting screen is displayed if one indoor unit is connected.
-
Press “ ” or “ ” to select the indoor unit by changing the “Index No.”. Then press “ ” to confirm the selection.
✓ Each indoor unit has its own index number. The corresponding refrigerant system number and address number are displayed. -
Wait for approximately 30 seconds after the initialization starts.
-
When the initialization is completed, the screen returns to home screen.
7.2 List of check functions
Item | Description |
---|---|
Check 1 | Sensor condition of the air conditioner is monitored and indicated. |
Check 2 | Sensor data of the air conditioner prior to alarm occurrence is |
indicated.
Alarm History Display| Alarm History Display Alarm record data: (date, time,
and alarm code) is displayed.
Up to 30 records can be recorded.
Self Check| Checking of wired controller is carried out.
7.2.1 Check 1 / Check 2
-
Press “ ” and “ ” simultaneously for 3 seconds to display the check screen.
-
Press “ ” or “ ” to select “Check 1” or “Check 2” and press “ ” to turn to next step.
-
Indoor unit selecting screen is displayed if multiple indoor units are connected.
✓ Each indoor unit has its own index number.
✓ The corresponding refrigerant system number and address number are displayed on the upper right corner of the screen. -
Press “ ” or “ ” to select the indoor unit by changing the “Index number”. Then press “ ” to confirm the selection.
-
Press “ ” or “ ” to switch the check item and check data.
-
Press “ ” to return to home screen.
◆ Checking the current operating condition
Contents of Check 1
Press “ ” to go to the next page. Press“ ” to go to the previous
page. ◆ Cause of indoor unit stoppage
Code | Cause |
---|---|
Operation OFF, Power OFF | |
Thermo-OFF | |
Alarm (*1) | |
Freeze Protection, Overheating Protection | |
Instantaneous Power Failure at Outdoor Unit/Reset (*2) | |
Instantaneous Power Failure at Indoor Unit/Reset (*3) | |
Stoppage of Cooling Operation due to Low Outdoor Air Temperature Stoppage of |
Heating Operation due to High Outdoor Air Temp.
| Stoppage of Reversing Valve Switching Control
| Demand Enforced Stoppage
| Retry due to Pressure Ratio Decrease
| Retry due to Low Pressure Increase
| Retry due to High Pressure Increase
| Retry due to Abnormal Current of Constant Speed Compressor
| Retry due to Vacuum Abnormality, Discharge Gas Temperature Increase
| Retry due to Decrease of Discharge Gas Superheat
| Retry due to Inverter Tripping
| Retry due to Voltage Decrease, Other Retry of Inverter
| Expansion Valve Opening Change Protection
| Operation Mode Difference between IDU and ODU/ Stoppage of Operation Mode
Switching during Operation
| Enforced Thermo-OFF (*4)
| Enforced Thermo-OFF (Hot Start Control at Crankcase Heater Preheating)
| Enforced Stoppage of compressor due to DIP switch (DSW) Setting
| Thermo-OFF during Energy-Saving Operation
| Retry due to High Pressure Decrease
| Retry due to Operation of Outdoor Blower Protector
| Stoppage due to Outlet temperature Decrease in Cooling
| Retry due to Abnormal Current during MS Motor Synchronous Operation
| Stoppage of Thermo-OFF due to Compressor Excepting
| Retry due to Abnormal Transmission of Outdoor Unit
Code| Cause
---|---
| Enforced Thermo-OFF due to Enforced Cleaning Operation
| Stoppage of Thermo-OFF by Motion Sensor
| Retry due to Abnormal Refrigeration Cycle
| Retry after Defrosting Operation
| Enforced Stoppage
| Thermo-OFF stop by indoor rotation control in power saving mode
Thermo-OFF stop by intermitent operation control in power saving mode
| Enforced Thermo-OFF Stoppage due to GentleCool Comfort at Indoor Unit
| Enforced Thermo-OFF Stoppage of the Connecting Indoor Unit due to PumpDown
at Outdoor Unit
| Enforced Thermo-OFF Stoppage of Cooling/Heating Operation in frostWash Mode
| Enforced Thermo-OFF Stoppage due to Econo Fresh
NOTE
(1) Even if stoppage Alarm “02” is not always indicated. If the unit is
Thermo-OFF due to another cause of stoppage prior to alarm occurrence, the
code of the cause remains.
(2) The outdoor unit equipped with an inverter resets ODU Micro-Computer if
the transmission between inverter PCB and outdoor unit PCB is interrupted for
30 seconds. Therefore, the stoppage cause code when Alarm 04 occurs may be
“05”.
(3) IDU Micro-Computer is reset if the transmission between the indoor unit
and the outdoor unit is interrupted for 3 minutes. Therefore, the stoppage
cause code when Alarm 03 occurs may be “06”.
