Specifications

  • Model Number: PDU3XVSR6G20

  • Input Phase: 3-Phase 360; 380; 400; 415

  • Input Voltage: Three-phase 16A 360-415V service

  • Maximum Input Amps: 16A

  • PDU Plug Type: IEC-309 16/20A RED (3P+N+E)

  • Input Cord Length: 6 ft. (1.83 m)

  • Output Capacity: 11.5kW (415/240V), 11.1kW (400/230V), 10.5kW
    (380/220V), 10kW (360/208V)

  • Frequency Compatibility: 50 / 60 Hz

  • Output Receptacles: (24) C13; (6) C19

  • Output Nominal Voltage: 208-240V

Product Usage Instructions

Installation

  1. Mount the vertical rackmount PDU using the pre-installed mounting buttons.
  2. Secure power cables with the Plug-lock cable retention inserts.
  3. Connect the input cord to a compatible power source.

Configuration

  1. Connect the configuration cable to set up the PDU.
  2. Use the built-in web/network interface to configure power-on, power-off sequences, and load management.

Usage

  1. Access the local digital display or remote web interface to monitor voltage, amperage, and load levels.
  2. Control each outlet individually for power-on, power-off, or reboot actions.
  3. Utilize the color-coded and labeled outlets for easy identification of phases and load banks.

Highlights

  • Switched 11.5kW 3-Phase 360-415V input 208-240V output PDU
  • Reports voltage, frequency & load per-outlet and per phase via ethernet interface
  • 1% billing-grade accuracy; Digital display reports detailed status and loading information
  • 70in / 1778mm 0U vertical format; Toolless button-mount installation
  • 24 C13 & 6 C19 single phase outlets; Plug-lock cable retention inserts keep power cables secure
  • IEC309 16/20A Red (3P+N+E) 3 phase input; 6-ft. (1.83 m) line cord
  • TAA Compliant

Package Includes

  • Switched, vertical rackmount PDU with pre-installed mounting buttons
  • 24 C13/C14 and 6 C19/C20 Plug-lock cable retention inserts
  • Spare installation buttons (2 9mm / 4 6mm), Mounting brackets
  • Configuration cable
  • Owner’s manual

Features

  • 11.5kW Switched 360-415V input 208-240V output PDU with built-in web/network interface
  • IEC309 16/20A Red (3P+N+E) 360-415V 3 phase input with 6 ft. / 1.8m line cord
  • 0U, 70 inch / 178cm vertical form factor
  • 30 switched 208-240V outlets (24 C13, 6 C19) in 3 single phase load banks
  • Supports power-on, power-off or reboot of each outlet on a real-time or programmable basis
  • DHCP/Manual configuration support
  • 10/100 Mbps auto-sensing
  • Real-time clock backup maintains the time of day and date even if the PDU is unpowered
  • Tiered access privileges allow an administrator and a guest to login via web browser
  • Alert notifications via email or SNMP traps offer immediate event notification
  • Firmware upgrade ability supports future product enhancements
  • Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, SNMPv3, Telnet, SSH, FTPP, DHCP, BootP, NTP protocols
  • Fully compatible with FREE PowerAlert Network Management System / NMS Software
  • Included set of Plug-lock inserts keep C14 and C20 power cords solidly connected to PDU outlets Toolless mounting supported in button-mount compatible racks, plus nut-and-bolt mounting brackets for other mounting applications (set of 2 9mm buttons pre-installed, 2 9mm and 4 6mm spare buttons included)
  • Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases

Specifications


OVERVIEW


UPC Code| 037332180254
PDU Type| Switched


INPUT

Input Phase| 3-Phase
PDU Input Voltage| 360; 380; 400; 415
Recommended Electrical Service| Three-phase 16A 360-415V service
Maximum Input Amps| 16
Maximum Input Amps Details| Agency de-rated to 16A continuous
PDU Plug Type| IEC-309 16/20A RED (3P+N+E)
Input Cord Length (ft.)| 6
Input Cord Length (m)| 1.83


OUTPUT

Output Capacity Details| 11.5kW (415/240V), 11.1kW (400/230V), 10.5kW (380/220V), 10kW (360/208V) total capacity; 16A max per output phase (L1-L2, L2-L3, L3-L1); 16A max per C19 outlet; 12A (10A CE) max per C13 outlet
Frequency Compatibility| 50 / 60 Hz
Output Receptacles| (24) C13; (6) C19
Output Nominal Voltage| 208-240V
Customized Load Management Receptacles| ****

