1 SAFETY INFORMATION
1.1 SAFETY WARNINGS
NOTE!
- Only use the expansion plug-in module for analog, digital and relay inputs and outputs (CFW500-IOR-B) on WEG inverters of the CFW500 line.
- We recommend reading the CFW500 user’s manual before installing or operating this accessory.
- This guide contains important information for the correct understanding and proper operation of this module.
1.2 PRELIMINARY RECOMMENDATIONS
⚠ ATTENTION!
- Always disconnect the general power supply before connecting or disconnecting the accessories of the frequency inverter CFW500.
- Wait for at least 10 minutes to guarantee complete reenergization of the inverter.
2 GENERAL INFORMATION
This guide provides instructions for the installation, configuration and operation of the plug-in expansion module for digital relay outputs (CFW500-IOR-B).
3 CONTENTS OF THE PACKAGE
When receiving the product, check if this package contains:
- Accessory in anti-static packaging.
- Installation, configuration and operation guide.
4 ACCESSORY INSTALLATION
The accessory is easily installed or replaced. For correct installation of the accessory execute the following steps:
Step 1: with the inverter de-energized, remove the front cover of the Inverter
(figure A.1 (a)).
Step 2: remove the accessory (connected plug-in module) if any, as in figure
A.1 (a).
Step 3: fit and press the accessory to be installed as indicated in figure A.1
(b) and then assemble the front cover of the inverter.
Step 4: power up the inverter and check if parameter P0027 shows value 4
(P0027 = 4). If this information is not true, check if the module used is
actually the CFW500-IOR500 and repeat steps 1-4.
5 SETTINGS
The control connections (analogical input / output, digital inputs / outputs and RS485 interface) must be performed as shown in figure 2.
The location of the DIP switches to select the kind of analog output and input
signal can be better viewed in figure A.2. To use the analog inputs and/ or
outputs with signal in current, switch S1 and related parameters must be set
as indicated in table 1. For further details about the control connections see
chapter 3 – Installation and Connection of the CFW500 user’s manual.
NOTE! The digital input signal DI5 is always NPN input instead of P0271
configuration.
This module has a connector (figure A.2) to enable the use of the Flash Memory Module (CFW500-MMF), which allows data transfer between inverters. For further details on this accessory, refer to the installation, configuration and operation guide of the CFW500-MMF.
APPENDIX A