Unipos 7000M Loop Controller Instruction Manual

May 15, 2024
Unipos

Unipos 7000M Loop Controller Instruction Manual

General description

Module Loop Controller contains two loops. Each loop can support up to 210 addresable devices M series. Please see the User Manual 7000M for more information

Installing module on DIN rail
Instructions

After mounting on the DIN rail, slide carefully and connect with the front one module

**Installation
Installation
Dismantling
Dismantling

**

Module
LoopController| 1| 2| 3| 4| 5| 6| 7| 8| 9| 10| 11| 12| 13| 14| 15| 16
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| Loop 1″i-*
start| Earth| Loop 1.•-•
start| Loop r+-
end| Earth| Loop l’-‘
end| Loop 2’+’
start| Earth| Loop 2″-–
start| Loop 2’+’
end| Earth| Loop 2′-‘
end| NOT
USED| NOT
USED| Earth| Earth

Technical data

C onnecting type DIN rail
Connecting line to loop two-wire shielded ­re rated cable (recommended 0,75 –

1.5mm²).Connecting line to loop
Loops per module| 2
Modules per panel| 5
Maximum resistance of a loop(incl. all contacts and build-in isolators)| 28Ω (- wire) / (210 devices, 1.5mm², 2 100 m distance) 60Ω (+ wire)
Maximum Consumption from one loop| 300mA/24VDC
Power supply (ensured by PSU module)| (27,6 +1/-8) VDC
Total module outputs comsumption| please see p.2.5 User Manual 7000M