(4) If the stoppage cause code “21” is indicated on the indoor unit of twin,
triple, or quad, check the stoppage cause of other indoor unit
numbers. Indoor unit capacity
code
Code | Indoor unit capacity number | Equivalent horse power |
---|---|---|
22 | 0.8 | |
28 | 1.0 | |
36 | 1.3 | |
40 | 1.5 | |
45 | 1.8 | |
50 | 2.0 | |
56 | 2.3 | |
63 | 2.5 | |
71 | 2.8 | |
80 | 3.0 | |
90 | 3.3 | |
112 | 4.0 | |
140 | 5.0 | |
160 | 6.0 | |
200 • 224 | 7.5 • 8.0 | |
280 | 10.0 |
◆ The data just before the latest failure
Contents of Check 2
Press “ ” to go to the next page. Press “ ” to go to the previous
page. 7.2.2 Alarm history
display
Alarm history can be browsed and deleted.
- Press “ ” for 3 seconds to display alarm history.
- Press “ ” or “ ” to switch “Alarm History Display” screen. ✓ Alarm history number starts with the latest alarm. 01 stands for the latest alarm.
- To delete alarm history, press “ ” and “ ” simultaneously for 3 seconds in the “Alarm History Display” screen.
- Press “ ” to return to home screen.
7.2.3 Self check
Self check and EEPROM (internal memory element of wired remote controller)
clear are provided.
Please note that the check is processed under the condition of “Operation
Stop” state.
Software version check
- Press “ ”, “ ” and “ ” simultaneously for 3 seconds on home screen to show software version in area Ⓒ and the number in area Ⓐ.
- Press “ ” to go to next check.
- Press “ ” and “ ” simultaneously for 3 seconds, the EEPROM is cleared.
LCD check
The number in area Ⓐ is 02.
- Press “ ” to turn on all icons.
- Press “ ” to go to next check.
Backlight check
The number in area Ⓐ is 03.
- Press “ ” to turn off the backlight.
- Press “ ” to go to next check.
Run indicator check
The number in area Ⓐ is 04.
- Press “ ” and run indicator LED switch between green and red.
- Press “ ” to go to next check.
Touch key and buzzer check
The number in area Ⓐ is 05.
- Press each key once a time in the sequence as follows:
- The number in area Ⓑ increases by 1 with each switch pressing.
NOTE
- The number increases regardless of the order of the switch pressing. The switch pressing is not counted if 2 or more switches are pressed simultaneously.
- When press the button, the buzzer sounds.
- If this step check is normal, the screen will go to next check automatically.
Transmission check
The number in area Ⓐ is 06.
The wired remote controller then automatically starts communication circuit
checking.
✓ If the communication circuit check is abnormal, “FF” will be displayed at
area Ⓑ and this status normally stays for 5 seconds.
✓ If this step check is normal, the screen will go to next check
automatically. Thermistor check
The number in area Ⓐ is 07.
- The temperature on the remote controller thermistor is shown in area Ⓑ.
- Press “ ” to go to next check.
NOTE
The thermistor temperature is the same as ambient temperature and the
tolerance is ±1°C.
RTC check
The number in area Ⓐ is 08.
- The area Ⓒ displays “12:34”.
- Press “ ”, “00:00” is displayed in area Ⓒ.
- Press “ ” to go to next check.
IR check
The number in area Ⓐ is 09. ✓ Not
check IR
Press “ ” and “ ” simultaneously for 3 seconds and the screen turns to next
check directly.
✓ Check IR
If the signal of the wireless remote controller is detected, the screen moves
to next check automatically.
NFC check
The number in area Ⓐ is 10. ✓ Not
check NFC
Press “ ” and “ ” simultaneously for 3 seconds and the screen turns to next
check directly.
✓ Check NFC
◉ If “FF” is displayed in area Ⓑ, it means that the NFC has failed. Please
enable NFC on the smartphone and bring it closer to the LCD of the wired
remote controller.
◉ If an NFC signal is detected, the screen will move to the next check
automatically.
EEPROM check
The number in area Ⓐ is 11. ✓ Not
clear EEPROM
Press “ ” and “ ” simultaneously for 3 seconds and the screen turns to home
screen.
✓ Check EEPROM
Press “ ” to start EEPROM check.
◉ If there is an error during EEPROM check, “FF” is displayed in area Ⓑ and
the screen will not turn to next step automatically.
After seconds, wired remote controller automatically finishes self check
process and restarts.
7.2.4 Reset wired remote controller
To delete the settings of Wired Remote Controller or re-connect the controller
to the unit, follow the below steps to reset the controller.
NOTE
It is not possible to delete only part of the record data by resetting.
-
Press “ ”, “ ” and “ ” simultaneously for 3 seconds when Wired Remote Controller is at home screen, under the condition of “Operation Stop” state.
-
Press “ ” and “ ” simultaneously for 3 seconds again, Wired Remote Controller starts EEPROM clear process.
The number in area Ⓐ is 13. -
After EEPROM is cleared, the screen automatically changes and Wired Remote Controller restarts.
Johnson Controls-Hitachi Air Conditioning Spain, S.A.U.
Ronda Shimizu, 1 – Políg. Ind. Can Torrella
08233 Vacarisses (Barcelona) Spain
© Copyright 2023 Johnson Controls-Hitachi Air Conditioning
Spain, S.A.U. – All rights reserved.
Printed in China
PMEN0630 rev.0 – 03/2023
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>