General description
Module Loop Controller contains two loops. Each loop can support up to 210 addresable devices M series. Please see the User Manual 7000M for more information
Installing module on DIN rail
After mounting on the DIN rail, slide carefully and connect with the front one module
**Installation
Dismantling
**
Module
LoopController| 1| 2| 3| 4| 5| 6| 7| 8| 9| 10| 11| 12| 13| 14| 15| 16
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
| Loop 1″i-*
start| Earth| Loop 1.•-•
start| Loop r+-
end| Earth| Loop l’-‘
end| Loop 2’+’
start| Earth| Loop 2″-–
start| Loop 2’+’
end| Earth| Loop 2′-‘
end| NOT
USED| NOT
USED| Earth| Earth
Technical data
C onnecting type | DIN rail |
---|---|
Connecting line to loop | two-wire shielded re rated cable (recommended 0,75 – |
1.5mm²).Connecting line to loop
Loops per module| 2
Modules per panel| 5
Maximum resistance of a loop(incl. all contacts and build-in isolators)| 28Ω
(- wire) / (210 devices, 1.5mm², 2 100 m distance) 60Ω (+ wire)
Maximum Consumption from one loop| 300mA/24VDC
Power supply (ensured by PSU module)| (27,6 +1/-8) VDC
Total module outputs comsumption| please see p.2.5 User Manual 7000M