Each outlet is individually controllable via remote interface


USER INTERFACE, ALERTS & CONTROLS

Reported Load Segments| Reports input current per phase (L1, L2, L3), plus output current for each output load bank (16A balanced max per B1-B3) and individual output receptacle (1-30); Outlets are color-coded and labeled for phase and load bank identification; L1-N feeds black outlets (B1); L2-N feeds dark-gray outlets (B2); L3-N feeds light-gray outlets (B3)
Front Panel LCD Display| Large digital display reports Amperage, Kilowatts, Voltage, Unbalance percentage, Temperature and Humidity information (*requires ENIVIROSENSE option); Small digital display provides detail on the measurement the large display is reporting: Input-phase (L#), Load bank (B#), Sensor (S#), Outlet (##), Load unbalance % (UB), Output power (OP)
Front Panel LEDs| Set of 6 LEDs identify the value displayed on the large digital display: Amperage (A), Kilowatts (kW), Voltage (V), Unbalance percentage (%UB), Temperature (T), Humidity (%RH); One additional LED for each output receptacle offers power availability information: GREEN (Power ON, load bank capacity <80%), YELLOW (Power ON, load bank capacity >80%), RED (Power OFF/undervoltage), RED FLASHING (Power OFF/breaker trip)
Switches| Set of UP/DOWN arrow buttons scroll through available Input, Bank, Power, Load balance and Sensor options; Additional MODE button advances the LEDs to view the next measurement
Current Measurement Accuracy (Amps)| ****

+/-1%

---|---
Voltage Measurement Accuracy (Volts)| ****

+/-1%

Power Measurement Accuracy (Watts)| ****

+/-1%


SURGE / NOISE SUPPRESSION

Automatic Shut-Off| No


PHYSICAL

Material of Construction| Metal
Form Factors Supported| Vertical rackmount installation supported with included mounting brackets; supports toolless mounting in button- mount compatible racks
PDU Form Factor| Vertical (0U)
Shipping Dimensions (hwd / in.)| 6.89 x 9.65 x 75.87
Shipping Dimensions (hwd / cm)| 17.50 x 24.51 x 192.71
Shipping Weight (lbs.)| 21.25
Shipping Weight (kg)| 9.64
Unit Dimensions (hwd / in.)| 70.000 x 2.170 x 2.860
Unit Dimensions (hwd / cm)| 177,8 x 5,51 x 7,3
Unit Weight (lbs.)| 14.5
Unit Weight (kg)| 6.58


ENVIRONMENTAL

Operating Temperature Range| 0C ~ 50C (32F ~ 122F)
Storage Temperature Range| -30°C to +60°C (-22°F to +140°F)
Relative Humidity| 5-95% non condensing
Operating Elevation| 0-10,000


COMMUNICATIONS

PowerAlert Software| SNMPWEBCARD Interface: PowerAlert 12
Communications Cable| RJ45-to-DB9 configuration/console Access cable
Network Compatibility| 10 Mbps; 100 Mbps (Fast Ethernet)


FEATURES & SPECIFICATIONS

High Availability PDU Features| Auto Load Shedding


STANDARDS & COMPLIANCE

Product Certifications| EN 60950-1; CSA (Canada); NOM (Mexico); UL 60950-1
Product Compliance| RoHS; CE (Europe); FCC Part 15 Class A (USA)


WARRANTY & SUPPORT


Product Warranty Period (Worldwide)| ****

2-year limited warranty

Contact Information

1000 Eaton Boulevard Cleveland, OH 44122 United States
https://tripplite.eaton.com

© 2024 Eaton. All Rights Reserved.
Eaton is a registered trademark. All other trademarks are the property of their respective owners.

Frequently Asked Questions

Q: Can I control each outlet separately?

A: Yes, you can control each outlet individually for power-on, power-off, or reboot actions using the remote interface.

Q: What is the maximum input amperage supported?

A: The PDU supports a maximum input amperage of 16A with a three-phase 360-415V service.

Q: Is the PDU compliant with TAA regulations?

A: Yes, the PDU is TAA Compliant, making it suitable for GSA Schedule purchases.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals