UniPOS 7000M Addressable Modular System Panel Owner’s Manual
- July 23, 2024
- Unipos
Table of Contents
UniPOS 7000M Addressable Modular System Panel Owner’s Manual
The Addressable Modular System Panel 7000M is designed to satisfy a professional solution enhancing:
- Installation procedure with set-up flexibility
- 2-10 loop capability
- Supplied with 2 loops as standard
- Add up to 4 more loop module cards to increase panel capacity to a maximum of 10 loops
- Certified to EN54-2/4/13
Product is also available with a printer – Part Number: 7000M-P
Technical Features
Number of Loop Addressable Devices per Loop | up to 210 pcs |
---|---|
Number of Loop Addressable Devices per Panel | up to 2,100 pcs |
Number of Loop Modules per Panel | up to 5 (total 10 loops) |
Number of Loop Modules per System | up to 64 |
Number of BIO Modules | up to 5 per panel |
Number of Addressable Devices per System | up to 13,440 p c s |
Detection Zone | contain up to 32 loop detectors, fire inputs or/and manual |
call points
Detection Zones per Panel / System| up to 1,023 / 30 per loop
Configurable Week Schedule (Day / Night Mode)| sensitivity and logic change to
detectors, delays change in alarm zones
Protection Zones per Panel / System| up to 1,023 / 30 per loop
Protection Zones peí Panel / System| up to 1,023 / 30 per loop
Protection Zones per Panel / System| redundant CAN network supports up to 16
panels and up to 13,440 detectors
Maximum Number of Addressable and Conventional Fire Alarm Devices| up to 35
per loop, up to 350 per panel connected to the loops – conventional and
addressable devices (sounders)
Dependencies on more than one alarm signal| CI Mode B (detecting fire by
two zones activation)
CI Mode C (detecting fire with inspection time)
Alarm Counter| up to 9,999 (can be deleted by script at level access 4)
Event Log (archive)| 10,000 events
Configurable Output to Fire Protection Equipment (addressable output device)
| LED indication for activation
---|---
input for the reception of a confirmatory signal from fire protection
equipment, indicated by means of separate indicator
Other Features
| alarm zones and protection zones can be activated from any detection Zones
(one detection zone cannot activate two alarm zones)
configurable sounder melodies in alarm and prealarm state (Warning-state) for
every Alarm zone.
output to fire alarm devices
alarm confirmation input from fire alarm routing equipment
fault monitoring fire protection equipment (in/out)
delay to outputs, day / night mode
fault signals from points
total loss of power supply
output to fault warning routing equipment
disablement of addressable points
1 Efr. Nikola Paskalev Str, Mladost 1
Sofia 1748, Bulgaria
Telephone: +359 2 97 439 2
Email: sales@unipos-bg.com
Website: www.unipos-bg.com